Home > GE > Power Products > GE Pqm 2 Manual

GE Pqm 2 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							CHAPTER 6: MONITORING
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL6–21
    To assist in troubleshooting, the state of each switch can be verif ied using these messages. 
    A separate message displays the status of each input identif ied by the corresponding 
    name as shown in the wiring diagrams in chapter 2. For a dry contact closure across the 
    corresponding switch terminals the message will read “Closed”.
    6.3.3 Clock
    PATH: ACTUAL VALUES  A2 STATUS  CLOCK
    The current time and date is displayed in this message. The PQMII uses an internally 
    generated software clock which runs for approximately thirty days after the control power 
    has been removed. For instructions on setting the clock, see 5.2.6 Clock. The 
    S4 ALARMS/
    CONTROL  MISCELLANEOUS  CLOCK NOT SET ALARM
     alarm occurs if power has been removed 
    for longer than thirty days and the clock value has been lost .
    6.3.4 Programmable Message
    PATH: ACTUAL VALUES  A2 STATUS  PROGRAMMABLE MESSAGE
    A 40-character user def ined message is displayed. The message is programmed using the 
    keypad or via the serial port using the EnerVista PQMII Setup Software. See 6.3.4 
    Programmable Message for programming details.
     CLOCK [] TIME: 12:00:00am
    DATE: Nov 21 2003
     PROGRAMMABLE []
    MESSAGEPHONE: 905-294-6222
    www.GEmultilin.com 
    						
    							6–22PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 6: MONITORING
    6.4 A3 Power Analysis
    6.4.1 Power Quality
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  POWER QUALITY VALUES
    •Ia/Ib/Ic CREST FACTOR: The crest factor describes how much the load current can 
    vary from a pure sine wave while maintaining the system’s full rating. A completely 
    linear load (pure sine wave) has a crest factor of   (1 /0.707), which is the ratio of the 
    peak value of sine wave to its RMS value. Typically, the crest factor can range from   
    to 2.5.
    •Ia/Ib/Ic THDF: The Transformer Harmonic Derating Factor (THDF), also known as 
    CBEMA factor, is def ined as the crest factor of a pure sine wave ( ) divided by the 
    measured crest factor. This method is useful in cases where lower order harmonics are 
    dominant . In a case where higher order harmonics are present , it may be necessary 
    to use a more precise method (K-factor) of calculating the derating factor. This method 
    also does not take into consideration the losses associated with rated eddy current in 
    the transformer. The EnerVista PQMII Setup Software provides the K-factor method of 
    calculating the derating factor, which is def ined on a per unit basis as follows:
    (EQ 6.3)
    where:Ih = RMS current at harmonic h, in per unit of rated RMS load current
    6.4.2 THD
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  TOTAL HARMONIC DISTORTION
     POWER QUALITY []
    VALUESIa CREST FACTOR =
    1.233
    MESSAGEIb CREST FACTOR =
    1.008
    MESSAGEIc CREST FACTOR =
    1.000
    MESSAGEIa THDF = 0.944
    MESSAGEIb THDF = 0.999
    MESSAGEIc THDF = 0.988
    2
    2
    2
    KIh 2h2×
    h1 = h
    max
    =
     TOTAL HARMONIC []
    DISTORTIONPHASE A CURRENT THD=
    5.3%
    MESSAGEPHASE B CURRENT THD=
    7.8% 
    						
