GE Pqm 2 Manual
Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–35 •DETECT I/V ALARMS USING PERCENTAGE: When “Yes” is selected, all current and voltage alarms can be set in percentages of CT and VT. When “No” is selected, all current and voltage alarms are actual voltage and current levels. •PHASE UNDERCURRENT RELAY: Undercurrent can be disabled, used as an alarm, or as a process control feature. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever an undercurrent condition exists. Selecting an auxiliary relay activates the selected auxiliary relay for an undercurrent condition but no message will be displayed. This is intended for process control. •PHASE UNDERCURRENT LEVEL: When the average three phase current drops to or below the level set by this setpoint , a phase undercurrent condition will occur. Refer to the DETECT UNDERCURRENT WHEN 0A setpoint description below to enable/disable undercurrent detection below 5% of CT. •PHASE UNDERCURRENT DELAY: If the average phase current is less than or equal to the PHASE UNDERCURRENT LEVEL setpoint value for the time delay programmed in this setpoint , a phase undercurrent condition will occur. MESSAGEDETECT UNDERVOLTAGE BELOW 20V: NORange: No, Yes MESSAGEOVERVOLTAGE RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEOVERVOLTAGE LEVEL ≥ 100 VRange: 20 to 65000 V in steps of 1, or 20 to 150% of VT in steps of 1, set by the DETECT I/V ALARMS USING PERCENTAGE value. MESSAGEOVERVOLTAGE DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEPHASES REQ’D FOR O/V OPERATION: ANY ONERange: Any One, Any Two, All Three. Not seen when VT WIRING is set to “Single Phase Direct” MESSAGECURRENT UNBALANCE RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGECURRENT UNBALANCE LEVEL ≥ 100%Range: 1 to 100% in steps of 1 MESSAGECURRENT UNBALANCE DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEVOLTAGE UNBALANCE RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEVOLTAGE UNBALANCE LEVEL ≥ 100%Range: 1 to 100% in steps of 1 MESSAGEVOLTAGE UNBALANCE DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEVOLTS PHASE REVERSAL RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEVOLTS PHASE REVERSAL DELAY: 1.0 sRange: 0.5 to 600.0 s in steps of 0.5
5–36PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS •DETECT UNDERCURRENT WHEN 0A: If this setpoint is set to “Yes”, undercurrent will be detected if the average phase current drops below 5% of CT. If the setting is “No”, the undercurrent detection is only enabled if the average phase current is equal to or above 5% of CT. •PHASE OVERCURRENT RELAY: Overcurrent can either be disabled, used as an alarm or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever an overcurrent condition exists. Selecting an auxiliary relay activates the auxiliary relay for an overcurrent condition but no message will be displayed. This is intended for process control. •PHASE OVERCURRENT LEVEL: When the average (or maximum, see below) three phase current equals or exceeds the level set by this setpoint , a phase overcurrent condition will occur. •PHASE OVERCURRENT DELAY: If the average (or maximum, see below) phase current equals or exceeds the PHASE OVERCURRENT LEVEL setpoint value and remains this way for the time delay programmed in this setpoint , a phase overcurrent condition will occur. •PHASE OVERCURRENT ACTIVATION: The Phase Overcurrent function can use either the average phase current or the maximum of the three phase currents. This setpoint determines which is used. •NEUTRAL OVERCURRENT RELAY: Neutral overcurrent can be disabled, used as an alarm, or used as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever a neutral overcurrent condition exists. Selecting an auxiliary relay activates the auxiliary relay for a neutral overcurrent condition but no message will be displayed. This is intended for process control. •NEUTRAL OVERCURRENT LEVEL: When the neutral current equals or exceeds the level set by this setpoint , a neutral overcurrent condition will occur. •NEUTRAL OVERCURRENT DELAY: If the neutral current greater than or equal to the NEUTRAL OVERCURRENT LEVEL setpoint value for the time delay programmed in this setpoint , a neutral overcurrent condition will occur. •UNDERVOLTAGE RELAY: Undervoltage can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever an undervoltage condition exists. Selecting an auxiliary relay activates the auxiliary relay for an undervoltage condition but no message will be displayed. This is intended for process control. •UNDERVOLTAGE LEVEL: When the voltage on one, two, or three phases drops to or below this level, an undervoltage condition occurs. The required number of phases is determined by the PHASES REQUIRED FOR U/V OPERATION setpoint . To clear the undervoltage condition, the level must increase to 103% of the UNDERVOLTAGE LEVEL setting. For example, if the UNDERVOLTAGE LEVEL is “4000 V”, the condition clears when the voltage in the appropriate phase(s) increases above 4120 V (4000 × 1.03). This hysteresis is implemented to avoid nuisance alarms due to voltage fluctuations. •UNDERVOLTAGE DELAY: If the voltage drops to or below the UNDERVOLTAGE LEVEL setpoint value and remains this way for the time delay programmed in this setpoint , an undervoltage condition will occur.
