Home > GE > Power Products > GE Pqm 2 Manual

GE Pqm 2 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Pqm 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							CHAPTER 2: INSTALLATION
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL2–11
    For a single-phase connection, connect current and voltage to the phase A inputs only. All 
    other inputs are ignored. Select the 
    S2 SYSTEM SETUP  CURRENT/VOLTAGE CONFIGURATION  VT 
    WIRING:
     “SINGLE PHASE” setpoint .
    FIGURE 2–8: Single Phase Connection 
    						
    							2–12PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 2: INSTALLATION
    2.2.3 3-wire System using Two CTs
    The f igure below shows two methods for connecting CTs to the PQMII for a 3-wire system. 
    The top drawing shows the standard wiring conf iguration using three CTs. An alternate 
    wiring conf iguration uses only two CTs. With the two CT method, the third phase is 
    measured by connecting the commons from phase A and C to the phase B input on the 
    PQMII. This causes the phase A and phase C current to flow through the PQMII’s phase B CT 
    in the opposite direction, producing a current equal to the actual phase B current .
    Ia + Ib + Ic = 0 for a three wire system.
    Ib = – (Ia + Ic)
    For the CT connections above, the 
    S2 SYSTEM SETUP  CURRENT/VOLTAGE CONFIGURATION  
    PHASE CT WIRING  PHASE CT PRIMARY
     setpoint must be set to PHASE A, B, AND C. 
    FIGURE 2–9: Alternate CT Connections for 3-wire System 
    						
    							CHAPTER 2: INSTALLATION
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL2–13
    2.2.4 Control Power
    The control power supplied to the PQMII must match the installed power supply. If the 
    applied voltage does not match, damage to the unit may occur. Check the product 
    identif ication to verify the control voltage matches the intended application.
    A universal AC/DC power supply is standard on the PQMII. It covers the range 90 to 300 V 
    DC and 70 to 265 V AC at 50/60 Hz. It is not necessary to adjust the PQMII if the control 
    voltage is within this range. A low voltage power supply is available as an option. It covers 
    the range 20 to 60 V DC and 24 to 48 V AC at 50/60 Hz. Verify from the product 
    identif ication label that the control voltage matches the intended application. Connect the 
    control voltage input to a stable source for reliable operation. A 2.5 A HRC fuse is 
    accessible from the back of the PQMII via the fuse access door. Consult the factory for 
    replacement fuses, if required. Using #12 gauge wire or ground braid, connect Terminals 5 
    and 6 to a solid system ground, typically a copper bus in the switchgear. The PQMII 
    incorporates extensive f iltering and transient protection to ensure reliable operation under 
    harsh industrial operating environments. Transient energy must be conducted back to the 
    source through Filter Ground Terminal (5). The Filter Ground Terminal (5) is separated from 
    the Safety Ground Terminal (6) to allow dielectric testing of switchgear with the PQMII 
    wired up. Filter Ground Terminal connections must be removed during dielectric testing.
    When properly installed, the PQMII meets the interference immunity requirements of IEC 
    801 and ANSI C37.90.1.
    2.2.5 VT Inputs
    The PQMII accepts input voltages from 0 to 600 V AC between the voltage inputs (V1, V2, 
    V3) and voltage common (Vn). These inputs can be directly connected or supplied through 
    external VTs. If voltages greater than 600 V AC are to be measured, external VTs are 
    required. When measuring line-to-line quantities using inputs V1, V2, and V3, ensure that 
    the voltage common input Vn is grounded. This input is used as a reference for measuring 
    the voltage inputs.
    All connections to the PQMII voltage inputs should be connected using HRC fuses rated at 
    2 Amps to ensure adequate interrupting capacity.
    2.2.6 CT Inputs
    Current transformer secondaries of 1 A or 5 A can be used with the PQMII for phase and 
    neutral sensing. Each current input has 3 terminals: 5 A input , 1 A input , and common. 
    Select either the 1 A or 5 A terminal and common to match the phase CT secondary. 
    Correct polarity as indicated in the wiring diagrams is essential for correct measurement of 
    all power quantities.
    The CTs selected should be capable of supplying the required current to the total 
    secondary load, including the PQMII burden of 0.1 VA at rated secondary current and the 
    connection wiring burden.
    All PQMII internal calculations are based on information measured at the CT and VT inputs. 
    The accuracy specif ied in this manual assumes no error contribution from the external CTs 
    and VTs. To ensure the greatest accuracy, Instrument class CTs and VTs are recommended. 
    						
