GE Pqm 2 Manual
Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–1 PQMII Power Quality Meter Chapter 6: Monitoring Digital Energy Monit oring 6.1 Actual Values Viewing 6.1.1 Description Any measured value can be displayed on demand using the MENU and MESSAGE keys. Press the MENU key to select the actual values, then the MESSAGE RIGHT key to select the beginning of a new page of monitored values. These are grouped as follows: A1 Metering, A2 Status, A3 Power Analysis, and A4 Product Info. Use the MESSAGE keys to move between actual value messages. A detailed description of each displayed message in these groups is given in the sections that follow.
6–2PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.1.2 Actual Values Menu ACTUAL VALUES [] A1 METERING CURRENT []See page 6–4. MESSAGE VOLTAGE []See page 6–6. MESSAGE PHASORS []See page 6–8. MESSAGE POWER []See page 6–8. MESSAGE ENERGY []See page 6–12. MESSAGE DEMAND []See page 6–14. MESSAGE FREQUENCY []See page 6–15. MESSAGE PULSE INPUT [] COUNTERSSee page 6–16. MESSAGE ANALOG INPUT []See page 6–17. MESSAGE END OF PAGE A1 [] MESSAGE ACTUAL VALUES [] A2 STATUS ALARMS []See page 6–18. MESSAGE SWITCHES []See page 6–20. MESSAGE CLOCK []See page 6–21. MESSAGE PROGRAMMABLE [] MESSAGESee page 6–21. MESSAGE END OF PAGE A2 [] MESSAGE ACTUAL VALUES [] A3 POWER ANALYSIS POWER QUALITY [] VALUESSee page 6–22. MESSAGE TOTAL HARMONIC [] DISTORTIONSee page 6–22. MESSAGE DATA LOGGER []See page 6–24.
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–3 MESSAGE EVENT RECORDER []See page 6–24. MESSAGE VOLTAGE DIST. [] RECORDERSee page 6–28. MESSAGE END OF PAGE A3 [] MESSAGE ACTUAL VALUES [] A4 PRODUCT INFO SOFTWARE [] VERSIONSSee page 6–30. MODEL [] INFORMATIONSee page 6–30. MESSAGE END OF PAGE A4 []
6–4PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2 A1 Metering 6.2.1 Current Metering PATH: ACTUAL VALUES A1 METERING CURRENT •A, B, C CURRENT: Displays the current in each phase corresponding to the A, B, and C phase inputs. Current will be measured correctly only if the CT PRIMARY is entered to match the installed CT primary and the CT secondary is wired to match the 1 or 5 A input . If the displayed current does not match the actual current , check this setpoint and wiring. •Iavg/Vavg: Displays the average of the three phase currents and three voltages. This line is not visible if the VT WIRING setpoint is set to “Single Phase Direct”. L-N is displayed when VT WIRING is set to “4 Wire Wye /3 VTs”, “4 Wire Wye Direct”, “4 Wire Wye / 2 VTs”, or “3 Wire Direct”. L-L is displayed when VT WIRING is set to “3 Wire Delta / 2 VTs”. CURRENT [] A = 100 B = 100 C = 100 AMPS MESSAGEIavg = 100 AMPS Vavg = 120 V L-N MESSAGENEUTRAL CURRENT = 0 AMPS MESSAGECURRENT UNBALANCE = 0.0% MESSAGEIa MIN = 100 AMPS 12:00:00am 01/01/95 MESSAGEIb MIN = 100 AMPS 12:00:00am 01/01/95 MESSAGEIc MIN = 100 AMPS 12:00:00am 01/01/95 MESSAGEIn MIN = 100 AMPS 12:00:00am 01/01/95 MESSAGEI U/B MIN = 0.0% 12:00:00am 01/01/95 MESSAGEIa MAX = 100 AMPS 12:00:00am 01/01/95 MESSAGEIb MAX = 100 AMPS 12:00:00am 01/01/95 MESSAGEIc MAX = 100 AMPS 12:00:00am 01/01/95 MESSAGEIn MAX = 100 AMPS 12:00:00am 01/01/95 MESSAGEI U/B MAX = 0.0% 12:00:00am 01/01/95
