    							ADS XiLog+ System  User Manual 
     65 
    7.  Verify the settings and readings ret urned.  Edit the settings as 
    necessary, and c onsider the following:  
      The Flow Channel  header displays the current flow and meter 
    readings.  These updates every 10 seconds.  If the flow rate does not 
    match the meter reading, edit the FCAL  value as necessary and 
    click on the red arrow 
     to send the new value to the logger.  Edit 
    the Meter Reading  as necessary and click on the corresponding red 
    arrow 
     t o send the new value to the logger. 
      The Pressure Channel  header displays the current pressure 
    reading.  This reading updates every second.  To set the pressure 
    reading to zero (when necessary), click on the Auto Zero  button.  
    8.  Click on the Finish  button, and disconnect from the logger. 
    Testing the Signal Strength 
    Performing the signal strength test using XiLog+ FastTrack  requires pre-
    planning so that adequate time will be available  for initiating the test, 
    disconnecting from the logger, and placing the logger at the location of 
    deployment before the formal test begins.  The test provides a 30- second 
    window, or dela y, following test initiation through  FastTrack to allow for 
    these activities to occur without disrupting the actual signal test.  Run the test 
    in the following way:  
    1.  Make sure the proper SIM card has been installed  in the logger. 
    2.  Locate the logger near the proposed site at  which it will be deployed. 
    3.  Click on the Signal Strength button. 
    4.  Disconnect the logger from the  computer. 
    5.  Place the logger in the deployment location, and verify that all 
    enclosures, lids, and doors are in positions (e.g., open or closed) t hat 
    accurately reflect  the deployment conditions. 
    The signal strength test takes one minute to complete, following the 30- second 
    delay for preparation. 
    6. Once the test is complete, recover the logger and reconnect it to the 
    computer.  
    7.  Evaluate the results in  XiLog+ FastTrack.  Refer to Performing a 
    Signal Strength Test  on page 16 for information on properly 
    interpreting the test results.   
    						
    							ADS XiLog+ System User Manual 
     66 
    Appendix  B:  Meter Scaling Tables 
    Elster/Kent Helix & Domes tic Meters 
    Meter PU10/LRP 
     (mm) FCAL 
    Helix 2000 40-80 10 
    100-300 100 
    Helix 3000 40-80 10 
    100 10 
    150 100 
    Master 2000 40-50 1 
    80-100 10 
     PG100 
    Helix 4000 80-125 10/1000 
    150-300 100/10000 
     PSM 
    PSM-PS15-PS20 (V100) 15/20 0.5 
    PSM-PS25-PS30 (V100) 25-30 5 
    PSM-PS40 (V100) 40 5 
    PSM-LT (V100) 15 & 20 0.5 
     MSM 
    MSM-T (V210)  1 
    KVM-T (V200)  1 
    MSM-RS  10 
    Schlumberger/Actaris/Stream Domestic & Helix Meters  
    Meter CYBLE LF 
     (mm) K=2.5 K=10 K=25 
    Aquadis (4X4) 15 0.25 1 2.5 
    Aquadis 15-40 2.5 10 25 
    P40M (4x4) 15 0.25 1 2.5 
    P40M 15 2.5 10 25  
    						
    							ADS XiLog+ System  User Manual 
     67 
    Meter CYBLE LF 
     (mm) K=2.5 K=10 K=25 
    FlostarM 40-100 25 100 250 
    W oltex  50-100 25 100 250 
    150-300 250 1000 2500 
    400-500 2500 10000 25000 
    Sensus (Socam/Meinecke)  
    Meter K510 K505R 
     (mm) FCAL 
    510/510PR 15-20 1 0.5 
    501L 10 
    501LM 100 
    501JM 1000 
    510/510PR 25-30 10 5 
    501JM 100 
     R01.1 
    Cosmosil  50-125 100/1000 
    150-250 1000/10000 
    300-800 10000/100000 
     RD 01 
    Cosmos 50-125 100 
    WP/WS-Dyn amic   40-125 100/1000 
    10/1000 
    150- 300 1000/10000 
    100/10000 
    Supplementary Notes for Me ter Scaling Tables 
    FCAL = NUMBER OF LITERS PER PULSE  
      Kent Meters:  
    * Some earlier 100 -mm meters require the following: 
    FCAL = 100(PU10/LRP) or 10(PU100/HRP).  Distinguish t hese meters by the 
    center  pointer dial registration = 1000 lit ers/rev.   
    						
    							ADS XiLog+ System User Manual 
     68 
    ** Applies onl y to 7- digit counters ; the other FCALs apply to the 8- digit 
    counters. 
    Kent combination meters use a Helix 3000 meter as the main meter and a 
    PSM -T as the secondary meter.   Select the appropriate FCAL from the table 
    above for each  meter.  
    The Master 2000 has  been discontinued. 
      Socam meters:  
    *The 510 pulse unit is factory installed  and cannot be removed.  The FCAL is 
    determined at the factory , and the table above displays the values available.  
    Check t he individual meter before selecting the appropriate FCAL.   
    						
    							ADS XiLog+ System  User Manual 
     69 
    Appendix  C:  Battery Life  
     
    Measurement 
    Interval 
    Transmission  Standard 
    Internal 
    Battery 
    Double 
    Internal 
    Battery 
    External 
    Lithium 
    Battery 
    ≥1 minute  Once per day >5 years  >10 years   
    ≥1 minute  Once per hour >1.2 years  >2.5 years  >7 years  
    ≥1 minute  Once every 15 
    minutes ( for 10 
    hours  a  day)   >0.7 year
     >1.5 years  >5 years  
    ≥1 minute  Once every 15 
    minutes  0.3 year
      0.7 year  2.5 years  
    Power Supply Options  
    Following are the internal power options available for the XiLog+:  
     Standard pack  
     Double battery pack  
    Followin g are the external  power options available for the XiLog+ ( all 
    loggers ): 
      External b attery pack  
     Mains  
     Solar   
    						
    							ADS XiLog+ System User Manual 
     70 
    Appendix  D:  Airfreight Restrictions  
     APP3.1:  Essential Safety Precautions before Air F reighting 
    To pr event radio transmission on aircraft, remove the  batteries and the 
    removable external antenna  (when applicable) from the equipment before 
    transporting this product by air.  
      IATA Hazardous Goods Regulation 
    This product is powere d by a battery containing lithium D -cells.   IATA 
    (International Air Transport Association) regulation UN/ID number 3091, 
    “ Lithium batteries contained in equipment,” governs a ir-freighting of products 
    containing these lithium cells .  This regulation clearly states that th is 
    equipment  is classified as Hazardous Goods , Class 9.  This equipment  can be 
    transported by air only if it is  packed specifically as defined in instruction 
    UN/ID number 3091.  This instruction defines the necessary packing 
    requirements ( Packing Instruction 912) and labeling requirements 
    ( Miscellaneous ). 
      Transporting  XiLog+ Dataloggers to ADS by Air  
    To transport this product by air, first remove all batteries .  Removing the 
    batteries from the XiLog+ allows the logger to  be transported without being 
    declared  hazardous .   
    Dispose of any batteries removed according to  local waste regulations.   ADS 
    will install new batteries in the product at the factory.      
    T o airfreight these products or obtain further information concerning  air-
    freight ing regulations , please contact ADS in the following way : 
    ADS Client Services  
    (877) 237- 9585 
    [email protected]  
    						