    							2–14PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 2: INSTALLATION
    2.2.7 Output Relays
    The basic PQMII comes equipped with one output relay; the control option supplies three 
    additional output relays. The PQMII output relays have form C contacts (normally open 
    (NO), normally closed (NC), and common (COM)). The contact rating for each relay is 5 A 
    resistive and 5 A inductive at 250 V AC. Consult 1.6: Specifications for contact ratings under 
    other conditions. The wiring diagrams show the state of the relay contacts with no control 
    power applied; that is, when the relays are not energized. Relay contact wiring depends on 
    how the relay operation is programmed in the 
    S3 OUTPUT RELAYS setpoint group (see 5.4: S3 
    Output Relays for details).
    •Alarm Relay (Terminals 43/44/45): A selected alarm condition activates the alarm 
    relay. Alarms can be enabled or disabled for each feature to ensure only desired 
    conditions cause an alarm. If an alarm is required when control power is not present , 
    indicating that monitoring is not available, select “Fail-safe” operation for the alarm 
    relay through the 
    S3 OUTPUT RELAYS  ALARM RELAY  ALARM OPERATION setpoint . The NC/
    COM contacts are normally open going to a closed state on an alarm. If “Unlatched” 
    mode is selected with setpoint 
    S3 OUTPUT RELAYS  ALARM RELAY  ALARM ACTIVATION, the 
    alarm relay automatically resets when the alarm condition disappears. For “Latched” 
    mode, the key must be pressed (or serial port reset command received) to reset the 
    alarm relay. Refer to 6.3.1: Alarms for all the displayed alarm messages. 
    •Auxiliary Relays 1,2,3 (Optional; Terminals 34 to 42): Additional output relays can be 
    conf igured for most of the alarms listed in 6.3.1 Alarms. When an alarm feature is 
    assigned to an auxiliary relay, it acts as a control feature. When the setpoint is 
    exceeded for a control feature, the output relay changes state and the appropriate 
    Aux LED lights but no indication is given on the display. The auxiliary relays can also be 
    programmed to function as kWh, kvarh, and kVAh pulse outputs.
    2.2.8 Switch Inputs (Optional)
    With the control (C) option installed the PQMII has four programmable switch inputs that 
    can be used for numerous functions. The f igure below shows the internal circuitry of the 
    switches.
    FIGURE 2–10: Switch Input Circuit
    EXTERNAL
    SWITCH
    OPTO
    ISOLATION
    TYPICAL
    SWITCH
    TERMINALSISOLATED
    POWER
    SUPPLY
    +24VDC
    PQM II
    TO LOGIC
    10mA
    PULSED
    FILTERIN COM 
    						