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–37 •PHASES REQ’D FOR U/V OPERATION: Select the minimum number of phases on which the undervoltage condition must be detected before the selected output relay will operate. This setpoint is not visible if VT WIRING is set to “Single Phase Direct”. •DETECT UNDERVOLTAGE BELOW 20V: If an indication is required for loss of voltage, select “Yes”. If “No” is selected and any one of the voltage inputs has less than 20 V applied, the undervoltage feature will be disabled. •OVERVOLTAGE RELAY: Overvoltage can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever an overvoltage condition exists. Selecting an auxiliary relay activates the auxiliary relay for an overvoltage condition but no message will be displayed. This is intended for process control. •OVERVOLTAGE LEVEL: When the voltage on one, two, or three phases equals or exceeds the level determined with this setpoint , an overvoltage condition occurs. The required number of phases is determined by the PHASES REQUIRED FOR O/V OPERATION setpoint . To clear the overvoltage condition, the level must decrease to 97% of the OVERVOLTAGE LEVEL setting. For example, if the OVERVOLTAGE LEVEL is set to “4200 V”, the condition clears when the voltage in the appropriate phase(s) goes below 4074 V (4200 × 0.97). This hysteresis is implemented to avoid nuisance alarms due to voltage fluctuations. •OVERVOLTAGE DELAY: If the voltage equals or exceeds the OVERVOLTAGE LEVEL setpoint value for the time delay programmed in this setpoint , an overvoltage condition will occur. •PHASES REQ’D FOR O/V OPERATION: Select the minimum number of phases on which the overvoltage condition must be detected before the selected output relay operates. This setpoint is not visible if VT WIRING is set to “Single Phase Direct”. •CURRENT UNBALANCE RELAY: Current unbalance is calculated as the maximum deviation from the average divided by the average three phase current . Current unbalance can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever a current unbalance condition exists. Selecting an auxiliary relay activates the auxiliary relay for a current unbalance condition but no message will be displayed. This is intended for process control. •CURRENT UNBALANCE LEVEL: When the current unbalance equals or exceeds this level, a current unbalance condition will occur. See 6.2.1 Current Metering for details on the method of calculation. •CURRENT UNBALANCE DELAY: If the current unbalance equals or exceeds the CURRENT UNBALANCE LEVEL value for the time delay programmed in this setpoint , a current unbalance condition occurs. •VOLTAGE UNBALANCE RELAY: Voltage unbalance is calculated as the maximum deviation from the average divided by the average three phase voltage. Voltage unbalance can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever a voltage unbalance condition exists. Selecting an auxiliary relay activates the auxiliary relay for a voltage unbalance condition but no message will be displayed. This is intended for process control.
