Home > GE > Power Products > GE Pqm 2 Manual

GE Pqm 2 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							CHAPTER 5: SETPOINTS
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL5–15
    metering calculations is done on top of the trace memory sampling. The harmonic analysis 
    sampling (256 samples/cycles, 1 cycle) causes the trace memory sampling to stop for one 
    cycle whenever a harmonic analysis is requested. Refer to 4.5.3 Trace Memory for details 
    on trace memory implementation in the EnerVista PQMII Setup Software.
    •TRACE MEMORY USAGE: The trace memory feature allows the user to capture 
    maximum of 36 cycles. The 
    TRACE MEMORY USAGE setpoint allows the buffer to be divided 
    into maximum of 3 separate buffers as shown in table below. 
    						
    							5–16PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 5: SETPOINTS
    •TRACE MEMORY TRIGGER MODE: The trace memory can be conf igured to trigger in 
    two different modes as described in the table below.
    •Ia/Ib/Ic/In OVERCURRENT TRIG LEVEL: Once the phase A/B/C/neutral current equals 
    or increases above this setpoint value, the trace memory is triggered and data on all 
    inputs are captured in the buffer. The number of cycles captured depends on the value 
    specif ied in the 
    TRACE MEMORY USAGE setpoint .
    •Va/Vb/Vc OVERVOLTAGE TRIG LEVEL: Once the phase A/B/C voltage equals or 
    increases above this setpoint value, the trace memory is triggered and data on all 
    inputs are captured in the buffer. The number of cycles captured depends on the value 
    specif ied in the 
    TRACE MEMORY USAGE setpoint . Phase to neutral levels are used 
    regardless of the VT wiring.
    •Va/Vb/Vc UNDERVOLTAGE TRIG LEVEL: Once the phase A/B/C voltage is equal to or 
    less than this setpoint value, the trace memory is triggered and data on all inputs are 
    captured in the buffer. The number of cycles captured depends on the value specif ied 
    in the 
    TRACE MEMORY USAGE setpoint .
    •SWITCH INPUT A(D) TRIG: If the setpoint is set to “Open-to-Closed”, the trace memory 
    is triggered and data on all inputs are captured in the buffer on a Switch A(D) close 
    transition. If the setpoint is set to “Closed-to-Open”, the trace memory is triggered and 
    data on all inputs are captured in the buffer on a Switch A(D) open transition. The 
    number of cycles captured depends on the value specif ied in the 
    TRACE MEMORY USAGE 
    setpoint .
    •TRACE MEMORY TRIGGER DELAY: In some applications it may be necessary to delay 
    the trigger point to observe the data before the fault occurred. The PQMII allows the 
    trigger to be delayed by the amount of cycles set in this setpoint . Therefore, buffer will 
    always contain the number cycles specif ied in this setpoint before the trigger point 
    and the remaining space in the buffer is f illed with the cycles after the trigger point .
    •TRACE MEMORY TRIGGER RELAY: The relay selected here will be activated upon the 
    occurrence of a Trace Memory Trigger. This relay will be cleared once the Trace 
    Memory is re-armed.
    See 7.4 Triggered Trace Memory for additional details on this feature.
    Setpoint Value Result
    1 x 36 cycles Upon a trigger, the entire buffer is f illed with 36 cycles of data.
    2 x 18 cyclesThe buffer is split into 2 separate buffers and upon a trigger, the 
    f irst buffer is f illed with 18 cycles of data and upon a second 
    trigger, the second buffer is filled with 18 cycles of data.
    3 x 12 cyclesThe buffer is split into 3 separate buffers and upon a trigger, the 
    f irst buffer is f illed with 12 cycles of data, upon a second trigger, 
    the second buffer is f illed with 12 cycles of data and upon a 
    third trigger, the third buffer is f illed with 12 cycles of data.
    Setpoint Value Result
    One ShotThe trace memory will be triggered once per buffer as def ined 
    in the TRACE MEMORY USAGE setpoint above. In order for it to 
    re-trigger, it must be re-armed through the serial port using the 
    EnerVista PQMII Setup Software or other software. Once re-
    armed the trace memory will default back to the f irst buffer.
    RetriggerThe trace memory will automatically re-trigger upon each 
    condition and overwrite the previous buffer data. 
    						
