Home > GE > Controller > GE F650 Manual

GE F650 Manual

Here you can view all the pages of manual GE F650 Manual. The GE manuals for Controller are available online for free. You can easily download all the documents as PDF.

Page 71

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-9
Table 3-2:  Types of f iles generated by EnerVista 650 Setup software, online 
Settings & Conf iguration File *.650Logic Conf iguration Files (*.pep, *.aut , *.lib)
*.pep*.aut*.lib
Description Settings and Conf iguration Section Header for Logic 
pr

oject Graphical edition 
cont
ainer. Logic 
equations (Virtual 
Outputs) in FDB 
format . User programmable 
lo
gic objects...

Page 72

3-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.1.5  EnerVista 650 Setup menu
The EnerVista 650 Setup menu structure is shown in Table 3-3: EnerVista 650 Setup menu structure. 
Unless specified, options are available in both online and offline mode.
(*) indicates options enabled only in online mode.  (**) indicates options enabled only in offline mode.
Table 3-3: EnerVista 650 Setup menu structure
NOTICEThe View > Language...

Page 73

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-11
3.1.6  File menu
(*) indicates online only, (**) indicates offline only
File
New (**) Create a new settings and conf iguration f ile, with the default relay 
setti
ngs and no conf iguration 
Open (**) Open a settings and conf iguration f ile for offline working. 
Save (**)Save *.650 settings and conf iguration f ile 
Save As (**)Save as *.650 settings and conf iguration f ile....

Page 74

3-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.1.6.1   New, Open, Save, Save as, and Close
In these options, the EnerVista 650 Setup program opens a dialog box (with default path to Files > Config program folder) 
where the setting and configuration files  can be selected from offline files. To access this menu, there must be no 
communication between the PC program and the relay (offline mode).
Figure 3-5: Open f ile menu...

Page 75

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-13
3.1.6.2  Conf iguration f ile converter 
The configuration file converter tool provides automatic conversion of configuration files from and older firmware version 
to a newer version. In order to convert a configuration file, follow these steps:
1. Working in offline mode, go to File > Conf ig File (*.650) Converter
2. Select the f ile to be converted.
3. After source f ile...

Page 76

3-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
For example, if the Phase TOC High element is config ured in the source *.650 file as described below:
                     1. Note that fields in blue contain default values
CASE 1: If the setting groups option is disabled (Setpoint > Control Elements > Setting group) in the source file, conversion 
is performed in the destination file as follows:
• Settings of different...

Page 77

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-15
3.1.6.3  Properties
When this option is selected, the program displays the relay  model information, firmware version, etc. of the file being 
edited, as shown:
Figure 3-7: File properties menu
3.1.6.4  Print options
The printing options are active only in offline mode with a file open, and not in online mode, connected with the relay.
Print setup
Option to configure the...

Page 78

3-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
Print
Option to print the relay configuration using the PC default (activ e) printer on port COMx or LPT. This option is active only in 
offline mode and in file edition (not in online mode while connected to the relay).
Print to f ile (*xls)
Option to export the configuration file to an Excel file.
3.1.6.5  Compare to settings f ile
This tool provides an automatic comparison  of...

Page 79

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-17
3.1.6.7  Setting checksum calculation
When working in offline mode, the Settings Checksum calcul ation option calculates the CRC of different configured 
settings for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated Sett ings Checksum and the actual 
value of the Settings Checksum read from the relay (Actual values > Status > System Info) must...

Page 80

3-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.1.7.1  Product setup menu
(*) indicates online only,  (**) indicates offline only
3.1.7.2  Communication settings menu
This section details the settings related to communication  parameters for the different protocols available in the F650.
(*) indicates online only, (**) indicates offline only
Product Setup
Communication 
Settings Serial Ports, Network (Ethernet), ModBus...
Start reading GE F650 Manual
All GE manuals