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–5 •NEUTRAL CURRENT: Neutral current can be determined by two methods. One method measures the current via the neutral CT input . The second calculates the neutral current based on the three phase currents; using the instantaneous samples, Ia + Ib + Ic = In. If the sum of the phase currents does not equal 0, the result is the neutral current . When using the CT input , the neutral current reading will be correct only if the CT is wired correctly and the correct neutral CT primary value is entered. Verify neutral current by connecting a clamp-on ammeter around all 3 phases. If the neutral current appears incorrect , check the settings in S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION and verify the CT wiring. •CURRENT UNBALANCE: Displays the percentage of current unbalance. Current unbalance is calculated as: (EQ 0.1) where:Iav = average phase current = (Ia + Ib + Ic) / 3 I m = current in phase with maximum deviation from Iav, Even though it is possible to achieve unbalance greater than 100% with the above formula, the PQMII limits unbalance readings to 100%. If the average current is below 10% of the CT PRIMARY setpoint , the unbalance reading is forced to 0%. This avoids nuisance alarms when the system is lightly loaded. If the simulation currents are being used, the unbalance is never forced to 0%. •Ia, Ib, Ic, In MIN: Displays the minimum current magnitudes and the time and date of their occurrence. This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX CURRENT VALUE S setpoint clears these values. •I U/B MIN: Displays the minimum current unbalance and the time and date of its measurement . This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX CURRENT VALUE S setpoint clears this value. •Ia, Ib, Ic, In MAX: Displays the maximum current magnitudes and the time and date of their occurrence. This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX CURRENT VALUE S setpoint clears these values. •I U/B MAX: Displays the maximum current unbalance and the time and date of its measurement . This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX CURRENT VALUE S setpoint command clears this value. Current UnbalanceImIav– I av --------------------- 100 % × =
6–6PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2.2 Voltage Metering PATH: ACTUAL VALUES A1 METERING VOLTAGE VOLTAGE [] Van = 120 Vbn = 120 Vcn = 120 V MESSAGEIavg = 100 AMPS Vavg = 120 V L-N MESSAGEVab= 0 Vbc= 0 Vca= 0 V MESSAGEAVERAGE LINE VOLTAGE = 208 V MESSAGEVOLTAGE UNBALANCE = 0.0% MESSAGEVan MIN = 100 V 12:00:00am 01/01/95 MESSAGEVbn MIN = 100 V 12:00:00am 01/01/95 MESSAGEVcn MIN = 100 V 12:00:00am 01/01/95 MESSAGEVab MIN = 173 V 12:00:00am 01/01/95 MESSAGEVbc MIN = 173 V 12:00:00am 01/01/95 MESSAGEVca MIN = 173 V 12:00:00am 01/01/95 MESSAGEV U/B MIN = 0.0% 12:00:00am 01/01/95 MESSAGEVan MAX = 140 V 12:00:00am 01/01/95 MESSAGEVbn MAX = 140 V 12:00:00am 01/01/95 MESSAGEVcn MAX = 140 V 12:00:00am 01/01/95 MESSAGEVab MAX = 242 V 12:00:00am 01/01/95 MESSAGEVbc MAX = 242 V 12:00:00am 01/01/95 MESSAGEVca MAX = 242 V 12:00:00am 01/01/95 MESSAGEV U/B MAX = 5.1% 12:00:00am 01/01/95