    							CHAPTER 5: SETPOINTS
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL5–17
    5.2.11 Programmable Message
    PATH: SETPOINTS  S1 PQMII SETUP  PROGRAMMABLE MESSAGE
    A 40-character message can be programmed using the keypad, or via a serial port using 
    the EnerVista PQMII Setup Software. An example of writing a new message over the 
    existing one is shown below:
    TIPS:
    • The setpoint access must be enabled in order to alter the characters.
    • To skip over a character press the 
    ENTER key.
    • If a character is entered incorrectly, press the 
    ENTER key repeatedly until the 
    cursor returns to the position of the error, and re-enter the character.
    •See 3.4 Default Messages for details on selecting this message as a default 
    message
    A copy of this message is displayed in actual values page 
    A2 STATUS  PROGRAMMABLE 
    MESSAGE
    .
     PROGRAMMABLE []
    MESSAGEPHONE: 905-294-6222
    www.GEmultilin.comRange: 40 alphanumeric characters
    PROGRAMMABLE
    MESSAGEPHONE: 905-294-6222GEindustrial.comNEW SETPOINT
    STORED
    P ONE: 905-294-6222HGEindustrial.comNEW SETPOINT
    STORED
    STORE
    Displayed for 3 seconds when
    ENTER key pressedDisplayed for 3 seconds when
    ENTER key pressed
    USE THE VALUE
    KEYS TO SELECT
    THE UNDERLINED
    QUANTITIES
    VALUEMESSAGE
    ENTER
    ENTER 
    						
    							5–18PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 5: SETPOINTS
    5.2.12 Product Options
    PATH: SETPOINTS  S1 PQMII SETUP  PRODUCT OPTIONS
    The PQMII can have options and certain modif ications upgraded on-site via use of a 
    passcode provided by GE Multilin. Consult the factory for details on the use of this feature.
     PRODUCT []
    OPTIONSSELECT ORDER:
    PQMII-T20-C-ARange: see range in PQMII Modbus 
    memory format code F116
    MESSAGESELECT MOD1 TO
    ENABLE: 0Range: 0 to 999 in steps of 1
    MESSAGESELECT MOD2 TO
    ENABLE: 0Range: 0 to 999 in steps of 1
    MESSAGESELECT MOD3 TO
    ENABLE: 0Range: 0 to 999 in steps of 1
    MESSAGESELECT MOD4 TO
    ENABLE: 0Range: 0 to 999 in steps of 1
    MESSAGESELECT MOD5 TO
    ENABLE: 0Range: 0 to 999 in steps of 1
    MESSAGEENTER PASSCODE: _Range: consult the factory 
    						
    							CHAPTER 5: SETPOINTS
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL5–19
    5.3 S2 System Setup
    5.3.1 Current and Voltage Conf iguration
    NoteThe shaded setpoints below must be set to a value other than “Off ” to clear the Critical 
    Setpoints Not Stored alarm.
    PATH: SETPOINTS  S2 SYSTEM SETUP  CURRENT/VOLTAGE CONFIG.
    •PHASE CT WIRING: The table below indicates the required connection per setpoint 
    setting.
    If the “A and B Only”, “A and C Only”, or “A Only” connection is selected, the neutral 
    sensing must be accomplished with a separate CT.
    •PHASE CT PRIMARY: Enter the primary current rating of the phase current 
    transformers. All three phase CTs must have the same rating. For example, if 500:5 CTs 
    are used, the 
    PHASE CT PRIMARY value is entered as “500”. The PHASE CT PRIMARY factory 
    default is “Off ”. While set to “Off ”, the PQMII is forced to an alarm state as a safety 
     CURRENT/ []
    VOLTAGE CONFIG.PHASE CT WIRING:
    Phases A, B, AND CRange: A, B, and C, A and B only, A and 
    C only, A only
    MESSAGEPHASE CT PRIMARY:
    OFF ARange: 5 to 12000 A in steps of 5 or Off
    MESSAGENEUTRAL CURRENT
    SENSING: OFFRange: Off, Separate CT, Calculated
    MESSAGENEUTRAL CT PRIMARY:
    100 ARange: 5 to 6000 A in steps of 5
    MESSAGEVT WIRING:
    OFFRange: Off, 4 Wire Wye / 3 VTs, 4 Wire 
    Wye / Direct , 4 Wire Wye / 2 
    VTs, 3-Wire Delta / 2 VTs, 3 
    Wire Direct , Single Phase Direct
    MESSAGEVT RATIO:
    1.0:1Range: 1.0 to 3500.0 in steps of 0.1
    MESSAGEVT NOMINAL SECONDARY
    VOLTAGE: 120 VRange: 40 to 600 V in steps of 1
    MESSAGENOMINAL DIRECT INPUT
    VOLTAGE: 600 VRange: 40 to 600 V in steps of 1
    MESSAGENOMINAL SYSTEM
    FREQUENCY: 60 HzRange: 50 Hz, 60 Hz
    Setpoint Value Required CT Connection
    A,B, and C CTs are connected to phase A, B and C inputs.
    A and B OnlyCTs are connected to phase A and B only. Phase C input is left 
    open. The value for phase C is calculated by the PQMII.
    A and C OnlyCTs are connected to phase A and C only. Phase B input is left 
    open. The value for phase B is calculated by the PQMII.
    A OnlyCT is connected to phase A only. Phase B and C inputs are left 
    open. 
    The values for phase B and C are calculated by the PQMII. 
    						
