Air Circulation Mode Operation Time Diagram Standard for Determining Operation Mode 8.4. Air Circulation Mode Operation • • • • Fan Operation only. Indoor fan speed selection by remote control and setting refer to Indoor Fan speed control. 8.5. Automatic Mode Operation • • • • Indoor fan operates at SLo fan speed for 20 seconds. • • • • After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined. • • • • After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation include s Coolin g mode operation. • • • • Room temperature adjustment. The following are added to the setting temperature specified as above. • • • • The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor electronic controller. 8.6. Random Auto Restart Control • • • • If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the power is resumed. It will start with previous operation mode and airflow direction. • • • • Restart time is decide d randomly using 4 parameter:- Intake air temperature, setting temperature, fan speed and Air Swing Blade position. • • • • Auto Restart Control is not available when Timer is set. • • • • This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram) 21 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Vertical Airflow Direction Auto-Control • • • • W hen set a Airflow Direction Auto-Control with remote control, the louver swings up and down as shown in the diagram. • • • • The louver does not swing when the Indoor Fan Motor stops during operation at the upper limit. • • • • W hen stopped with remote control, the discharge vent is reset, and stopped at the closing position. Vertical Airflow Direction manual Control • • • • W hen the manua l Airflow Direction Selection Button is pressed, the automatic airflow is released and the airflow direction louver move up and down in the range shown in the diagram. The louver can be adjusted by pressing the button to the desired louver position. • • • • W hen the remote control is used to stop the operation, the discharge vent is reset, and stopped at the closing position. 8.7. Vertical Airflow Direction Control 1.There is no swinging while indoor fan motor is stopped during Cooling, Ion,Oxygen and Soft Dry operation. 8.8. Delay ON Timer Control • • • • W hen the Delaye d ON Timer is set by using theremote control, the unit will start operate slightly before the set time, so that the room will reach nearly to the set temperature by the desiredtime. • • • • For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time. • • • • For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the intake air temperature to determine the operation mode. The operation indication lamp will blink at this time. 8.9. Remote Control Signal Receiving Sound • • • • Long beep sound will be heard when:- − − − − Stopping the Air Conditioner using ON/OFF switch. − − − − Stopping the Quiet Mode. − − − − Stopping the Oxygen Mode. − − − − Stopping the Ion Mode. • • • • Short beep sound will be heard for others. • • • • To switch off the beep sound:- Press the “Automatic Operation Button” continuously for 10s or < 15s (“beep” “beep” will be heard at the 10th second). Repea t the above if you want to switch ON the beep sound. However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated. If you do not require this operation, you may change it by using the remote control. 22 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
8.10. Ionizer Operation Purpose To provide fresh air effect to users by discharging minus Ion to air. Control Condition a. Ionizer Only Operation. 1. When airconditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed. Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1→ 2) However, fan speed can be adjusted later by customer during this operation. Airflow direction (Horizontal Vane) control: Follow vane direction control at cooling mode. Horizontal vane can be changed by customer during ion only operation. 2. Ion only operation can be off by pressed ION button again. (2→ 1) 3. It can be changed to previous operated mode (Auto, Cool, Dry, Fan) + ion operation by OFF/ON switch. (2→ 4) 4. During ion only operation, if power failure occur, after power resume, ionizer & air conditioner resumes immediately. 5. After error = 24 times, (about 11h 30 min.), ion & fan off with Ion LED blinks continuously. (Detail refer to Ionizer Error detection control.) b. Operation Mode + Ionizer Operation. 1. Ionising Operation Start Condition When airconditioner unit is in “ON” condition (Cool, Dry, Fan, Auto mode) and ION operation button at remote control is pressed. Ionizer on & ION LED illuminates. (3→ 4) Power LED also illuminates. 2. Ionising Operation Stop Condition When one of thefollowing condition is satisfied, ION operation stops. a. Stopped by ON/OFF switch. 23 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