    							CHAPTER 6: MONITORING
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL6–23
    •PHASE A/B/C/N CURRENT THD: These messages display the calculated total 
    harmonic distortion for each current input .
    •VOLTAGE Van/Vbn/Vcn/Vab/Vbc THD: These messages display the calculated total 
    harmonic distortion for each voltage input . Phase-to-neutral voltages will appear 
    when the setpoint 
    S2 SYSTEM SETUP  CURRENT/VOLTAGE CONFIGURATION  VT WIRING is set 
    as “Wye”. Line-to-line voltages will appear when 
    VT WIRING is set as “Delta”.
    •Ia/Ib/Ic/In MAX THD: The maximum total harmonic value for each current input and 
    the time and date which the maximum value occurred are displayed. The 
    S1 PQMII SETUP 
     CLEAR DATA \ CLEAR MAX THD VALUES
     setpoint clears this value.
    MESSAGEPHASE C CURRENT THD=
    4.5%
    MESSAGENEUTRAL CURRENT THD=
    15.4%
    MESSAGEVOLTAGE Van THD=
    1.2%
    MESSAGEVOLTAGE Vbn THD=
    2.0%
    MESSAGEVOLTAGE Vcn THD=
    2.0%
    MESSAGEVOLTAGE Vab THD=
    2.0%
    MESSAGEVOLTAGE Vbc THD=
    1.1%
    MESSAGEIa MAX THD =  5.9%
    12:00:00am 01/01/95
    MESSAGEIb MAX THD =  7.8%
    12:00:00am 01/01/95
    MESSAGEIc MAX THD =  4.5%
    12:00:00am 01/01/95
    MESSAGEIn MAX THD =  15.4%
    12:00:00am 01/01/95
    MESSAGEVan MAX THD =  1.2%
    12:00:00am 01/01/95
    MESSAGEVbn MAX THD =  2.0%
    12:00:00am 01/01/95
    MESSAGEVcn MAX THD =  2.0%
    12:00:00am 01/01/95
    MESSAGEVab MAX THD =  2.0%
    12:00:00am 01/01/95
    MESSAGEVbc MAX THD =  1.1%
    12:00:00am 01/01/9 
    						
    							6–24PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 6: MONITORING
    •Van/Vbn/Vcn/Vab/Vbc MAX THD: These messages display the maximum total 
    harmonic value for each voltage input and the time and date of its occurrence. The 
    setpoint 
    S1 PQMII SETUP  CLEAR DATA \CLEAR MAX THD VALUES is used to clear this value. 
    Phase to neutral voltages will appear when the setpoint 
    S2 SYSTEM SETUP  CURRENT/
    VOLTAGE CONFIGURATION  VT WIRING
     is set to “Wye”. Line to line voltages will appear 
    when 
    VT WIRING is set to “Delta”.
    6.4.3 Data Logger
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  DATA LOGGER
    These message display the current status of Data Loggers 1 and 2. The Data Logger can 
    be set up and run only from the EnerVista PQMII Setup Software. See 4.5.4 Data Logger and 
    7.6 Data Logger Implementation for additional details on the Data Logger feature.
    It is possible to stop the data loggers from the PQMII front panel using the 
    S2 SYSTEM SETUP 
     DATA LOGGER  STOP DATA LOGGER 1(2)
     setpoint .
    6.4.4 Event Recorder
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  EVENT RECORDER
    The PQMII Event Recorder runs continuously and records the number, cause, time, date, 
    and metering quantities present at the occurrence of each event . This data is stored in 
    non-volatile memory and is not lost when power to the PQMII is removed. The Event 
    Recorder must be enabled in 
    S1 PQMII SETUP  EVENT RECORDER  EVENT RECORDER OPERATION. 
    The Event Recorder can be cleared in 
    S1 PQMII SETUP  CLEAR DATA  CLEAR EVENT RECORD. 
    Data for the 150 most recent events is stored. Event data for older events is lost . Note that 
    the event number, cause, time, and date is available in the messages as shown in the 
    following table, but the associated metering data is available only via serial 
    communications.
    NoteThe event data stored for POWER OFF events does not reflect values at the time of 
    power-off.
    These messages display the 150 most recent events recorded by the event recorder. The 
    list of possible events and their display on the PQMII is shown below.
     DATA LOGGER [] DATA LOG 1: STOPPED:
    0% FULL
    MESSAGEDATA LOG 2: STOPPED:
    0% FULL
     EVENT RECORDER [] 3: POWER ON
    12:00:00am 01/01/03
    MESSAGE2: POWER OFF
    12:00:00am 01/01/03
    MESSAGE1: CLEAR RECORDS
    12:00:00am 01/01/03 
    						