    							CHAPTER 2: INSTALLATION
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL2–15
    Each switch input can be programmed with a 20-character user def ined name and can be 
    selected to accept a normally open or normally closed switch. A list of various functions 
    assignable to switches is shown below, followed by a description of each function.
    •Alarm Relay: When a switch input is assigned to the alarm relay, a change in the 
    switch status produces an alarm condition and the alarm relay activates.
    •Pulse Input 1/2/3/4: When a switch input is assigned as a pulse input counter, the 
    PQMII counts the number of transitions from open to closed when the input is 
    conf igured as normally open and closed to open when the input is conf igured as 
    normally closed. The minimum pulse width required for the PQMII to read the switch is 
    150 ms. Therefore, for the PQMII to read one pulse, the switch input must be in its 
    inactive state (closed/open) for a minimum of 150 ms then in its active state (open/
    closed) for another 150 ms. See 1.6: Specifications for more details.
    •New Demand Period: The PQMII can be used for load shedding by assigning a switch 
    input to a new demand period. This allows the PQMII demand period to be 
    synchronized with the utility meter. One of the billing parameters used by a utility is 
    peak demand. By synchronizing the PQMII to the utility meter, the PQMII can monitor 
    the demand level read by the utility meter and perform load shedding to prevent the 
    demand from reaching the penalty level. The utility meter provides a dry contact 
    output which can be connected to one of the PQMII switch inputs. When the PQMII 
    senses a contact closure, it starts a new demand period (with Block Interval Demand 
    calculation only).
    •Setpoint Access: The access terminals must be shorted together in order for the 
    faceplate keypad to have the ability to store new setpoints. Typically the access 
    terminals are connected to a security keyswitch to allow authorized access only. Serial 
    port commands to store new setpoints operate even if the access terminals are not 
    shorted. When the access terminals are open, all actual and setpoint values can still 
    be accessed for viewing; however, if an attempt is made to store a new setpoint value, 
    the message 
    SETPOINT ACCESS DISABLED is displayed and the previous setpoint 
    remains intact . In this way, all of the programmed setpoints remain secure and 
    tamper proof.
    •Select Analog Output: This switch selection allows each analog output to be 
    multiplexed into two outputs. If the switch is active, the parameter assigned in 
    setpoint 
    S2 SYSTEM SETUP  ANALOG OUTPUT 1  ANALOG OUTPUT 1 ALT determines the 
    output level. If the switch is not active, the parameter assigned in setpoint 
    S2 SYSTEM 
    SETUP  ANALOG OUTPUT 1  ANALOG OUTPUT 1 MAIN
     is used. See the following section 
    and 5.3.2: Analog Outputs for additional details.
    •Select Analog Input: This switch selection allows the analog input to be multiplexed 
    into two inputs. If the switch is active, the parameter assigned in setpoint 
    S2 SYSTEM 
    SETUP  ANALOG INPUT  ANALOG INPUT ALT
     is used to scale the input . If the switch is not 
    active, the parameter assigned in setpoint 
    S2 SYSTEM SETUP  ANALOG INPUT  ANALOG 
    INPUT MAIN
     is used. If a relay is assigned in S2 SYSTEM SETUP  ANALOG INPUT  ANALOG IN 
    MAIN/ALT SELECT RELAY
    , that relay energizes when the switch is active and de-energizes 
    when the switch is not active, thus providing the ability to feed in analog inputs from 
    two separate sources as shown in the figure below. See the 2.2.10: Analog Input 
    (Optional) section below for details. Refer to 5.3.3: Analog Input for additional details. 
    						