b. Timer OFF activates. c. ION operation button is pressed again. d. ION feedback signal shows error. 3. Ionizer operation status is not memorised by Micon. After OFF, when operation is “ON” again, air conditioner operates without ionizer operation. However, during Cool mode etc + ionizer operation, if there is a power failure & then power resume, air conditioner shall on at that mode + ionizer operation. c. Timer during ionizer operation Refer to case study in next page for detail. 8.10.1. Ionizer Error Detection Control A. Purpose To inform user that error occurs at ionizer system so that repairing job can be carried out. B. Two type oferror detection control: (a) When Ionizer is ON(example case: Ionizer shorted, ionizer over current protection) • • • • During ionizer ON operation, when feed back voltage = Lo (micon input) is detected, Ion is OFF. If feedback = Lo for 11 hrs 30 min, ION LED blinks continuously. • • • • To cancel ion LED blinking, press ion button at remocon (or Auto operation switch at air conditioner unit). If ion button is pressed again, ion LED blinks again. • • • • The error can be reset by: i) Operation ON/OFF button press to operation OFF. ii) Auto Operation switch press to operation OFF. iii) Operation OFF due to Timer OFF reach. iv) Timer set ON & operation from ON to OFF(only applica ble to 12 hrstimer models). (b) When Ionizer is OFF(example case: ionizer connecting wire loose) • • • • During air conditioner is at standby or ON operation and ionizer at OFF condition, if ionizer feed back voltage = Hi (micon input) is detected, Ionizer breakdown detection control is activated and ion LED immediately blinks. • • • • To cancel Ion LED blinking, press ion button at remote control (or Auto operation switch at air conditioner unit). If ion button is pressed again, ion LED blinks again. • • • • During ionizer at breakdown condition, if ionizer feedba ck voltage = Lo (become OK), ion LED will stop blinking. 8.10.2. Ionizer Operation case study 24 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Note: 1. 24 times checking: Actual Ion ON for 10s & OFF for 1s 30 min continuously for 24 times. 2. 24 times count will be cleared when following conditions happen. a) 24 times count over, b) Ionizer cancel if press Ion button or power reset, c) Ion f/b sgnl OK. 3. Error protection will be cleared when following conditions happen. a) Power reset, b) Remote Control operation ON/OFF button press, c) Auto operation switch press, d) Operation OFF due to Timer OFF 4. Ion auto restart: Ion will auto restart if Actual Ion was ON with no error protection control before power shutdown. Otherwise Ion will not auto restart. 5. Ion LED blinking can ON/OFF during error protection by following conditions: a) Press remote control ion button b) Press Auto Operation Switch to OFF blinking. 25 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
8.11. Oxygen Operation Mode 8.11.1. Purpose To supply oxygen enrich air to indoor room for healthi er andcomfortable environment and for wider operation scope. 8.11.2. Oxygen Enrich Control A. Indoor fan control 1. Manua l Fan Speed During Oxygen only operation, Manua l Fan Speed can be set byremote control. 2. Auto Fan Speed Fan Speed control is as shown below. However, if it is a combined operation with other mode, priority is given to fan control of other mode. Priority: Cool - Dry - Fan > Ionizer > Oxygen Fan Speed: Auto between Hlo ~ Clo B. Indoor airflow direction control 1. Airflow direction manua l, auto→ same as cooling operation However when combined-operation with other mode, priority is given to airflow direction control of other mode. Priority: Cool - Dry - Fan > Ionizer > Oxygen C. Start & Cancel condition of Oxygen Enrich Operation 1. By ON/OFF switch a. If Ionizer is not set and Oxygen button is pressed → Start operation of Oxygen Enrich Operation b. If Ionizer is set and Oxygen button is pressed → Start operation of Ionizer operation + Oxygen Enrich Operation c. During Oxygen Enrich Operation, if Oxygen button is pressed → Operation stop d. During Oxygen only operation, ifOn/Off button is pressd → Air conditioner operation (mode shown in remote control) +Oxygen operation In additio n, if Ionizer button is pressed → Air conditioner operation + Oxygen Enrich + Ionizer e. During Cool, Dry, Ionizer operation, If Oxygen button is pressed → Cool, Dry, Ionizer + Oxygen Enrich operation f. Oxygen only operation stop condition i Oxygen button is pressed again ii Off timer operates iii Air conditioner Off/On button is pressed 27 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
D. When used togetherwith On/Off timer E. Oxygen monitor indication During oxygen enrich operation, oxygen monitor LED lights on. 28 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
8.11.3. Oxygen Enrich System A. Oxygen enrich tube connection B. Oxygen Enrich control overview Whenoxygen button atremote control is On, LED at air conditioner unit lights on & vacuum pump & outdoor fan operates. *Note: Outdoor fan must run when vacuum pump operates. 29 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
C. Oxygen operation time diagram 1. Oxygen +compressor running mode (Cool, Dry) T1 = 30 min, T2 = 3 min, T3 = 7 min 2. Oxygen only or Oxygen + Compressor stop mode (Ion, Fan) T1 = 60 min, T2 = 2 min, T3 = 8 min 3. Oxygen demon stration mode * Pump & outdoo r fan “ON” continuously. * Fan speed & airflow direction control vane angle follow previous setting. * Indoor fan speed can be set by pressing fan speed selection button on remote control. D. Oxygen Enrich Protection Control 1. Vacuum pump restart protection control Purpose: To prevent starting noise if vacuum pump is started too often within short period. 30 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