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–7 •Van, Vbn, Vcn: Displays phase voltages corresponding to the A, B, and C voltage inputs. This voltage will be measured correctly only if the VT RATIO, VT NOMINAL SECONDARY , and VOLTAGE WIRING setpoints match the installed VTs. If the displayed voltage does not match the actual voltage, check the setpoints and wiring. This message appears only if the VT WIRING is conf igured for a wye input . •Iavg/Vavg: Displays the average of the three phase currents/voltages. This value is not visible if the VT WIRING setpoint is set to “Single Phase Direct”. L-N is displayed when VT WIRING is set to “4 Wire Wye / 3 VTs”, “4 Wire Wye Direct”, “4 Wire Wye / 2 VTs”, or “3 Wire Direct” and L-L is displayed when VT WIRING is set to “3 Wire Delta / 2 VTs”. •Vab, Vbc, Vca: Displays line voltages corresponding to the A, B, and C voltage inputs. The measured voltage is correct only if the VT RATIO, VT NOMINAL SECONDARY, and VOLTAGE WIRING setpoints match the installed VTs. If the displayed voltage does not match the actual voltage, check the setpoints and wiring. •AVERAGE LINE VOLTAGE: Displays the average of the three line voltages. This value is not visible if the VT WIRING setpoint is set to “Single Phase Direct”. •VOLTAGE UNBALANCE: Displays the percentage voltage unbalance. Voltage unbalance is calculated as shown below. If the VOLTAGE WIRING is conf igured for a wye input , voltage unbalance is calculated using phase quantities. If the VT WIRING is conf igured as a delta input , voltage unbalance is calculated using line voltages. (EQ 0.2) where:Vavg= average phase voltage = (Van + Vbn + Vcn) / 3 for “Wye” and “3 Wire Direct” connections; = average line voltage = ( Vab + Vbc + Vca) / 3 for “3 Wire Delta / 2 VTs” connection Vm = voltage in a phase (or line) with maximum deviation from Vavg. NoteEven though it is possible to achieve unbalance greater than 100% with the above formula, the PQMII will limit unbalance readings to 100%. If the average voltage is below 10% of VT RATIO×VT NOMINAL SECONDARY VOLTAGE for “3 Wire Delta / 2 VTs”, “4 Wire Wye / 3 VTs”, and “4 Wire Wye / 2 VTs” connections, or below 10% of VT RATIO×NOMINAL DIRECT INPUT VOLTAGE for “4 Wire Wye/Direct” and “3 Wire Direct” connections, the unbalance reading is forced to 0%. This is implemented to avoid nuisance alarms when the system is lightly loaded. If the simulation voltages are being used, the unbalance is never forced to 0%. •Van, Vbn, Vcn MIN/MAX: Displays the minimum/maximum phase voltage magnitudes and the time and date of their occurrence. This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX VOLTAGE VALUES setpoint clears these values. •Vab, Vbc, Vca MIN/MAX: Displays the minimum/maximum line voltage magnitudes and the time and date of their occurrence. This information is stored in non-volatile memory and is retained during loss of control power. The S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX VOLTAGE VALUES setpoint clears these values. •V U/B MIN/MAX: Displays minimum/maximum voltage unbalance and the time and date of its measurement . This information is stored in non-volatile memory and is retained during loss of control power. This value is cleared with the S1 PQMII SETUP CLEAR DATA CLEAR MIN/MAX VOLTAGE VALUES setpoint . Voltage UnbalanceVmVavg– V avg--------------------------- 100 % × =
