GE Pqm 2 Manual
Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–15 metering calculations is done on top of the trace memory sampling. The harmonic analysis sampling (256 samples/cycles, 1 cycle) causes the trace memory sampling to stop for one cycle whenever a harmonic analysis is requested. Refer to 4.5.3 Trace Memory for details on trace memory implementation in the EnerVista PQMII Setup Software. •TRACE MEMORY USAGE: The trace memory feature allows the user to capture maximum of 36 cycles. The TRACE MEMORY USAGE setpoint allows the buffer to be divided into maximum of 3 separate buffers as shown in table below.
5–16PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS •TRACE MEMORY TRIGGER MODE: The trace memory can be conf igured to trigger in two different modes as described in the table below. •Ia/Ib/Ic/In OVERCURRENT TRIG LEVEL: Once the phase A/B/C/neutral current equals or increases above this setpoint value, the trace memory is triggered and data on all inputs are captured in the buffer. The number of cycles captured depends on the value specif ied in the TRACE MEMORY USAGE setpoint . •Va/Vb/Vc OVERVOLTAGE TRIG LEVEL: Once the phase A/B/C voltage equals or increases above this setpoint value, the trace memory is triggered and data on all inputs are captured in the buffer. The number of cycles captured depends on the value specif ied in the TRACE MEMORY USAGE setpoint . Phase to neutral levels are used regardless of the VT wiring. •Va/Vb/Vc UNDERVOLTAGE TRIG LEVEL: Once the phase A/B/C voltage is equal to or less than this setpoint value, the trace memory is triggered and data on all inputs are captured in the buffer. The number of cycles captured depends on the value specif ied in the TRACE MEMORY USAGE setpoint . •SWITCH INPUT A(D) TRIG: If the setpoint is set to “Open-to-Closed”, the trace memory is triggered and data on all inputs are captured in the buffer on a Switch A(D) close transition. If the setpoint is set to “Closed-to-Open”, the trace memory is triggered and data on all inputs are captured in the buffer on a Switch A(D) open transition. The number of cycles captured depends on the value specif ied in the TRACE MEMORY USAGE setpoint . •TRACE MEMORY TRIGGER DELAY: In some applications it may be necessary to delay the trigger point to observe the data before the fault occurred. The PQMII allows the trigger to be delayed by the amount of cycles set in this setpoint . Therefore, buffer will always contain the number cycles specif ied in this setpoint before the trigger point and the remaining space in the buffer is f illed with the cycles after the trigger point . •TRACE MEMORY TRIGGER RELAY: The relay selected here will be activated upon the occurrence of a Trace Memory Trigger. This relay will be cleared once the Trace Memory is re-armed. See 7.4 Triggered Trace Memory for additional details on this feature. Setpoint Value Result 1 x 36 cycles Upon a trigger, the entire buffer is f illed with 36 cycles of data. 2 x 18 cyclesThe buffer is split into 2 separate buffers and upon a trigger, the f irst buffer is f illed with 18 cycles of data and upon a second trigger, the second buffer is filled with 18 cycles of data. 3 x 12 cyclesThe buffer is split into 3 separate buffers and upon a trigger, the f irst buffer is f illed with 12 cycles of data, upon a second trigger, the second buffer is f illed with 12 cycles of data and upon a third trigger, the third buffer is f illed with 12 cycles of data. Setpoint Value Result One ShotThe trace memory will be triggered once per buffer as def ined in the TRACE MEMORY USAGE setpoint above. In order for it to re-trigger, it must be re-armed through the serial port using the EnerVista PQMII Setup Software or other software. Once re- armed the trace memory will default back to the f irst buffer. RetriggerThe trace memory will automatically re-trigger upon each condition and overwrite the previous buffer data.