    							CHAPTER 6: MONITORING
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL6–25
    Table 6–1: List of Possible Events (Sheet 1 of 4)
    Displayed Event Name Event Description
    3Φ +kvar DMD ↑Positive Reactive Power Demand Alarm/Control Pickup
    3Φ +kvar DMD ↓Positive Reactive Power Demand Alarm/Control Dropout
    3Φ +kW DMD ↑Positive Real Power Demand Alarm/Control Pickup
    3Φ +kW DMD ↓Positive Real Power Demand Alarm/Control Dropout
    3Φ kVA DEMAND ↑Apparent Power Demand Alarm/Control Pickup
    3Φ kVA DEMAND ↓Apparent Power Demand Alarm/Control Dropout
    3Φ –kvar DMD ↑Negative Reactive Power Demand Alarm/Control Pickup
    3Φ –kvar DMD ↓Negative Reactive Power Demand Alarm/Control Dropout
    3Φ –kW DMD ↑Negative Real Power Demand Alarm/Control Pickup
    3Φ –kW DMD ↓Negative Real Power Demand Alarm/Control Dropout
    ALARM RESET Latched Alarm/Auxiliary Reset
    AN INPUT ALT ↑Alternate Analog Input Alarm/Control Pickup
    AN INPUT ALT ↓Alternate Analog Input Alarm/Control Dropout
    AN INPUT MAIN ↑Main Analog Input Alarm/Control Pickup
    AN INPUT MAIN ↓Main Analog Input Alarm/Control Dropout
    CLOCK NOT SET ↑Clock Not Set Alarm Pickup
    CLOCK NOT SET ↓Clock Not Set Alarm Dropout
    COM1 FAILURE ↑COM1 Failure Alarm Pickup
    COM1 FAILURE ↓COM1 Failure Alarm Dropout
    COM2 FAILURE ↑COM2 Failure Alarm Pickup
    COM2 FAILURE ↓COM2 Failure Alarm Dropout
    CURRENT THD ↑Current THD Alarm/Control Pickup
    CURRENT THD ↓Current THD Alarm/Control Dropout
    CURRENT U/B ↑Current Unbalance Alarm/Control Pickup
    CURRENT U/B ↓Current Unbalance Alarm/Control Dropout
    DATA LOG 1 ↑Data Log 1 Alarm Pickup
    DATA LOG 1 ↓Data Log 1 Alarm Dropout
    DATA LOG 2 ↑
    Data Log 2 Alarm Pickup
    DATA LOG 2 ↓Data Log 2 Alarm Dropout
    Ia DEMAND ↑Phase A Current Demand Alarm/Control Pickup 
    						
    							6–26PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 6: MONITORING
    Ia DEMAND ↓Phase A Current Demand Alarm/Control Dropout
    Ib DEMAND ↑Phase B Current Demand Alarm/Control Pickup
    Ib DEMAND ↓Phase B Current Demand Alarm/Control Dropout
    Ic DEMAND ↑Phase C Current Demand Alarm/Control Pickup
    Ic DEMAND ↓Phase C Current Demand Alarm/Control Dropout
    In DEMAND ↑Neutral Current Demand Alarm/Control Pickup
    In DEMAND ↓Neutral Current Demand Alarm/Control Dropout
    NEG kvar ↑Negative Reactive Power Alarm/Control Pickup
    NEG kvar ↓Negative Reactive Power Alarm/Control Dropout
    NEG kW ↑Negative Real Power Alarm/Control Pickup
    NEG kW ↓Negative Real Power Alarm/Control Dropout
    NEUTRAL ↑Neutral Overcurrent Alarm/Control Pickup
    NEUTRAL ↓Neutral Overcurrent Alarm/Control Dropout
    OVERCURRENT ↑Overcurrent Alarm/Control Pickup
    OVERCURRENT ↓Overcurrent Alarm/Control Dropout
    OVERFREQUENCY ↑Overfrequency Alarm/Control Pickup
    OVERFREQUENCY ↓Overfrequency Alarm/Control Dropout
    OVERVOLTAGE ↑Overvoltage Alarm/Control Pickup
    OVERVOLTAGE ↓Overvoltage Alarm/Control Dropout
    PARAM NOT SET ↑Critical Setpoints Not Stored Alarm Pickup
    PARAM NOT SET ↓Critical Setpoints Not Stored Alarm Dropout
    PF LAG 1 ↑Power Factor Lag 1 Alarm/Control Pickup
    PF LAG 1 ↓Power Factor Lag 1 Alarm/Control Dropout
    PF LAG 2 ↑Power Factor Lag 2 Alarm/Control Pickup
    PF LAG 2 ↓Power Factor Lag 2 Alarm/Control Dropout
    PF LEAD 1 ↑Power Factor Lead 1 Alarm/Control Pickup
    PF LEAD 1 ↓Power Factor Lead 1 Alarm/Control Dropout
    PF LEAD 2 ↑Power Factor Lead 2 Alarm/Control Pickup
    PF LEAD 2 ↓Power Factor Lead 2 Alarm/Control Dropout
    PHASE REVERSAL↑Phase Reversal Alarm/Control Pickup
    PHASE REVERSAL↓Phase Reversal Alarm/Control Dropout Table 6–1: List of Possible Events (Sheet 2 of 4)
    Displayed Event Name Event Description 
    						
