Page 91

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-29
Table 3-9: Protection elements, actual values menu 
Table 3-10: Control elements, actual values 
 menu, f irmware versions below 7.50
Protection
Protection BlocksThis screen shows all the protection element blocks available. Protection elements block 
si
gnals can be conf igured at  Setpoint > Relay Conf iguration > Protection Elements .
Phase CurrentProtection status signals...

Page 92

3-30F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
Table 3-11: Control elements, actual valu es menu, f irmware version 7.50 and above
Table 3-12: Records status, actual values menu
3.1.8.3  Metering
The Metering menu includes all the measurements available in the device. Primary and secondary values, and also the 
data related to the recording functions in the relay
Control Elements
Frequency Status signals (pickups and...

Page 93

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-31
3.1.8.4  Inputs/Outputs menu
The Inputs/Outputs menu includes all the inputs and outputs signals available in the device. Contact and virtual type.
(*) indicates online only, (**) indicates offline only
3.1.8.5  Records menu
The Records menu is only available in online mode and includes  the possibility to retrieve all the records available in the 
device. By serial or...

Page 94

3-32F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.1.9  Operations menu
Option only available in online mode, showing all the operations previously configured in the relay with their 
corresponding texts, which must be different  from the default text (Op_X not configured). 
(*) indicates online only, (**) indicates offline only
3.1.10  Communications menu
The communication menu includes the computer screen to  start...

Page 95

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-33
CAUTIONCAREFULLY READ THE FLASH MEMORY UPDATE PROCEDURE DESCRIBED IN SECTION 
“BOOT CODE AND FIRMWARE AND CLOSE ALL RUNNING APPLICATIONS BEFORE 
PERFORMING FIRMWARE AND OPERATING SYSTEM UPDATES.
NOTICEFor f irmware versions below 7.00, check that the f irmware version that is going to be 
updated matches the operating system version of the relay before updating f irmware. If...

Page 96

3-34F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
An example of  Communication > Troubleshooting follows :
Figure 3-15: Communication troubleshooting example
3.1.11  Security menu
The security menu includes all the menus related to security  control in EnerVista 650 Setup. EnerVista 650 Setup security 
users and passwords are not related to passwords in HMI. Ea ch security level has its own access for HMI management 
and...

Page 97

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-35
3.1.12  View menu
The view menu includes the  computer screen to start communicating with the relay, the different update procedures 
available in device: firmware, operating system, web server and other file storing capabilities (upload and download info 
files to/from relay).
The ModBus memory map is detailed in the complete instruction manual (English only) and can be...

Page 98

3-36F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.2 HUMAN-MACHINE INTERFACE (HMI)CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.2   Human-machine interface (HMI)
The HMI interface consists of several functional panels. Th e faceplate can be unscrewed to allow easy access to the 
removable modules. There is also a removable dust cover that  fits over the display and other cover that protects the front 
RS232 Communications port and the commands buttons that can be sealed. The following figure shows the...

Page 99

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.2 HUMAN-MACHINE INTERFACE (HMI)
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-37
Figure 3-17: Enhanced HMI interface
3.2.1  Display 
F650 units are available with two different options for the front display. The first option is an alphanumerical display of 4 
lines with 20 characters each, and the second option is a graphical display of 16 lines wi th 40 characters each (128x240 
pixels).
The boot code and firmware versions can be seen in the relay text...

Page 100

3-38F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.2 HUMAN-MACHINE INTERFACE (HMI)CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.2.2  LED indicators
The relay provides 16 LED indicators, 15 user programmable pl us one non-configurable LED (READY) that shows if the relay 
is in service.
Programmable LEDs are divided into groups of 5 LEDs, each of  the groups having a different color. The first group of LED 
indicators is latched by hardware (red), usually configured for trip signals. The second group...