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–17 5.2.11 Programmable Message PATH: SETPOINTS S1 PQMII SETUP PROGRAMMABLE MESSAGE A 40-character message can be programmed using the keypad, or via a serial port using the EnerVista PQMII Setup Software. An example of writing a new message over the existing one is shown below: TIPS: • The setpoint access must be enabled in order to alter the characters. • To skip over a character press the ENTER key. • If a character is entered incorrectly, press the ENTER key repeatedly until the cursor returns to the position of the error, and re-enter the character. •See 3.4 Default Messages for details on selecting this message as a default message A copy of this message is displayed in actual values page A2 STATUS PROGRAMMABLE MESSAGE . PROGRAMMABLE [] MESSAGEPHONE: 905-294-6222 www.GEmultilin.comRange: 40 alphanumeric characters PROGRAMMABLE MESSAGEPHONE: 905-294-6222GEindustrial.comNEW SETPOINT STORED P ONE: 905-294-6222HGEindustrial.comNEW SETPOINT STORED STORE Displayed for 3 seconds when ENTER key pressedDisplayed for 3 seconds when ENTER key pressed USE THE VALUE KEYS TO SELECT THE UNDERLINED QUANTITIES VALUEMESSAGE ENTER ENTER
5–18PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS 5.2.12 Product Options PATH: SETPOINTS S1 PQMII SETUP PRODUCT OPTIONS The PQMII can have options and certain modif ications upgraded on-site via use of a passcode provided by GE Multilin. Consult the factory for details on the use of this feature. PRODUCT [] OPTIONSSELECT ORDER: PQMII-T20-C-ARange: see range in PQMII Modbus memory format code F116 MESSAGESELECT MOD1 TO ENABLE: 0Range: 0 to 999 in steps of 1 MESSAGESELECT MOD2 TO ENABLE: 0Range: 0 to 999 in steps of 1 MESSAGESELECT MOD3 TO ENABLE: 0Range: 0 to 999 in steps of 1 MESSAGESELECT MOD4 TO ENABLE: 0Range: 0 to 999 in steps of 1 MESSAGESELECT MOD5 TO ENABLE: 0Range: 0 to 999 in steps of 1 MESSAGEENTER PASSCODE: _Range: consult the factory
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–19 5.3 S2 System Setup 5.3.1 Current and Voltage Conf iguration NoteThe shaded setpoints below must be set to a value other than “Off ” to clear the Critical Setpoints Not Stored alarm. PATH: SETPOINTS S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIG. •PHASE CT WIRING: The table below indicates the required connection per setpoint setting. If the “A and B Only”, “A and C Only”, or “A Only” connection is selected, the neutral sensing must be accomplished with a separate CT. •PHASE CT PRIMARY: Enter the primary current rating of the phase current transformers. All three phase CTs must have the same rating. For example, if 500:5 CTs are used, the PHASE CT PRIMARY value is entered as “500”. The PHASE CT PRIMARY factory default is “Off ”. While set to “Off ”, the PQMII is forced to an alarm state as a safety CURRENT/ [] VOLTAGE CONFIG.PHASE CT WIRING: Phases A, B, AND CRange: A, B, and C, A and B only, A and C only, A only MESSAGEPHASE CT PRIMARY: OFF ARange: 5 to 12000 A in steps of 5 or Off MESSAGENEUTRAL CURRENT SENSING: OFFRange: Off, Separate CT, Calculated MESSAGENEUTRAL CT PRIMARY: 100 ARange: 5 to 6000 A in steps of 5 MESSAGEVT WIRING: OFFRange: Off, 4 Wire Wye / 3 VTs, 4 Wire Wye / Direct , 4 Wire Wye / 2 VTs, 3-Wire Delta / 2 VTs, 3 Wire Direct , Single Phase Direct MESSAGEVT RATIO: 1.0:1Range: 1.0 to 3500.0 in steps of 0.1 MESSAGEVT NOMINAL SECONDARY VOLTAGE: 120 VRange: 40 to 600 V in steps of 1 MESSAGENOMINAL DIRECT INPUT VOLTAGE: 600 VRange: 40 to 600 V in steps of 1 MESSAGENOMINAL SYSTEM FREQUENCY: 60 HzRange: 50 Hz, 60 Hz Setpoint Value Required CT Connection A,B, and C CTs are connected to phase A, B and C inputs. A and B OnlyCTs are connected to phase A and B only. Phase C input is left open. The value for phase C is calculated by the PQMII. A and C OnlyCTs are connected to phase A and C only. Phase B input is left open. The value for phase B is calculated by the PQMII. A OnlyCT is connected to phase A only. Phase B and C inputs are left open. The values for phase B and C are calculated by the PQMII.
