ADS XiLog+ System User Manual 65 7. Verify the settings and readings ret urned. Edit the settings as necessary, and c onsider the following: The Flow Channel header displays the current flow and meter readings. These updates every 10 seconds. If the flow rate does not match the meter reading, edit the FCAL value as necessary and click on the red arrow to send the new value to the logger. Edit the Meter Reading as necessary and click on the corresponding red arrow t o send the new value to the logger. The Pressure Channel header displays the current pressure reading. This reading updates every second. To set the pressure reading to zero (when necessary), click on the Auto Zero button. 8. Click on the Finish button, and disconnect from the logger. Testing the Signal Strength Performing the signal strength test using XiLog+ FastTrack requires pre- planning so that adequate time will be available for initiating the test, disconnecting from the logger, and placing the logger at the location of deployment before the formal test begins. The test provides a 30- second window, or dela y, following test initiation through FastTrack to allow for these activities to occur without disrupting the actual signal test. Run the test in the following way: 1. Make sure the proper SIM card has been installed in the logger. 2. Locate the logger near the proposed site at which it will be deployed. 3. Click on the Signal Strength button. 4. Disconnect the logger from the computer. 5. Place the logger in the deployment location, and verify that all enclosures, lids, and doors are in positions (e.g., open or closed) t hat accurately reflect the deployment conditions. The signal strength test takes one minute to complete, following the 30- second delay for preparation. 6. Once the test is complete, recover the logger and reconnect it to the computer. 7. Evaluate the results in XiLog+ FastTrack. Refer to Performing a Signal Strength Test on page 16 for information on properly interpreting the test results.
ADS XiLog+ System User Manual 66 Appendix B: Meter Scaling Tables Elster/Kent Helix & Domes tic Meters Meter PU10/LRP (mm) FCAL Helix 2000 40-80 10 100-300 100 Helix 3000 40-80 10 100 10 150 100 Master 2000 40-50 1 80-100 10 PG100 Helix 4000 80-125 10/1000 150-300 100/10000 PSM PSM-PS15-PS20 (V100) 15/20 0.5 PSM-PS25-PS30 (V100) 25-30 5 PSM-PS40 (V100) 40 5 PSM-LT (V100) 15 & 20 0.5 MSM MSM-T (V210) 1 KVM-T (V200) 1 MSM-RS 10 Schlumberger/Actaris/Stream Domestic & Helix Meters Meter CYBLE LF (mm) K=2.5 K=10 K=25 Aquadis (4X4) 15 0.25 1 2.5 Aquadis 15-40 2.5 10 25 P40M (4x4) 15 0.25 1 2.5 P40M 15 2.5 10 25
ADS XiLog+ System User Manual 67 Meter CYBLE LF (mm) K=2.5 K=10 K=25 FlostarM 40-100 25 100 250 W oltex 50-100 25 100 250 150-300 250 1000 2500 400-500 2500 10000 25000 Sensus (Socam/Meinecke) Meter K510 K505R (mm) FCAL 510/510PR 15-20 1 0.5 501L 10 501LM 100 501JM 1000 510/510PR 25-30 10 5 501JM 100 R01.1 Cosmosil 50-125 100/1000 150-250 1000/10000 300-800 10000/100000 RD 01 Cosmos 50-125 100 WP/WS-Dyn amic 40-125 100/1000 10/1000 150- 300 1000/10000 100/10000 Supplementary Notes for Me ter Scaling Tables FCAL = NUMBER OF LITERS PER PULSE Kent Meters: * Some earlier 100 -mm meters require the following: FCAL = 100(PU10/LRP) or 10(PU100/HRP). Distinguish t hese meters by the center pointer dial registration = 1000 lit ers/rev.
ADS XiLog+ System User Manual 68 ** Applies onl y to 7- digit counters ; the other FCALs apply to the 8- digit counters. Kent combination meters use a Helix 3000 meter as the main meter and a PSM -T as the secondary meter. Select the appropriate FCAL from the table above for each meter. The Master 2000 has been discontinued. Socam meters: *The 510 pulse unit is factory installed and cannot be removed. The FCAL is determined at the factory , and the table above displays the values available. Check t he individual meter before selecting the appropriate FCAL.
ADS XiLog+ System User Manual 69 Appendix C: Battery Life Measurement Interval Transmission Standard Internal Battery Double Internal Battery External Lithium Battery ≥1 minute Once per day >5 years >10 years ≥1 minute Once per hour >1.2 years >2.5 years >7 years ≥1 minute Once every 15 minutes ( for 10 hours a day) >0.7 year >1.5 years >5 years ≥1 minute Once every 15 minutes 0.3 year 0.7 year 2.5 years Power Supply Options Following are the internal power options available for the XiLog+: Standard pack Double battery pack Followin g are the external power options available for the XiLog+ ( all loggers ): External b attery pack Mains Solar
ADS XiLog+ System User Manual 70 Appendix D: Airfreight Restrictions APP3.1: Essential Safety Precautions before Air F reighting To pr event radio transmission on aircraft, remove the batteries and the removable external antenna (when applicable) from the equipment before transporting this product by air. IATA Hazardous Goods Regulation This product is powere d by a battery containing lithium D -cells. IATA (International Air Transport Association) regulation UN/ID number 3091, “ Lithium batteries contained in equipment,” governs a ir-freighting of products containing these lithium cells . This regulation clearly states that th is equipment is classified as Hazardous Goods , Class 9. This equipment can be transported by air only if it is packed specifically as defined in instruction UN/ID number 3091. This instruction defines the necessary packing requirements ( Packing Instruction 912) and labeling requirements ( Miscellaneous ). Transporting XiLog+ Dataloggers to ADS by Air To transport this product by air, first remove all batteries . Removing the batteries from the XiLog+ allows the logger to be transported without being declared hazardous . Dispose of any batteries removed according to local waste regulations. ADS will install new batteries in the product at the factory. T o airfreight these products or obtain further information concerning air- freight ing regulations , please contact ADS in the following way : ADS Client Services (877) 237- 9585 [email protected]