    							2–16PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 2: INSTALLATION
    FIGURE 2–11: Analog Input Multiplexing
    •Aux 1/2/3 Relay: When a switch input is assigned to an Auxiliary relay, a closure on 
    the switch input causes the programmed auxiliary relay to change state. This 
    selection is available only if the Control (C) option is installed.
    •Clear Energy: When a switch input is assigned to “Clear Energy”, a closure on the 
    switch input will clear all Energy data within the PQMII.
    •Clear Demand: When a switch input is assigned to “Clear Demand”, a closure on the 
    switch input will clear all Demand data within the PQMII.
    2.2.9 Analog Outputs (Optional)
    The PQMII has four current outputs when the transducer option is installed (T20 = 4 to 20 
    mA, T1 = 0 to 1 mA in the order code). These outputs can be multiplexed to produce 8 
    analog transducers. This output is a current source suitable for connection to a remote 
    meter, chart recorder, programmable controller, or computer load. Use the 4 to 20 mA 
    option with a programmable controller that has a 2 to 40 mA current input . If only a 
    voltage input is available, use a scaling resistor at the PLC terminals to scale the current to 
    the equivalent voltage. For example, install a 500Ω resistor across the terminals of a 0 to 
    10 V input to make the 4 to 20 mA output correspond to 2 to 10 V (R = V/I = 10 V / 0.02 A = 
    500Ω). Current levels are not affected by the total lead and load resistance which must not 
    exceed 600Ω for the 4 to 20 mA range and 2400Ω for the 0 to 1 mA range. For readings 
    greater than full scale the output will saturate at 22 mA (4 to 20 mA) or 1.1 mA (0 to 1 mA). 
    These analog outputs are isolated and since all output terminals are floating, the 
    connection of the analog output to a process input will not introduce a ground loop. Part of 
    the system should be grounded for safety, typically at the programmable controller. For 
    floating loads (such as a meter), ground Terminal 24 externally.
    The outputs for these transducers can be selected from any of the measured parameters 
    in the PQMII. The choice of output is selected in the 
    S2 SYSTEM SETUP  ANALOG OUTPUT 1(4) 
    setpoints group. See 5.3.2: Analog Outputs for a list of available parameters. Each analog 
    output can be assigned two parameters: a main parameter and an alternate parameter. 
    Under normal operating conditions, the main parameter will appear at the output 
    terminals. To select the alternate parameter, one of the switch inputs must be assigned to 
    “SELECT ANALOG OUT” and the switch input must be closed (assuming normally closed 
    activation). By opening and closing the switch input , two analog output parameters can be 
    multiplexed on one output . This effectively achieves 8 analog outputs for the PQMII. 
    						
    							CHAPTER 2: INSTALLATION
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL2–17
    FIGURE 2–12: Analog Output
    As shown in wiring diagrams, these outputs are at Terminals 25 to 28 and share Terminal 
    24 as their common. Shielded cable should be used, with only one end of the shield 
    grounded, to minimize noise effects.
    Signals and power supply circuitry are internally isolated, allowing connection to devices 
    (PLCs, computers, etc.) at ground potentials different from the PQMII. Each terminal, 
    however, is clamped to ±36 V to ground.
    2.2.10 Analog Input (Optional)
    Terminals 22(–) and 23(+) are provided for a current signal input . This current signal can be 
    used to monitor any external quantity, such as transformer winding temperature, battery 
    voltage, station service voltage, transformer tap position, etc. Any transducer output 
    ranges within the range of 0 to 20 mA can be connected to the analog input terminals of 
    the PQMII. See 5.3.3: Analog Input for details on programming the analog input .
    2.2.11 RS485 Serial Ports
    A fully loaded PQMII is equipped with three serial ports. COM1 is a RS485 port available at 
    the rear terminals of the PQMII which is normally used as the main communications 
    interface to the system. COM2, which is also a rear RS485 port , can be used for data 
    collection, printing reports, or problem analysis without disturbing the main 
    communications interface. COM3 is a front panel RS232 port that can be used for setpoint 
    programming or recording using the EnerVista PQMII Setup Software.
    A serial port provides communication capabilities between the PQMII and a remote 
    computer, PLC, or distributed control system (DCS). Up to thirty-two PQMIIs can be daisy 
    chained together with 24 AWG stranded, shielded, twisted-pair wire on a single 
    communication channel. Suitable wire should have a characteristic impedance of 120 W 
    (such as Belden #9841). These wires should be routed away from high power AC lines and 
    other sources of electrical noise. The total length of the communications wiring should not 
    exceed 4000 feet for reliable operation. Correct polarity is essential for the 
    communications port to operate. Terminal (485+) of every PQMII in a serial communication 
    link must be connected together. Similarly, the (485–) terminal of every PQMII must also be 
    connected together. These polarities are specif ied for a 0 logic and should match the 
    polarity of the master device. If the front panel RX1 or RX2 lights are flashing, this indicates 
    that the PQMII is receiving data. If the front panel TX1 or TX2 lights are flashing, this 
    823700A1.CDR
    PQMII 
    						