    							5–20PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 5: SETPOINTS
    precaution until a valid CT value is entered. Ensure that the CT is connected to the 
    correct 1 or 5 A terminals to match the CT secondary.
    •NEUTRAL CURRENT SENSING: Neutral current sensing can be accomplished by using 
    a separate external CT connection or by calculations. Select “Separate CT” when using 
    an external CT. If “Calculated” is selected, the PQMII calculates the neutral current 
    using the vector sum of Ia + Ib + Ic = In. If a residual connection is required using the 
    PQMII internal CT, the neutral CT primary must be the same as the phase CT primary to 
    ensure correct readings.
    •NEUTRAL CT PRIMARY: This message is visible only if the neutral current sensing 
    setpoint is set to “Separate CT”. Enter the CT primary current . For example, if a 50:5 CT 
    is installed for neutral sensing enter 50. One amp CTs can also be used for neutral 
    sensing.
    •VT WIRING: Enter the VT connection of the system in this setpoint . The three possible 
    wiring conf igurations are Wye, Delta, and Single Phase.
    If the system to be measured is a Wye connection, the selections are “4 Wire Wye 
    Direct”, “4 Wire Wye / 3 VTs”, and “4 Wire Wye /2 VTs”. The “4 Wire Wye Direct” value is 
    used for systems that are 600 V or less and directly connected to the PQMII. The 
    VT 
    NOMINAL SECONDARY VOLTAGE
     setpoint is replaced by NOMINAL DIRECT INPUT VOLTAGE. With 
    external VTs (depending upon how many external VTs are used), the “4 Wire Wye / 3 
    VTs” or “4 Wire Wye / 2 VTs” value must be selected. Note that when using the “4 Wire 
    Wye / 2 VTs” value, only two voltages are measured; the third voltage is calculated on 
    the assumption that Van + Vbn + Vcn = 0. This assumption is valid only for balanced 
    system voltages.
    If the system to be measured is a Delta connection, the values are “3 Wire Direct” and 
    “3 Wire Delta / 2 VTs”. The “3 Wire Direct” value should be used for systems that are 
    600 V or less and directly connected to the PQMII. With external VTs, “3 Wire Delta / 2 
    VTs” must be selected.
    The PQMII accepts input voltages from 0 to 600 V AC between any two of the voltage 
    terminals (V1, V2, V3, and Vn). These inputs can be directly connected or supplied via 
    external VTs. External VTs are required for input voltages greater than 600 V AC (line-
    to-line). When measuring line-to-line quantities using inputs V1, V2 and V3, ensure 
    that the voltage common input Vn is grounded. This input is used as a reference for 
    measuring the voltage inputs.
    All connections to the PQMII voltage inputs should be connected using HRC fuses 
    rated at 2 amps to ensure adequate interrupting capacity.
    •VT RATIO: Enter the voltage transformer ratio. All three voltage inputs must be of the 
    same rating. For example, if 4200:120 VTs are used, the 
    VT RATIO should be 4200 / 120 = 
    35.0:1. This setpoint is not visible if 
    VT WIRING is set to “3 Wire Direct”, “4 Wire Direct”, or 
    “Single Phase Direct”.
    •VT NOMINAL SECONDARY VOLTAGE: Enter the nominal secondary of the VTs. If the 
    voltage inputs are directly connected, enter the nominal system voltage that will be 
    applied to the PQMII. This setpoint is not visible if the 
    VT WIRING is set to “3 Wire Direct”, 
    “4 Wire Direct”, or “Single Phase Direct”. This value is used to scale an analog output 
    that is assigned to display voltage as a percentage of nominal.
    •NOMINAL DIRECT INPUT VOLTAGE: This setpoint is displayed only if VT WIRING is 
    selected as a direct connection. The nominal direct input voltage must be entered in  
    						