6–8PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2.3 Phasors PATH: ACTUAL VALUES A1 METERING PHASORS •Va PHASOR: Displays a phasor representation for the magnitude and angle of Va. Va is used as a reference for all other phasor angles. If there is no voltage present at the PQMII voltage inputs, then Ia will be used as the reference for all other angles. Va is also used as the reference when in Simulation Mode. •Vb/Vc PHASOR: Displays a phasor representation for the magnitude and angle of Vb/ Vc. Both VB and VC PHASOR values use the angle of VA PHASOR as a reference point . If there is no voltage at the PQMII voltage inputs, IA PHASOR is used as the reference. These setpoints are not displayed when the PQMII is conf igured for the “3 Wire Delta/2 VTs”, “4 Wire Wye/2 VTs”, or “Single Phase Direct” connections. •Ia PHASOR: A phasor representation for the magnitude and angle of Ia is displayed here. Ia is used as a reference for all other Phasor angles only when there is no voltage present at the PQMII voltage inputs, otherwise, Va is used as the reference. •Ib/Ic PHASOR: A phasor representation for the magnitude and angle of Ib/Ic is displayed here. The Ib and Ic currents use the angle of Va as a reference point . If there is no voltage at the PQMII voltage inputs, Ia is used as the reference. These setpoints are is not displayed when the PQMII is configured for “Single Phase Direct” connection. 6.2.4 Power Metering PATH: ACTUAL VALUES A1 METERING POWER PHASORS [] Va PHASOR: 0V at 0° Lag MESSAGEVb PHASOR: 0V at 0° Lag MESSAGEVc PHASOR: 0V at 0° Lag MESSAGEIa PHASOR: 0A at 0° Lag MESSAGEIb PHASOR: 0A at 0° Lag MESSAGEIc PHASOR: 0A at 0° Lag POWER [] THREE PHASE REAL POWER = 1000 kW MESSAGETHREE PHASE REACTIVE POWER = 120 kvar MESSAGETHREE PHASE APPARENT POWER = 1007 kVA MESSAGETHREE PHASE POWER FACTOR = 0.99 Lag
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–9 MESSAGE PHASE A REAL POWER = 1000 kW MESSAGEPHASE A REACTIVE POWER = 120 kvar MESSAGEPHASE A APPARENT POWER = 1007 kVA MESSAGEPHASE A POWER FACTOR = 0.99 Lag MESSAGEPHASE B REAL POWER = 1000 kW MESSAGEPHASE B REACTIVE POWER = 120 kvar MESSAGEPHASE B APPARENT POWER = 1007 kVA MESSAGEPHASE B POWER FACTOR = 0.99 Lag MESSAGEPHASE C REAL POWER = 1000 kW MESSAGEPHASE C REACTIVE POWER = 120 kvar MESSAGEPHASE C APPARENT POWER = 1007 kVA MESSAGEPHASE C POWER FACTOR = 0.99 Lag MESSAGETHREE PHASE REAL POWER = 10.00 MW MESSAGETHREE PHASE REACTIVE POWER = 1.20 Mvar MESSAGETHREE PHASE APPARENT POWER = 10.07 MVA MESSAGE3Φ kW MIN = 1000 12:00:00am 01/01/95 MESSAGE3Φ kvar MIN = 120 12:00:00am 01/01/95 MESSAGE3Φ kVA MIN = 1007 12:00:00am 01/01/95 MESSAGE3Φ PF MIN = 0.99 Lag 12:00:00am 01/01/95 MESSAGE3Φ kW MAX = 1000 12:00:00am 01/01/95 MESSAGE3Φ kvar MAX = 120 12:00:00am 01/01/95
6–10PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING MESSAGE3Φ kVA MAX = 1007 12:00:00am 01/01/95 MESSAGE3Φ PF MAX = 0.99 Lag 12:00:00am 01/01/95 MESSAGEAΦ kW MIN = 1000 12:00:00am 01/01/95 MESSAGEAΦ kvar MIN = 120 12:00:00am 01/01/95 MESSAGEAΦ kVA MIN = 1007 12:00:00am 01/01/95 MESSAGEAΦ PF MIN = 0.99 Lag 12:00:00am 01/01/95 MESSAGEAΦ kW MAX = 1000 12:00:00am 01/01/95 MESSAGEAΦ kvar MAX = 120 12:00:00am 01/01/95 MESSAGEAΦ kVA MAX = 1007 12:00:00am 01/01/95 MESSAGEAΦ PF MAX = 0.99 Lag 12:00:00am 01/01/95 MESSAGEBΦ kW MIN = 1000 12:00:00am 01/01/95 MESSAGEBΦ kvar MIN = 120 12:00:00am 01/01/95 MESSAGEBΦ kVA MIN = 1007 12:00:00am 01/01/95 MESSAGEBΦ PF MIN = 0.99 Lag 12:00:00am 01/01/95 MESSAGEBΦ kW MAX = 1000 12:00:00am 01/01/95 MESSAGEBΦ kvar MAX = 120 12:00:00am 01/01/95 MESSAGEBΦ kVA MAX = 1007 12:00:00am 01/01/95 MESSAGEBΦ PF MAX = 0.99 Lag 12:00:00am 01/01/95 MESSAGECΦ kW MIN = 1000 12:00:00am 01/01/95 MESSAGECΦ kvar MIN = 120 12:00:00am 01/01/95