    							2–18PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 2: INSTALLATION
    indicates that the PQMII is transmitting data. Each PQMII must be daisy-chained to the 
    next one as shown in the f igure below. Avoid star or stub connected conf igurations. If a 
    large difference in ground potentials exists, communication on the serial communication 
    link will not be possible. Therefore, it is imperative that the serial master and PQMII are both 
    at the same ground potential. This is accomplished by joining the RS485 ground terminal 
    (Terminal 46 for COM1; Terminal 49 for COM2) of every unit together and grounding it at the 
    master only.
    The last PQMII in the chain and the master computer require a terminating resistor and 
    terminating capacitor to ensure proper electrical matching of the loads and prevent 
    communication errors. Using terminating resistors on all the PQMIIs would load down the 
    communication network while omitting them at the ends could cause reflections resulting 
    in communication errors. Install the 120Ω, ¼ watt terminating resistor and 1 nF capacitor 
    externally. Although any standard resistor and capacitor of these values are suitable, these 
    components can also be ordered from GE Multilin as a combined terminating network.
    Each communication link must have only one computer (PLC or DCS) issuing commands 
    called the master. The master should be centrally located and can be used to view actual 
    values and setpoints from each PQMII called the slave device. Other GE Multilin relays or 
    devices using the Modbus RTU protocol can be connected to the communication link. 
    Setpoints in each slave can also be changed from the master. Each PQMII in the link must 
    be programmed with a different slave address prior to running communications using the 
    S1 PQMII SETUP  COM1 RS485 SERIAL PORT  MODBUS COMMUNICATION ADDRESS setpoint . The GE 
    Multilin EnerVista PQMII Setup Software may be used to view status, actual values, and 
    setpoints. See 4.4: Using the EnerVista PQMII Setup Software for more information on the 
    EnerVista PQMII Setup Software.
    FIGURE 2–13: RS485 Communication Wiring
    PQM II
    48
    47
    6
    46
    PQM II
    GEMultilin
    IED
    SRSeries
    GEMultilin
    ProtectionRelay
    RS485.CDR 
    						
    							CHAPTER 2: INSTALLATION
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL2–19
    2.2.12 RS232 Front Panel Port
    A 9-pin RS232C serial port provided on the front panel allows the user to program the 
    PQMII with a personal computer. This port uses the same communication protocol as the 
    rear terminal RS485 ports. To use this interface, the personal computer must be running 
    the EnerVista PQMII Setup Software provided with the relay. Cabling to the RS232 port of 
    the computer is shown below for both 9-pin and 25-pin connectors.
    FIGURE 2–14: RS232 Connection
    2.2.13 Dielectric Strength Testing
    It may be required to test the complete switchgear for dielectric strength with the PQMII 
    installed. This is also known as “flash” or “hipot” testing. The PQMII is rated for 1500 V AC 
    isolation between relay contacts, CT inputs, VT inputs, control power inputs and Safety 
    Ground Terminal 6. Some precautions are necessary to prevent damage to the PQMII 
    during these tests.
    Filter networks and transient protection clamps are used between the control power, serial 
    port , switch inputs, analog outputs, analog input , and the f ilter ground terminal 5 to f ilter 
    out high voltage transients, radio frequency interference (RFI) and electromagnetic 
    interference (EMI). The f ilter capacitors and transient absorbers could be damaged by the 
    continuous high voltages relative to ground that are applied during dielectric strength 
    testing. Disconnect the Filter Ground (Terminal 5) during testing of the control power 
    inputs. Relay contact and CT terminals do not require any special precautions. Do not 
    perform dielectric strength testing on the serial ports, switch inputs, analog input or analog 
    output terminals or the PQMII internal circuitry will be damaged.
    PQMII
    PQMII
    RS232.CDR 
    						
    							2–20PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 2: INSTALLATION
    FIGURE 2–15: Hi-Pot Testing
    746702A1.CDR
    5
    PQMII
    POWER QUALITY METER
    GE Multilin 
    						
    All GE manuals Comments (0)