Panasonic Cs Xc12ckq Cs Xc9ckq Repair Manual
Here you can view all the pages of manual Panasonic Cs Xc12ckq Cs Xc9ckq Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 21
Air Circulation Mode Operation Time Diagram Standard for Determining Operation Mode 8.4. Air Circulation Mode Operation • • • • Fan Operation only. Indoor fan speed selection by remote control and setting refer to Indoor Fan speed control. 8.5. Automatic Mode Operation • • • • Indoor fan operates at SLo fan speed for 20 seconds. • • • • After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined. • • • • After...
Page 22
Vertical Airflow Direction Auto-Control • • • • W hen set a Airflow Direction Auto-Control with remote control, the louver swings up and down as shown in the diagram. • • • • The louver does not swing when the Indoor Fan Motor stops during operation at the upper limit. • • • • W hen stopped with remote control, the discharge vent is reset, and stopped at the closing position. Vertical Airflow Direction manual Control • • • • W hen the manua l Airflow Direction...
Page 23
8.10. Ionizer Operation Purpose To provide fresh air effect to users by discharging minus Ion to air. Control Condition a. Ionizer Only Operation. 1. When airconditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed. Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1→ 2) However, fan speed can be adjusted later by customer during this operation. Airflow direction (Horizontal Vane) control: Follow vane direction control at cooling mode....
Page 24
b. Timer OFF activates. c. ION operation button is pressed again. d. ION feedback signal shows error. 3. Ionizer operation status is not memorised by Micon. After OFF, when operation is “ON” again, air conditioner operates without ionizer operation. However, during Cool mode etc + ionizer operation, if there is a power failure & then power resume, air conditioner shall on at that mode + ionizer operation. c. Timer during ionizer operation Refer to case study in next page for detail. 8.10.1. Ionizer...
Page 25
Note: 1. 24 times checking: Actual Ion ON for 10s & OFF for 1s 30 min continuously for 24 times. 2. 24 times count will be cleared when following conditions happen. a) 24 times count over, b) Ionizer cancel if press Ion button or power reset, c) Ion f/b sgnl OK. 3. Error protection will be cleared when following conditions happen. a) Power reset, b) Remote Control operation ON/OFF button press, c) Auto operation switch press, d) Operation OFF due to Timer OFF 4. Ion auto restart: Ion will auto...
Page 27
8.11. Oxygen Operation Mode 8.11.1. Purpose To supply oxygen enrich air to indoor room for healthi er andcomfortable environment and for wider operation scope. 8.11.2. Oxygen Enrich Control A. Indoor fan control 1. Manua l Fan Speed During Oxygen only operation, Manua l Fan Speed can be set byremote control. 2. Auto Fan Speed Fan Speed control is as shown below. However, if it is a combined operation with other mode, priority is given to fan control of other mode. Priority: Cool - Dry - Fan > Ionizer >...
Page 28
D. When used togetherwith On/Off timer E. Oxygen monitor indication During oxygen enrich operation, oxygen monitor LED lights on. 28 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Page 29
8.11.3. Oxygen Enrich System A. Oxygen enrich tube connection B. Oxygen Enrich control overview Whenoxygen button atremote control is On, LED at air conditioner unit lights on & vacuum pump & outdoor fan operates. *Note: Outdoor fan must run when vacuum pump operates. 29 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Page 30
C. Oxygen operation time diagram 1. Oxygen +compressor running mode (Cool, Dry) T1 = 30 min, T2 = 3 min, T3 = 7 min 2. Oxygen only or Oxygen + Compressor stop mode (Ion, Fan) T1 = 60 min, T2 = 2 min, T3 = 8 min 3. Oxygen demon stration mode * Pump & outdoo r fan “ON” continuously. * Fan speed & airflow direction control vane angle follow previous setting. * Indoor fan speed can be set by pressing fan speed selection button on remote control. D. Oxygen Enrich Protection Control 1. Vacuum pump restart...