    							CHAPTER 6: MONITORING
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL6–27
    POS kvar ↑Positive Reactive Power Alarm/Control Pickup
    POS kvar ↓Positive Reactive Power Alarm/Control Dropout
    POS kW ↑Positive Real Power Alarm/Control Pickup
    POS kW ↓Positive Real Power Alarm/Control Dropout
    POWER OFF Power Off
    POWER ON Power On
    PROGRAM ENABLE Setpoint Access On
    PULSE IN 1 ↑Pulse Input 1 Alarm/Control Pickup
    PULSE IN 1 ↓Pulse Input 1 Alarm/Control Dropout
    PULSE IN 2 ↑Pulse Input 2 Alarm/Control Pickup
    PULSE IN 2 ↓Pulse Input 2 Alarm/Control Dropout
    PULSE IN 3 ↑Pulse Input 3 Alarm/Control Pickup
    PULSE IN 3 ↓Pulse Input 3 Alarm/Control Dropout
    PULSE IN 4 ↑Pulse Input 4 Alarm/Control Pickup
    PULSE IN 4 ↓Pulse Input 4 Alarm/Control Dropout
    PULSE TOTAL ↑Totalized Pulses Alarm/Control Pickup
    PULSE TOTAL ↓Totalized Pulses Alarm/Control Dropout
    SELF TEST ↑Self Test Failure Alarm Pickup
    SELF TEST ↓Self Test Failure Alarm Dropout
    SW A ACTIVE ↑Switch Input A Alarm/Control Pickup
    SW A ACTIVE ↓Switch Input A Alarm/Control Dropout
    SW B ACTIVE ↑Switch Input B Alarm/Control Pickup
    SW B ACTIVE ↓Switch Input B Alarm/Control Dropout
    SW C ACTIVE ↑Switch Input C Alarm/Control Pickup
    SW C ACTIVE ↓Switch Input C Alarm/Control Dropout
    SW D ACTIVE ↑Switch Input D Alarm/Control Pickup
    SW D ACTIVE ↓Switch Input D Alarm/Control Dropout
    TIME ↑T ime Alarm/Control Pickup
    TIME ↓T ime Alarm/Control Dropout
    TRACE TRIG ↑Trace Memory Triggered
    UNDERCURRENT ↑Undercurrent Alarm/Control Pickup Table 6–1: List of Possible Events (Sheet 3 of 4)
    Displayed Event Name Event Description 
    						
    							6–28PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 6: MONITORING
    6.4.5 Voltage Disturbance
    Main Menu
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  VOLTAGE DIST. RECORDER
    The Voltage Disturbance Recorder runs continuously and records the source, level and 
    duration of each voltage disturbance. Up to 500 disturbances are recorded in a circular 
    buffer. When over 500 disturbances are recorded, data for older disturbances are lost as 
    new disturbances are recorded. Additionally, since the events are stored within volatile 
    memory, the voltage disturbance recorder will lose all events upon a power loss. The time 
    and date of when the disturbance 
    ended is recorded with the disturbance event . The 
    following available is available for each disturbance:
    •Type: Each disturbance is classif ied as a 
    SWELL or SAG. The disturbance will be 
    distinguished as a swell if the voltage increases above the swell level, for up to 1 
    minute. A sag disturbance is distinguished in the same manner except that it involves 
    a voltage decrease below the sag level.
    •Source: The source of the disturbance is the phase voltage that recorded the 
    disturbance; either Van, Vbn, Vcn, Vab, or Vca. If the disturbance is found on two or 
    more phases, multiple disturbances will be recorded.
    NoteThe voltage disturbance recorder monitors only measured values. Therefore, when the 
    Vbc (delta connection only) and Vbn (2 VT 4-Wire Wye only) phases are calculated 
    quantities, they are not considered a source.UNDERCURRENT ↓Undercurrent Alarm/Control Dropout
    UNDERVOLTAGE ↑Undervoltage Alarm/Control Pickup
    UNDERVOLTAGE ↓Undervoltage Alarm/Control Dropout
    UNDRFREQUENCY ↑Underfrequency Alarm/Control Pickup
    UNDRFREQUENCY ↓Underfrequency Alarm/Control Dropout
    VOLTAGE THD ↑Voltage THD Alarm/Control Pickup
    VOLTAGE THD ↓Voltage THD Alarm/Control Dropout
    VOLTAGE U/B ↑Voltage Unbalance Alarm/Control Pickup
    VOLTAGE U/B ↓Voltage Unbalance Alarm/Control Dropout Table 6–1: List of Possible Events (Sheet 4 of 4)
    Displayed Event Name Event Description
     VOLTAGE DIST. []
    RECORDER3: Van SWELL
    12:00:05am 01/01/03
    MESSAGE2: Vbn SAG
    12:00:02am 01/01/03
    MESSAGE1: Vcn SAG
    12:00:00am 01/01/03 
    						