    							CHAPTER 5: SETPOINTS
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL5–21
    this message. This value will be used to scale an analog output that is assigned to 
    display voltage as a percentage of nominal.
    •NOMINAL SYSTEM FREQUENCY: Enter the nominal system frequency. The PQMII 
    measures frequency from the Van voltage and adjusts its internal sampling to best f it 
    the measured frequency. If the Van input is unavailable, the PQMII will assume the 
    frequency entered here.
    5.3.2 Analog Outputs
    PATH: SETPOINTS  S2 SYSTEM SETUP  ANALOG OUTPUT 1(4)
    The PQMII has four (4) Analog Outputs conf igured through four setpoints pages. The 
    ANALOG OUTPUT RANGE setpoint appears in the Analog Output 1 setpoints page only and 
    applies to all four outputs.
    •ANALOG OUTPUT RANGE: If the T20 option is installed, the Analog Outputs can be 
    conf igured to operate as 4 to 20 mA current sources or 0 to 20 mA current sources. All 
    four Analog Outputs will operate in the range def ined by this setpoint .
    •ANALOG OUTPUT 1(4) MAIN / ANALOG OUTPUT 1(4) ALT: If the PQMII is used in 
    conjunction with programmable controllers, automated equipment , or a chart 
    recorder, the analog outputs can be used for continuous monitoring. Although 
    parameters can be selected for continuous analog output , all values are available 
    digitally through the communications interface. Applications include using a 
    computer to automatically shed loads as the frequency decreases by monitoring 
    frequency or a chart recorder to plot the loading of a system in a particular process.
    Each of the analog outputs can be assigned to two of the parameters listed in the 
    Analog Output Parameters table. The analog output main selection is the default 
    selection and a programmable switch input can be programmed to multiplex the 
    ANALOG OUTPUT 1(4) ALT selection to the same output depending upon the open or closed 
    state of the switch input . See 5.3.4 Switch Inputs for details about conf iguring a switch 
    input . If no switch input is assigned as an analog output multiplexer, the analog output 
    main selection will be the only parameter which appears at the analog output 
    terminals. The ability to multiplex two different analog output quantities on one 
     ANALOG []
    OUTPUT 1ANALOG OUTPUT RANGE:
    4-20 mARange: 0-20 mA, 4-20 mA. Seen only in 
    the Analog Output 1 menu.
    MESSAGEANALOG OUTPUT 1 MAIN:
    Not UsedRange: refer to the Analog Output 
    Parameters table below
    MESSAGEMAIN 4 mA VALUE:
    0Range: refer to the Analog Output 
    Parameters table below
    MESSAGEMAIN 20 mA VALUE:
    0Range: refer to the Analog Output 
    Parameters table below
    MESSAGEANALOG OUTPUT 1 ALT:
    NOT USEDRange: refer to the Analog Output 
    Parameters table below
    MESSAGEALT 4 mA VALUE:
    0Range: refer to the Analog Output 
    Parameters table below
    MESSAGEALT 20 mA VALUE:
    0Range: refer to the Analog Output 
    Parameters table below 
    						
    							5–22PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 5: SETPOINTS
    analog output effectively gives the PQMII eight analog outputs. The table below shows 
    the criteria used by the PQMII to decide whether the output is based on MAIN or ALT 
    settings.
    •MAIN/ALT 4 mA VALUE: This message appears for each analog output and allows the 
    user to assign a numeric value which corresponds to the 4 mA end of the 4 to 20 mA 
    signal range (T20 option) or the 0 mA end of the 0 to 1 mA signal range (T1 option). The 
    numeric value range will depend upon which parameter is selected. See the 
    Analog 
    Output Parameters
     table below for details. Note that if the T20 option is installed and 
    the 
    ANALOG OUTPUT RANGE setpoint is set to “0-20 mA”, this message represents the 0 mA 
    end of the signal range.
    •MAIN/ALT 20 mA VALUE: This message appears for each analog output and allows 
    the user to assign a numeric value which corresponds to the 20 mA end of the 4 to 20 
    mA signal range (T20 option) or the 1 mA end of the 0 to 1 mA signal range (T1 option). 
    The numeric value range will depend upon which parameter is selected. See the 
    Analog Output Parameters table below.
    If the 4 mA (or 0 mA) value is programmed to be higher than the 20 mA (or 1 mA) value, 
    the analog output will decrease towards 4 mA (or 0 mA) as the value increases and the 
    analog output will increase towards 20 mA (or 1 mA) as the value decreases. If the 4 
    mA (or 0 mA) and 20 mA (or 1 mA) values are programmed to an identical value, the 
    output will always be 4 mA (or 0 mA).Table 5–3: Analog Output Selection Criteria
    Condition Present ‘Main’ 
    Parameter‘Alt’ Parameter Output 
    Based On
    Any condition “Not Used” “Not Used” Main
    Control option ‘C’ not installed any not available Main
    Switch assigned to 
    SELECT ANALOG 
    OUTPUT and is disabledany “Not Used” Main
    Switch assigned to 
    SELECT ANALOG 
    OUTPUT and is enabledany “Not Used” Main
    Any condition “Not Used”anything other 
    than “Not 
    Used”Alt
    Switch assigned to 
    SELECT ANALOG 
    OUTPUT and is disabled“Not Used”anything other 
    than “Not 
    Used”Alt
    Switch assigned to 
    SELECT ANALOG 
    OUTPUT and is enabledanyanything other 
    than “Not 
    Used”Alt 
    						
