Panasonic Cs Xc12ckq Cs Xc9ckq Repair Manual
Have a look at the manual Panasonic Cs Xc12ckq Cs Xc9ckq Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
5 Refrigeration Cycle Diagram 12 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
6 Block Diagram 13 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
REMARKS B: BLUEP: PINK BR: BROWNR: RED BL: BLACKW: WHITE G: GREENY: YELLOW GRY: GRAYY/G: YELLOW/G REEN O: ORANGE Resistance of Indoor Fan Motor Windings MODELCS-XC9CK CS-XC12CK CONNECTIONCWA921181 BLUE-YELLOW390Ω YELLOW-RED390Ω Note: Resistance at 20°C/25°C of ambient temperature. Resistance of Outdoor Fan Motor Windings MODELCU-XC9CK CU-XC12CK CONNECTIONCWA951128 BLUE-YELLOW210.7Ω YELLOW- RED196.5Ω Note: Resistance at 20°C of ambient temperature. Resistance of Compressor Windings MODELCU-XC9CKCU-XC12CK CONNECTION2R13C236BSC2P19S236A1L C-R3.298Ω2.237Ω C-S5.500Ω2.710Ω Note: Resistance at 20°C/25°C of ambient temperature. 7 Wiring Diagram 14 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
8 Operation Details 8.1. Indoor Fan Speed Control • • • • Auto Fan Speed Control When set toAuto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. • • • • Manual Fan Speed Control Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote control. 15 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Coolin g in operation according to Remote Control setting. Time DelaySafety Control (3 minutes) 7 minutes TimeSave Control Starting Current Control Anti-Freezing Control • • • • If the temperature of the indoor heat exchan ger falls continuously below 2°C for 4 minutes or more, the compressor turns off to protect the indoor heat exchan ger from freezing. The fan speed setting remains the same. • • • • Compressor will restart again when the indoor heat exchan ger temperature rises to 10°C (Recovery). 3 minutes waiting of Time Delay Safety Control is valid for Cooling Operation. Compressor Reverse Rotation Protection Control 8.2. Cooling Mode Operation • • • • W hen the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON. • • • • W hen the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes. • • • • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor ON temperature and OFF temperature. • • • • W hen the compressor outdoor fan motor and indoor fan motor are simultaneousl y started, the indoor fan motor will operate 1.6 second later. • • • • If the compressor is operating continuously for 5 minutes or longer and thetemperature difference between intake air and indoor heat exchan ger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically . (Time Delay Safety Control is valid) ! T = Intake air temperature - Indoor heat exchanger temperature This is to protect reverse rotation of the compressor when there is a instantaneous power failure. 16 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Automatic Fan Speed Mode Cooling Operation Time Diagram When Automatic Fan Speed is selected at Remote Control during cooling operation. • • • • Fan speed rotates in the range of Hi to Me. • • • • Deodorizing Control. 17 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Quiet Operation Control (For Coolin g Mode or cooling region of Soft Dry Mode) • • • • Purpose of this operation is to provide quite cooling operation compare to normal operation. • • • • W hen the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased 2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation. • • • • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. • • • • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1h 30 min (1h QLo, 30 min QLo + 50). After that, it goes back to Lo cool (However Quiet LED remains on). • • • • Manual Fan Speed:- − − − − RPM control during Lo cool − − − − RPM control during Hi & Me cool • • • • Auto Fan Speed:- • • • • Quiet Mode Operation will stop if:- − − − − Quiet mode button is pressed again. − − − − Stopped by ON/OFF switch. − − − − Timer OFF activates. − − − − W hen change mode to Air Circulation mode. 18 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Time DelaySafety Control Starting Current Control Anti-Freezing Control Compressor Reverse Rotation Protection Control Automatic Fan Speed Mode 8.3. Soft Dry Mode Operation • • • • The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start. • • • • During Soft Dry operation, the Indoor Fan will operate at Lo- speed. • • • • The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned off, it stops for 6 minutes. • • • • Once the compressor stops, it will not start for 3 minutes during Cooling operation. • • • • Same as Starting Current Control for Coolin g Mode operation. • • • • Same as Anti-Freezing Control for Coolin g Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.) • • • • Same as Compressor Reverse Rotation Protection Control for Coolin g Mode Operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.) When Automatic Fan Speed is selected at Remote Control during Soft Dry operation. • • • • Fan speed off and on at Lo- speed. • • • • Deodorizing Control. 19 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ
Soft Dry Operation Time Diagram Quiet Operation Control (For Dry region of Soft Dry Mode) 20 CS-XC9C KQ CU-XC 9CKQ / CS-XC12CK Q CU-XC12 CKQ