    							ADS XiLog+ System  User Manual 
     5 
     Appl ications  
     Flow monitor ing  
      leakage control (water loss reduction)  
      demand management  
      domestic  and industrial use  
      Hy draulic network modeling  
      Pressure mo nitoring 
      PRV (pressure reducing valve)  performance monitoring 
      Reservoir and bore -hole depth measuremen t 
       River level  measurement  
      Depth -to -flow conversion 
       Rainfall  measurement  
      Overflow detection   
    						
    							ADS XiLog+ System User Manual  
        6 
     PrimeWorks  Software 
    Use the PrimeWorks® software to configure the XiLog+ and manage the data 
    collected from the unit.  The management capabi lities include reporting and 
    grap hing func tions. 
    Note:  Do not run other applications on the  PC or laptop computer 
    during the PrimeWorks software installation process . 
    Software Requirements  
    ADS requires the following software  for proper operation of the PrimeWorks  
    software:  
     Mi crosoft® Windows® XP or later  
     Microsoft .NET Framework  version 3.5, Service Pack 1 
    As with any software application, software performance increases with 
    stronger host system specifications.  
    Note:  ADS does not provide technical support concerning issues 
    relating to, or caused by problems with, the operating system installed 
    on the user’s  PC. 
    User  Access  Requirements  
    The  user installing the PrimeWorks  software must have the appropriate 
    administrative privileges to write to the system’s Registry .  
    						
    							ADS XiLog+ System  User Manual 
     7 
    SIM Card  
    To perform wireless communication via GSM, the XiLog+ m ust be equipped 
    with a SIM card similar to the card  used in a cellular phone .  SIM cards are 
    available through a local service provider.  However, please contact ADS 
    before ordering a SIM card .  Technologies and business practices vary among 
    provider s; therefore, some provider’s services may not  be compatible with the 
    XiLog+ s ystem.   
    In addition, t he service provider must know the options to enable on the card 
    and the amount of data transfer that will occ ur over a particular time period to 
    ensure the card is set up correctly and the plan is administered properly.  The 
    selected data connection type ( SMS or GPRS) for the logger determines the 
    options that must be enabled on the S IM card. 
    Warning:   Do not disassemble or perform any maintenance or service 
    procedures on the Xi Log+ data logger beyond the scope of what is 
    described in this manual, except under the direct supervision of 
    qualified ADS personnel.  Conducting unauthorized procedures will 
    invalidate the warranty immediate ly. 
    Installing  or  Removing  the SIM Card  from the XiLog+  
    The SIM card must be placed in the  SIM holder located inside the XiLog+.  
    Therefore, to install, remove, or replace the SIM card, the holder must first be 
    removed from the logger.  This section provides instructions on the following:  
    •  Removing the SIM holder from the logger  
    •  (applies only to replacement )  Removing the SIM card from the SIM 
    holder  
    •  Inserting the SIM card in to the SIM holder  
    •  Installing the SIM holder in the logger   
    						
    							ADS XiLog+ System User Manual  
        8 
     R emov ing  the SIM H older from the XiLog+  
    1.  Loosen the 4 screws securing the cover plate in position. 
     
    2. Remove the cover plate.  
     
    3. Push on the SIM  release button.  This should cause the SIM holder to 
    protrude slightly from the slot . 
    4.  Remove the SIM holder from the log ger.  
    						
    							ADS XiLog+ System  User Manual 
     9 
      Removing the SIM Card from the SIM Holder ( applies only to replacement) 
    1.  Without touching the contacts on the SIM card, gently push an object 
    through the hole in the SIM holder. 
    2.  Remove the SIM card.  
      Insert ing a SIM Card into the SIM Holder  
    Without touc hing the SIM card contacts, insert the SIM card into the SIM 
    holder, aligning the beveled edge of the card with the keyed corner of the SIM 
    holder and facing the gold contacts on the card outward. 
     
      Installing the SIM Holder into the Logger  
    1.  Careful ly slide the SIM holder into slot in the logger housing until it 
    clicks into place.  
    2.  Verify that the seal is in the sealing groove and undamaged. 
    3.  Replace the cover plate onto the logger, and secure the plate to the 
    logger with the four screws. 
    Keyed Corner  
    SIM Holder  
    SIM Card  
    SIM Card  Contacts   
    						
    							ADS XiLog+ System User Manual  
        10 
     Technical Support  
    ADS provides comprehensive technical support to assist customers in the 
    configuration and operation of the XiLog+.   Please contact ADS Client 
    Services by email at 
    [email protected] or by phone at (877) 
    237- 9585 for assistance, when necessary.  
    						