    							CHAPTER 5: SETPOINTS
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL5–23
    Table 5–4: Analog Output Parameters (Sheet 1 of 2)
    Parameter Range Step
    Phase A Current 0 to 150% 1%
    Phase B Current 0 to 150% 1%
    Phase C Current 0 to 150% 1%
    Neutral Current 0 to 150% 1%
    Average Phase Current 0 to 150% 1%
    Current Unbalance 0 to 100.0% 0.1%
    Voltage Van 0 to 200% 1%
    Voltage Vbn 0 to 200% 1%
    Voltage Vcn 0 to 200% 1%
    Voltage Vab 0 to 200% 1%
    Voltage Vbc 0 to 200% 1%
    Voltage Vca 0 to 200% 1%
    Average Phase Voltage 0 to 200% 1%
    Average Line Voltage 0 to 200% 1%
    Voltage Unbalance 0 to 100.0% 0.1%
    Frequency 00.00 to 75.00 Hz 0.01 Hz
    3 Phase PF 0.01 lead to 0.01 lag 0.01
    3 Phase kW –32500 to +32500 1 kW
    3 Phase kvar –32500 to +32500 1 kvar
    3 Phase kVA 0 to 65400 1 kVA
    3 Phase MW –3250.0 to +3250.0 0.1 MW
    3 Phase Mvar –3250.0 to +3250.0 0.1 Mvar
    3 Phase MVA 0 to 6540.0 0.1 MVA
    Phase A PF 0.01 lead to 0.01 lag 0.01
    Phase A kW –32500 to +32500 1 kW
    Phase A kvar –32500 to +32500 1 kvar
    Phase A kVA 0 to 65400 1 kVA
    Phase B PF 0.01 lead to 0.01 lag 0.01
    Phase B kW –32500 to +32500 1 kW
    Phase B kvar –32500 to +32500  1 kvar 
    						
    							5–24PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 5: SETPOINTS
    Phase B kVA 0 to 65400 1 kVA
    Phase C PF 0.01 lead to 0.01 lag 0.01
    Phase C kW –32500 to +32500 1 kW
    Phase C kvar –32500 to +32500 1 kvar
    Phase C kVA 0 to 65400 1 kVA
    3 Phase +kWh Used 0 to 65400 1 kWh
    3 Phase +kvarh Used 0 to 65400 1 kvarh
    3 Phase –kWh Used 0 to 65400 1 kWh
    3 Phase –kvarh Used 0 to 65400 1 kvarh
    3 Phase kVAh Used 0 to 65400 1 kVAh
    Phase A Current Demand 0 to 7500 1 A
    Phase B Current Demand 0 to 7500 1 A
    Phase C Current Demand 0 to 7500 1 A
    Neutral Current Demand 0 to 7500 1 A
    3 Phase kW Demand –32500 to +32500 1 kW
    3 Phase kvar Demand –32500 to +32500 1 kvar
    3 Phase kVA Demand 0 to 65400 1 kVA
    3 Phase Current THD 0.0 to 100% 0.1%
    3 Phase Voltage THD 0.0 to 100% 0.1%
    Phase A Current THD 0.0 to 100% 0.1%
    Phase B Current THD 0.0 to 100% 0.1%
    Phase C Current THD 0.0 to 100% 0.1%
    Voltage Van THD 0.0 to 100% 0.1%
    Voltage Vbn THD 0.0 to 100% 0.1%
    Voltage Vcn THD 0.0 to 100% 0.1%
    Voltage Vab THD 0.0 to 100% 0.1%
    Voltage Vbc THD 0.0 to 100% 0.1%
    Neutral Current THD 0.0 to 100% 0.1%
    Serial Control –32500 to +32500 1 UnitTable 5–4: Analog Output Parameters (Sheet 2 of 2)
    Parameter Range Step 
    						
    All GE manuals Comments (0)