5–20PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS precaution until a valid CT value is entered. Ensure that the CT is connected to the correct 1 or 5 A terminals to match the CT secondary. •NEUTRAL CURRENT SENSING: Neutral current sensing can be accomplished by using a separate external CT connection or by calculations. Select “Separate CT” when using an external CT. If “Calculated” is selected, the PQMII calculates the neutral current using the vector sum of Ia + Ib + Ic = In. If a residual connection is required using the PQMII internal CT, the neutral CT primary must be the same as the phase CT primary to ensure correct readings. •NEUTRAL CT PRIMARY: This message is visible only if the neutral current sensing setpoint is set to “Separate CT”. Enter the CT primary current . For example, if a 50:5 CT is installed for neutral sensing enter 50. One amp CTs can also be used for neutral sensing. •VT WIRING: Enter the VT connection of the system in this setpoint . The three possible wiring conf igurations are Wye, Delta, and Single Phase. If the system to be measured is a Wye connection, the selections are “4 Wire Wye Direct”, “4 Wire Wye / 3 VTs”, and “4 Wire Wye /2 VTs”. The “4 Wire Wye Direct” value is used for systems that are 600 V or less and directly connected to the PQMII. The VT NOMINAL SECONDARY VOLTAGE setpoint is replaced by NOMINAL DIRECT INPUT VOLTAGE. With external VTs (depending upon how many external VTs are used), the “4 Wire Wye / 3 VTs” or “4 Wire Wye / 2 VTs” value must be selected. Note that when using the “4 Wire Wye / 2 VTs” value, only two voltages are measured; the third voltage is calculated on the assumption that Van + Vbn + Vcn = 0. This assumption is valid only for balanced system voltages. If the system to be measured is a Delta connection, the values are “3 Wire Direct” and “3 Wire Delta / 2 VTs”. The “3 Wire Direct” value should be used for systems that are 600 V or less and directly connected to the PQMII. With external VTs, “3 Wire Delta / 2 VTs” must be selected. The PQMII accepts input voltages from 0 to 600 V AC between any two of the voltage terminals (V1, V2, V3, and Vn). These inputs can be directly connected or supplied via external VTs. External VTs are required for input voltages greater than 600 V AC (line- to-line). When measuring line-to-line quantities using inputs V1, V2 and V3, ensure that the voltage common input Vn is grounded. This input is used as a reference for measuring the voltage inputs. All connections to the PQMII voltage inputs should be connected using HRC fuses rated at 2 amps to ensure adequate interrupting capacity. •VT RATIO: Enter the voltage transformer ratio. All three voltage inputs must be of the same rating. For example, if 4200:120 VTs are used, the VT RATIO should be 4200 / 120 = 35.0:1. This setpoint is not visible if VT WIRING is set to “3 Wire Direct”, “4 Wire Direct”, or “Single Phase Direct”. •VT NOMINAL SECONDARY VOLTAGE: Enter the nominal secondary of the VTs. If the voltage inputs are directly connected, enter the nominal system voltage that will be applied to the PQMII. This setpoint is not visible if the VT WIRING is set to “3 Wire Direct”, “4 Wire Direct”, or “Single Phase Direct”. This value is used to scale an analog output that is assigned to display voltage as a percentage of nominal. •NOMINAL DIRECT INPUT VOLTAGE: This setpoint is displayed only if VT WIRING is selected as a direct connection. The nominal direct input voltage must be entered in