    							ADS XiLog+ System  User Manual 
     11 
    ADS No -Hassle Warranty and Return Policy  
    The following sections detail the hassle-free warranty and return policy for the 
    ADS XiLog+ . 
    New Product Warranty  
    ADS will repair or replace any XiLog+  equipment (supplied by ADS) that is 
    defective in materials and/or workmanship for up to two (2) years following 
    the date of shipment from ADS.  To make a warranty claim, the customer 
    should simply call ADS at (256) 430- 3366 or contact ADS Client Services 
    toll- free at (877) 237- 9585.  The Client Services Representative  will assign a 
    Return Materials Authorization (RMA) to the customer’s claim immediately.  
    The customer shall return a defective unit or part to ADS for troubleshooting 
    and repair or replacement withi n 10 days with the RMA.   
    Replacement or Loaner Equipment  
    For a defective part, ADS will ship a replacement part immediately once the 
    customer makes an initial claim.  However, if ADS does not receive the 
    defective part within 30 days or testing concludes that the part experienced 
    excessive wear and tear or abuse for the period of use, ADS will bill the 
    customer for the replacement part.  
    For a defective unit , at the customer’s request,  ADS will ship a temporary 
    (loaner) unit to the customer at the time of the initial claim.  However, if ADS 
    does not receive the temporary unit from the customer within 15 days of 
    receiving the repaired or replacement unit or  testing concludes that the unit 
    experienced excessive wear and tear or abuse for the period of use, ADS  will 
    bill the customer for the temporary unit.  
    Shipping 
    The customer must pay to ship defective equipment to ADS for repair or 
    replacement.  However, ADS will incur the costs for shipping the repaired or 
    replacement equipment back to the customer using the same priority shipment 
    procured by the customer upon returning the defective equipment to ADS.  
    						
    							ADS XiLog+ System User Manual  
        12 
    Product Returns 
    If the customer is not satisfied with the performance of the XiLog+ system , the 
    customer may return the equipment within 30 days for a full ref und, provided 
    the condition of the equipment is in the same condition as sold, except for 
    expected or normal wear and tear for the period of use. 
      
    						
    							ADS XiLog+ System  User Manual 
     13 
    C H A P T E R  2  
    Deploying  the XiLog+  
     
    Deploying an ADS XiLog+ logger typical ly involves the involves the 
    following steps:  
    1.  Program ming the XiLog+  
    2.  Perform ing a Signal Strength Test  
    3.  Installing the XiLog+ at the Location  
    Deploy XiLog+ data loggers in a similar manner to other  comparable units. 
    However, consider the following factors concerning GSM capabilities and 
    requirements during deployment:  
    •  Mount  the logger in an upright position, not at an angle or on its side . 
    •  When i nstalling the logger underground, mount the logger as close as 
    possible to ground level, preferably within 6 inches of the surface. 
    Following these guidelines will help ensure the GSM functions most 
    effectively.   This chapter provide s detailed instructions for each  step in the  
    deployment  process.  
    						
    							ADS XiLog+ System User Manual  
        14 
    Programming the XiLog+  
    Configure the XiLog+ using the PrimeWorks  software.  Refer to 
    Programming the Logger Using PrimeWorks  on page 21 for more information 
    and instructions . 
    Note:  The logger also may be programmed using the XiLog+ 
    FastTrack  software.  Refer to  Appendix A:  XiLog+ FastTrack  
    Software on page 62 for brief instructions on programming a logger 
    using this simple application.  
    Configuring the GPRS Network Settings ( when applicable) 
    Loggers communicating over the GSM network via GPRS must be configured 
    with the appropriate network settings before  undergoing the more 
    comprehensive programming that occurs through PrimeWorks .  Configure 
    the GPRS settings  for a logger(s) using the GPRS Setup Utility  in the 
    following way:  
    1.  Connect the logger (s) to the computer via USB  using the 
    communication cable (ADS part number NXG -881- 001) . 
    2.  Select Start > All Program s >Primayer > GPRS Setup Utility > 
    GPRS Setup Utility.exe  from the Microsoft
    ® Windows® Start menu, 
    or click on the GPRS Set up Utility.exe icon on the Windows desktop.  
    The GPRS Setup Utility  dialog displays the loggers currently 
    connected to the computer . 
     
    GPRS Setup Utility 
    3. Select the first logger to configure from the Connected Loggers  box.  
    						
    All ADS manuals Comments (0)