    							CHAPTER 6: MONITORING
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL6–29
    The duration and average level are recorded in sub-menus as shown below.
    Sub-Menus
    PATH: ACTUAL VALUES  A3 POWER ANALYSIS  VOLTAGE DIST...  1(500): 
    The DURATION is the length of time of the disturbance. If the disturbance is either a sag or a 
    swell the duration will be recorded in cycles with a maximum possible value of 1 minute 
    (3600 cycles at 60Hz).
    The 
    VOLTAGE LEVEL represents the average level in volts for the disturbance.
    NoteThe voltage disturbance recorder is independent from the event recorder. The alarm 
    events will record normally as per the conditions set within the 
    S4 ALARMS  CONTROL 
    settings menu, regardless whether the voltage disturbance recorder is enabled or of 
    the sag/swell level.
    If an undervoltage/overvoltage alarm occurs, it is immediately recorded as an event (if 
    enabled). On the other hand, the voltage disturbance is recorded, if enabled, once the 
    voltage level returns to nominal and the condition is complete. As a result , the time 
    recorded in the event recorder is the start time of the alarm condition, while the time 
    recorded in the disturbance recorder is the end time of the condition.
    1: Vcn SAG
    12:00:00am 01/01/031 DURATION:
    65 cycles
    MESSAGE1 VOLTAGE LEVEL:
    4125 V 
    						
    							6–30PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 6: MONITORING
    6.5 A4 Product Info
    6.5.1 Software Versions
    PATH: ACTUAL VALUES  A4 PRODUCT INFO  SOFTWARE VERSIONS
    Product software revision information is contained in these messages.
    •MAIN PROGRAM VERSION: When referring to documentation or requesting technical 
    assistance from the factory, record the 
    MAIN PROGRAM VERSION. This value identif ies 
    the f irmware installed internally in the flash memory. The title page of this instruction 
    manual states the main program revision code for which the manual is written. There 
    may be differences in the product and manual if the revision codes do not match.
    •BOOT PROGRAM VERSION: This identif ies the f irmware installed internally in the 
    memory of the PQMII. This does not affect the functionality of the PQMII.
    6.5.2 Model Information
    PATH: ACTUAL VALUES  A4 PRODUCT INFO  MODEL INFORMATION
    Product identif ication information is contained in these messages.
    •ORDER CODE: This indicates which features were ordered with this PQMII. T = 
    Transducer option (T20 = 4-20 mA, T1 = 0-1 mA Analog Outputs), C = Control option, A 
    = Power Analysis option.
    •CPU SPEED: Newer hardware revisions support the 25 MHz CPU speed, while older 
    revisions only support 16 MHz. Certain features are only available on the 25 MHz 
    platform (such as the Voltage Disturbance Recorder).
    •MOD NUMBER(S): If unique features have been installed for special customer orders, 
    the 
    MOD NUMBER will be used by factory personnel to identify the matching product 
     SOFTWARE []
    VERSIONSMAIN PROGRAM VER:
    2.22 MAY 09, 2006
    MESSAGEBOOT PROGRAM VER:
    3.00
     MODEL []
    INFORMATIONORDER CODE:
    PQMII-T20-C-A
    MESSAGECPU SPEED:
    25 MHz
    MESSAGEMOD NUMBER(S): 000
    MESSAGESERIAL NUMBER:
    C7387777
    MESSAGEDATE OF MANUFACTURE:
    Aug 29 2003
    MESSAGEDATE OF CALIBRATION:
    Aug 29 2003 
    						
    All GE manuals Comments (0)