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–21 this message. This value will be used to scale an analog output that is assigned to display voltage as a percentage of nominal. •NOMINAL SYSTEM FREQUENCY: Enter the nominal system frequency. The PQMII measures frequency from the Van voltage and adjusts its internal sampling to best f it the measured frequency. If the Van input is unavailable, the PQMII will assume the frequency entered here. 5.3.2 Analog Outputs PATH: SETPOINTS S2 SYSTEM SETUP ANALOG OUTPUT 1(4) The PQMII has four (4) Analog Outputs conf igured through four setpoints pages. The ANALOG OUTPUT RANGE setpoint appears in the Analog Output 1 setpoints page only and applies to all four outputs. •ANALOG OUTPUT RANGE: If the T20 option is installed, the Analog Outputs can be conf igured to operate as 4 to 20 mA current sources or 0 to 20 mA current sources. All four Analog Outputs will operate in the range def ined by this setpoint . •ANALOG OUTPUT 1(4) MAIN / ANALOG OUTPUT 1(4) ALT: If the PQMII is used in conjunction with programmable controllers, automated equipment , or a chart recorder, the analog outputs can be used for continuous monitoring. Although parameters can be selected for continuous analog output , all values are available digitally through the communications interface. Applications include using a computer to automatically shed loads as the frequency decreases by monitoring frequency or a chart recorder to plot the loading of a system in a particular process. Each of the analog outputs can be assigned to two of the parameters listed in the Analog Output Parameters table. The analog output main selection is the default selection and a programmable switch input can be programmed to multiplex the ANALOG OUTPUT 1(4) ALT selection to the same output depending upon the open or closed state of the switch input . See 5.3.4 Switch Inputs for details about conf iguring a switch input . If no switch input is assigned as an analog output multiplexer, the analog output main selection will be the only parameter which appears at the analog output terminals. The ability to multiplex two different analog output quantities on one ANALOG [] OUTPUT 1ANALOG OUTPUT RANGE: 4-20 mARange: 0-20 mA, 4-20 mA. Seen only in the Analog Output 1 menu. MESSAGEANALOG OUTPUT 1 MAIN: Not UsedRange: refer to the Analog Output Parameters table below MESSAGEMAIN 4 mA VALUE: 0Range: refer to the Analog Output Parameters table below MESSAGEMAIN 20 mA VALUE: 0Range: refer to the Analog Output Parameters table below MESSAGEANALOG OUTPUT 1 ALT: NOT USEDRange: refer to the Analog Output Parameters table below MESSAGEALT 4 mA VALUE: 0Range: refer to the Analog Output Parameters table below MESSAGEALT 20 mA VALUE: 0Range: refer to the Analog Output Parameters table below
5–22PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS analog output effectively gives the PQMII eight analog outputs. The table below shows the criteria used by the PQMII to decide whether the output is based on MAIN or ALT settings. •MAIN/ALT 4 mA VALUE: This message appears for each analog output and allows the user to assign a numeric value which corresponds to the 4 mA end of the 4 to 20 mA signal range (T20 option) or the 0 mA end of the 0 to 1 mA signal range (T1 option). The numeric value range will depend upon which parameter is selected. See the Analog Output Parameters table below for details. Note that if the T20 option is installed and the ANALOG OUTPUT RANGE setpoint is set to “0-20 mA”, this message represents the 0 mA end of the signal range. •MAIN/ALT 20 mA VALUE: This message appears for each analog output