5–38PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS •VOLTAGE UNBALANCE LEVEL: When the voltage unbalance equals or exceeds this level, a voltage unbalance condition occurs. See 6.2.2 Voltage Metering for details on the method of calculation. •VOLTAGE UNBALANCE DELAY: If the voltage unbalance equals or exceeds the VOLTAGE UNBALANCE LEVEL setpoint value and remains this way for the time delay programmed in this setpoint , a voltage unbalance condition will occur. •VOLTAGE PHASE REVERSAL: Under normal operating conditions, the PQMII expects to see the voltages connected with a 1-2-3 or A-B-C sequence. If the voltages are connected with the wrong sequence (e.g. 2-1-3 or B-A-C), a voltage phase reversal condition will occur. A minimum of 20 V must be applied to the PQMII on all voltage inputs before the phase reversal feature will operate. A phase reversal condition is determined by looking at the phase angle at the occurrence of the peak sample of phase B voltage and subtracting it from the phase angle at the peak sample of phase A voltage (phase A angle – phase B angle). This angle is averaged over several cycles before deciding on the condition to avoid any false triggering of the feature. Only two phases are required to detect phase reversal because all phase reversal conditions can be covered without the use of the third phase. The angle to detect phase reversal will vary depending on the connection being used as described below. For “4-Wire Wye / 3 VTs”, “4 Wire Wye / 2 VTs”, “4 Wire Direct”, and “3 Wire Direct” connections, the phase reversal function operates when the angle between phase A and B becomes ≤ –150° or ≥ –90° as shown below. FIGURE 5–3: Phase Reversal for 4-wire and 3-wire Direct Connections For the “3 Wire Delta / 2 VTs” connection, the phase reversal function operates when the angle between phase A and B is ≤30° or ≥90° as shown below. FIGURE 5–4: Phase Reversal for 3-wire Delta (2 VTs Open-Delta) Wiring Vb(corn)+30° Va(born)=0°(reference) Vc(aorn)=–240° Vb(corn)–30° Vb(corn)=–120°shaded area = angle tolerance allowed before phase reversal willoccur Vcb –30° Vab=0°(reference) Vcb +30° Vcb=60° Vbc=–120°shaded area = angle tolerance allowed before phase reversal willoccur
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–39 When the “Single Phase Direct” connection is used the phase reversal feature will never operate. •VOLTAGE PHASE REVERSAL DELAY: If a voltage phase reversal exists for the time programmed in this setpoint a voltage phase reversal condition will occur. NotePlease note that the terms undervoltage and overvoltage used for alarm, are generic regardless of sag/swell or undervotlage/overvoltage conditions based on duration of the voltage disturbance 5.5.2 Harmonic Distortion PATH: SETPOINTS S4 ALARMS/CONTROL TOTAL HARMONIC DISTORTION •AVERAGE CURRENT THD RELAY: Excessive phase current THD detection can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever an excessive average current THD condition exists. Selecting an auxiliary relay activates the auxiliary relay, but no message will be displayed. This is intended for process control. •AVERAGE CURRENT THD LEVEL: When the measured average current THD exceeds this setpoint value, an average current THD condition occurs. •AVERAGE CURRENT THD DELAY: If the average current THD exceeds the AVERAGE CURRENT THD LEVEL for the time delay programmed in this setpoint , an average current THD condition occurs. •AVERAGE VOLTAGE THD RELAY: Average voltage THD detection can either be disabled, used as an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will cause the alarm relay to activate and display an alarm message whenever an average voltage THD condition exists. Selecting auxiliary relay will cause the auxiliary relay to activate, but no message will be displayed. This is intended for process control. •AVERAGE VOLTAGE THD LEVEL: When the measured average voltage THD equals or exceeds this setpoint value, an Average Voltage THD condition occurs. TOTAL HARMONIC [] DISTORTIONAVERAGE CURRENT THD RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEAVERAGE CURRENT THD LEVEL ≥ 10.0 %Range: 0.5 to 100.0% in steps of 0.5 MESSAGEAVERAGE CURRENT THD DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEAVERAGE VOLTAGE THD RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEAVERAGE VOLTAGE THD LEVEL ≥ 10.0 %Range: 0.5 to 100.0% in steps of 0.5 MESSAGEAVERAGE VOLTAGE THD DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5
5–40PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS •AVERAGE VOLTAGE THD DELAY: If the average voltage THD equals or exceeds the AVERAGE VOLTAGE THD LEVEL value and remains this way for the time delay programmed in this setpoint , an Average Voltage THD condition will occur. 5.5.3 Frequency PATH: SETPOINTS S4 ALARMS/CONTROL FREQUENCY •UNDERFREQUENCY RELAY: Underfrequency detection can either be disabled or used as an alarm, or process control. Set this setpoint to “Off ” if the feature is not required. Selecting alarm relay will cause the alarm relay to activate and display an alarm message whenever an underfrequency condition exists. Selecting an auxiliary relay activates the auxiliary relay for an underfrequency condition, but no message will be displayed. This is intended for process control. •UNDERFREQUENCY LEVEL: When the measured frequency drops to or below the level set by this setpoint , an underfrequency condition will occur. •UNDERFREQUENCY DELAY: If the underfrequency drops to or below the UNDERFREQUENCY LEVEL value for the time delay programmed in this setpoint , an underfrequency condition will occur. •UNDERFREQUENCY WHEN FREQ=0 Hz: A voltage greater than 20 V is required on phase AN (AB) voltage input before frequency can be measured. If no voltage is applied or if the voltage applied is less than 20 V, the displayed frequency will be 0 Hz. If “No” is selected in this setpoint , an underfrequency condition will not occur when the displayed frequency is 0 Hz. •OVERFREQUENCY RELAY: Overfrequency detection can either be disabled, used as an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will cause the alarm relay to activate and display an alarm message whenever an overfrequency condition exists. Selecting auxiliary relay will cause the auxiliary relay to activate for an overfrequency condition, but no message will be displayed. This is intended for process control. •OVERFREQUENCY LEVEL: When the measured frequency equals or exceeds the level set by this setpoint , an overfrequency condition will occur. FREQUENCY [] UNDERFREQUENCY RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEUNDERFREQUENCY LEVEL ≤ 40.00 HzRange: 20.00 to 70.00 Hz in steps of 0.01 MESSAGEUNDERFREQUENCY DELAY: 1.0 sRange: 0.1 to 10.0 s in steps of 0.1 MESSAGEUNDERFREQUENCY WHEN FREQUENCY=0 Hz: NORange: Yes, No MESSAGEOVERFREQUENCY RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEOVERFREQUENCY LEVEL ≥ 70.00 HzRange: 20.00 to 125.00 Hz in steps of 0.01 MESSAGEOVERFREQUENCY DELAY: 1.0 sRange: 0.1 to 10.0 s in steps of 0.1
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–41 •OVERFREQUENCY DELAY: If the overfrequency equals or exceeds the OVERFREQUENCY LEVEL setpoint value for the time delay programmed in this setpoint , an overfrequency condition will occur. 5.5.4 Power Alarms PATH: SETPOINTS S4 ALARMS/CONTROL POWER •POWER ALARMS LEVEL BASE UNIT(S): This setpoint is used to select the base unit multiplier for all power alarms. When set to kW/kvar, all power alarm levels can be set in terms of kW and kvar with a step value of 1 kW/kvar. When set to MW/Mvar, all power alarm levels can be set in terms of MW and Mvar with a step value of 0.01 MW/ Mvar. •POSITIVE/NEGATIVE REAL POWER RELAY: The positive and negative real power level detection can be disabled, used as an alarm, or used as a process control. The “Off ” setting disables this feature. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever a positive/negative real power level exceeds the selected level. Selecting an auxiliary relay activates the auxiliary relay for a set level of POWER [] POWER ALARMS LEVEL BASE UNIT(s): kW/kvarRange: kW/kvar, MW, Mvar MESSAGEPOSITIVE REAL POWER RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOSITIVE REAL POWER LEVEL ≥ 1000 kWRange: 1 to 65000 kW in steps of 1, or 0.01 to 650.00 MW in steps of 0.01 MESSAGEPOSITIVE REAL POWER DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGENEGATIVE REAL POWER RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGENEGATIVE REAL POWER LEVEL ≥ 1000 kWRange: 1 to 65000 kW in steps of 1, or 0.01 to 650.00 MW in steps of 0.01 MESSAGENEGATIVE REAL POWER DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEPOSITIVE REACT POWER RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOSITIVE REACT POWER LEVEL ≥ 1000 kvarRange: 1 to 65000 kvar in steps of 1, or 0.01 to 650.00 Mvar in steps of 0.01 MESSAGEPOSITIVE REACT POWER DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGENEGATIVE REACT POWER RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGENEGATIVE REACT POWER LEVEL ≥ 1000 kvarRange: 1 to 65000 kvar in steps of 1, or 0.01 to 650.00 Mvar in steps of 0.01 MESSAGENEGATIVE REACT POWER DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5
5–42PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS positive/negative real power but no message will be displayed. This is intended for process control. •POSITIVE/NEGATIVE REAL POWER LEVEL: When the three phase real power equals or exceeds the level def ined by this setpoint, an excess positive/negative real power condition will occur. •POSITIVE/NEGATIVE REAL POWER DELAY: If the positive/negative real power equals or exceeds the POSITIVE/NEGATIVE REAL POWER LEVEL setpoint value for the time delay programmed in this setpoint , an excessive positive/negative real power condition will occur. •POSITIVE/NEGATIVE REACTIVE POWER RELAY: Positive and negative reactive power level detection can either be disabled, used as an alarm, or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message whenever a positive/negative reactive power level exceeds the selected level. Selecting an auxiliary relay activates the auxiliary relay for a set level of positive/negative reactive power but no message will be displayed. This is intended for process control. •POSITIVE/NEGATIVE REACTIVE POWER LEVEL: When the three phase reactive power equals or exceeds the level set by this setpoint , an excess positive/negative reactive power condition will occur. •POSITIVE/NEGATIVE REACTIVE POWER DELAY: If the positive reactive power equals or exceeds the POSITIVE/NEGATIVE REACTIVE POWER LEVEL setpoint value for the time delay programmed in this setpoint , an excessive positive reactive power condition will occur.