and allows the user to assign a numeric value which corresponds to the 20 mA end of the 4 to 20 mA signal range (T20 option) or the 1 mA end of the 0 to 1 mA signal range (T1 option). The numeric value range will depend upon which parameter is selected. See the Analog Output Parameters table below. If the 4 mA (or 0 mA) value is programmed to be higher than the 20 mA (or 1 mA) value, the analog output will decrease towards 4 mA (or 0 mA) as the value increases and the analog output will increase towards 20 mA (or 1 mA) as the value decreases. If the 4 mA (or 0 mA) and 20 mA (or 1 mA) values are programmed to an identical value, the output will always be 4 mA (or 0 mA).Table 5–3: Analog Output Selection Criteria Condition Present ‘Main’ Parameter‘Alt’ Parameter Output Based On Any condition “Not Used” “Not Used” Main Control option ‘C’ not installed any not available Main Switch assigned to SELECT ANALOG OUTPUT and is disabledany “Not Used” Main Switch assigned to SELECT ANALOG OUTPUT and is enabledany “Not Used” Main Any condition “Not Used”anything other than “Not Used”Alt Switch assigned to SELECT ANALOG OUTPUT and is disabled“Not Used”anything other than “Not Used”Alt Switch assigned to SELECT ANALOG OUTPUT and is enabledanyanything other than “Not Used”Alt
CHAPTER 5: SETPOINTS PQMII POWER QUALITY METER – INSTRUCTION MANUAL5–23 Table 5–4: Analog Output Parameters (Sheet 1 of 2) Parameter Range Step Phase A Current 0 to 150% 1% Phase B Current 0 to 150% 1% Phase C Current 0 to 150% 1% Neutral Current 0 to 150% 1% Average Phase Current 0 to 150% 1% Current Unbalance 0 to 100.0% 0.1% Voltage Van 0 to 200% 1% Voltage Vbn 0 to 200% 1% Voltage Vcn 0 to 200% 1% Voltage Vab 0 to 200% 1% Voltage Vbc 0 to 200% 1% Voltage Vca 0 to 200% 1% Average Phase Voltage 0 to 200% 1% Average Line Voltage 0 to 200% 1% Voltage Unbalance 0 to 100.0% 0.1% Frequency 00.00 to 75.00 Hz 0.01 Hz 3 Phase PF 0.01 lead to 0.01 lag 0.01 3 Phase kW –32500 to +32500 1 kW 3 Phase kvar –32500 to +32500 1 kvar 3 Phase kVA 0 to 65400 1 kVA 3 Phase MW –3250.0 to +3250.0 0.1 MW 3 Phase Mvar –3250.0 to +3250.0 0.1 Mvar 3 Phase MVA 0 to 6540.0 0.1 MVA Phase A PF 0.01 lead to 0.01 lag 0.01 Phase A kW –32500 to +32500 1 kW Phase A kvar –32500 to +32500 1 kvar Phase A kVA 0 to 65400 1 kVA Phase B PF 0.01 lead to 0.01 lag 0.01 Phase B kW –32500 to +32500 1 kW Phase B kvar –32500 to +32500 1 kvar
5–24PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 5: SETPOINTS Phase B kVA 0 to 65400 1 kVA Phase C PF 0.01 lead to 0.01 lag 0.01 Phase C kW –32500 to +32500 1 kW Phase C kvar –32500 to +32500 1 kvar Phase C kVA 0 to 65400 1 kVA 3 Phase +kWh Used 0 to 65400 1 kWh 3 Phase +kvarh Used 0 to 65400 1 kvarh 3 Phase –kWh Used 0 to 65400 1 kWh 3 Phase –kvarh Used 0 to 65400 1 kvarh 3 Phase kVAh Used 0 to 65400 1 kVAh Phase A Current Demand 0 to 7500 1 A Phase B Current Demand 0 to 7500 1 A Phase C Current Demand 0 to 7500 1 A Neutral Current Demand 0 to 7500 1 A 3 Phase kW Demand –32500 to +32500 1 kW 3 Phase kvar Demand –32500 to +32500 1 kvar 3 Phase kVA Demand 0 to 65400 1 kVA 3 Phase Current THD 0.0 to 100% 0.1% 3 Phase Voltage THD 0.0 to 100% 0.1% Phase A Current THD 0.0 to 100% 0.1% Phase B Current THD 0.0 to 100% 0.1% Phase C Current THD 0.0 to 100% 0.1% Voltage Van THD 0.0 to 100% 0.1% Voltage Vbn THD 0.0 to 100% 0.1% Voltage Vcn THD 0.0 to 100% 0.1% Voltage Vab THD 0.0 to 100% 0.1% Voltage Vbc THD 0.0 to 100% 0.1% Neutral Current THD 0.0 to 100% 0.1% Serial Control –32500 to +32500 1 UnitTable 5–4: Analog Output Parameters (Sheet 2 of 2) Parameter Range Step