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–43 5.5.5 Power Factor PATH: SETPOINTS S4 ALARMS/CONTROL POWER FACTOR It is generally desirable for a system operator to maintain the power factor as close to unity as possible (that is, to make the real power of the system as close as possible to the apparent power) to minimize both costs and voltage excursions. On dedicated circuits such as some large motors, with a near-f ixed load, a capacitor bank may be switched on or off with the motor to supply leading vars to compensate for the lagging vars required by the motor. Since the power factor is variable on common non-dedicated circuits, it is POWER FACTOR [] POWER FACTOR LEAD 1 RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOWER FACTOR LEAD 1 PICKUP ≤ 0.99Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LEAD 1 DROPOUT ≥ 1.00Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LEAD 1 DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEPOWER FACTOR LAG 1 RELAY: OffRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOWER FACTOR LAG 1 PICKUP ≤ 0.99Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LAG 1 DROPOUT ≥ 1.00Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LAG 1 DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEPOWER FACTOR LEAD 2 RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOWER FACTOR LEAD 2 PICKUP ≤ 0.99Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LEAD 2 DROPOUT ≥ 1.00Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LEAD 2 DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5 MESSAGEPOWER FACTOR LAG 2 RELAY: OFFRange: Alarm, Aux1, Aux2, Aux3, Off MESSAGEPOWER FACTOR LAG 2 PICKUP ≤ 0.99Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LAG 2 DROPOUT ≥ 1.00Range: 0.50 to 1.00 in steps of 0.01 MESSAGEPOWER FACTOR LAG 2 DELAY: 10.0 sRange: 0.5 to 600.0 s in steps of 0.5
5–44PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS advantageous to compensate for low (lagging) power factor values by connecting a capacitor bank to the circuit when required. The PQMII provides power factor monitoring and allows two stages of capacitance switching for power factor compensation. FIGURE 5–5: Capacitor Bank Switching The PQMII calculates the average power factor in the three phases, according to the following equation: (EQ 5.2) Two independent ‘elements’ are available for monitoring power factor, Power Factor 1 and Power Factor 2, each having a pickup and a dropout level. For each element , when the measured power factor is equal to or becomes more lagging than the pickup level (i.e. numerically less than), the PQMII will operate a user-selected output relay. This output can be used to control a switching device which connects capacitance to the circuit , or to signal an alarm to the system operator. After entering this state, when the power factor becomes less lagging than the power factor dropout level, the PQMII will reset the output relay to the non-operated state. Both Power Factor 1 and 2 features are inhibited from operating unless all three voltages are above 20% of nominal and one or more currents is above 0. Power factor 1 and 2 delay timers will be allowed to time only when the 20% threshold is exceeded on all phases (and, of course, only while the power factor remains outside of the programmed pickup and dropout levels). In the same way, when a power factor condition starts the power factor 1 or 2 delay timer, if all three phase voltages fall below the 20% threshold before the timer has timed-out , the element will reset without operating. A loss of voltage during any state will return both Power Factor 1 and 2 to the reset state. •POWER FACTOR LEAD 1(2) RELAY: Power factor detection can either be disabled, used as an alarm or as a process control. Set this setpoint to “Off ” if the feature is not required. Selecting “Alarm” activates the alarm relay and displays an alarm message when the power factor is more leading than the level set . Selecting “Aux1”, “Aux2”, or “Aux3” activates the respective auxiliary relay when the power factor is equal to or more leading than the level set , but no message will be displayed. This is intended for Average Power FactorTotal 3-phase Real Power Total 3-phase Apparent Power ---------------------------------------------------------------------------- =