NDA-24307 CHAPTER 4 Page 343 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 4.3.4 PLO Card Replacement Procedure The PLO (PH-CK16-A/17-A) card is located in Slot No. 09 or 13 within the ISWM. Used together with a different direct digital interface circuit card, the card’s main function is to set up the clock synchronization on the network. Use the procedures below to replace the PLO card with a spare. Note:The ACT/STBY of PLO can be changed over via a single MB key operation on the circuit card (ACT...
Page 372
CHAPTER 4 NDA-24307 Page 344 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE OPE lamp on the new card is OFF. OPE lamp on the new card remains OFF. ATTENTIONContents Static Sensitive Handling Precautions Required END A Insert the new PLO card into the ISWM. On the new PLO card, set the MB key UP. Set the MB key on the new card DOWN.
Page 373
NDA-24307 CHAPTER 4 Page 345 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 4.3.5 PWR SW Card Replacement Procedure The PWR SW (PH-PW14) card is mounted in Slot No. 00 or 01 within the ISWM. The card’s main function is to supply DC -48V operating power to the same ISWM circuit cards and also DC +5, -5 V and +12 V output power to the PLO cards. Use the following procedures to replace the card with a new one. Replacement Procedure ATTENTIONContents Static Sensitive Handling Precautions Required P-ON lamp...
Page 374
CHAPTER 4 NDA-24307 Page 346 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 5. FAN UNIT REPLACEMENT This section explains how to replace the Fan Unit (FANU), which is fastened on the TOPU or inside the dedicated fan box within the system. Because the fan is a vital device to protect the system from heated air, it is recommended that the fan (a total of three per unit) be replaced at least every two years to guarantee its high performance. The mounting location of FANU differs, depending on the module...
Page 375
NDA-24307 CHAPTER 4 Page 347 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Figure 4-18 Preparation for FANU Replacement (Fans on TOPU) STEP 5 Remove the four screws fastening the fan to be replaced. Refer to Figure 4-19. Note:The removed screws are used in STEP 7 again. Do not dispose of them when unscrewing the fan here. PBX NECNEAX 2400 IMS NEAX 2400 IMSNEC Top Cover Unscrew the top cover by using a Phillips Screwdriver and remove it from the TOPU. . .. . .. ......... ......... ............
Page 376
CHAPTER 4 NDA-24307 Page 348 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE STEP 6 Remove the unscrewed fan from the FANU. STEP 7 Fasten the new fan with the removed screws. STEP 8 Connect the new fan cables to the fan connector and the connector(s) disconnected in STEP 4. STEP 9 Fix the fan fuse (5A) onto the PZ-M369. STEP 10 Set the PWR SW on the PZ-M369 to the AUTO position. Note:The switch setting of the PWR SW can be ON, depending on the location conditions of the system. STEP 11 Attach the top...
Page 377
NDA-24307 CHAPTER 4 Page 349 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Replacement Procedure: FANU in Fan Box When the FANU is mounted in the fan box, perform the following replacement procedures: STEP 1 Remove the front cover of the fan box. Then, extract the FANU. STEP 2 Turn OFF the PWR SW on the PZ-M369. (Refer to Figure 4-20.) STEP 3 Remove the fan fuse (5A) on the PZ-M369. STEP 4 Remove the fan cables from the fan connector and the connector(s) corresponding to the fan to be replaced (for...
Page 378
CHAPTER 4 NDA-24307 Page 350 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE STEP 5 Take off the four screws fastening the fan to be replaced. (Refer to Figure 4-21.) Note:The removed screws are used in STEP 7 again. Do not dispose of them when unscrewing the fan here. STEP 6 Remove the unscrewed fan from the FANU. STEP 7 Fasten the new fan with the removed screws. STEP 8 Connect the new fan cables to the fan connector and the connector(s) disconnected in STEP 4. STEP 9 Fix the fan fuse (5A) again onto...
Page 379
NDA-24307 CHAPTER 4 Page 351 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 6. CPR COOLING FAN REPLACEMENT This section explains how to replace a Cooling Fan in the back side of the CPR. This procedure is necessary when a fault is detected in the Cooling Fan. Because the fan is a vital device to protect the CPR from heated air, it is also recommended that the fan be replaced at least every two years, even if a fault is not detected. STEP 1 Set the CPU, whose rack houses the fan to be replaced, in STBY...
Page 380
CHAPTER 4 NDA-24307 Page 352 Issue 1 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Figure 4-23 Extraction of CPR from LPM STEP 7 Disconnect the fan cable from the connector in the backbone of CPR. Note:The Cooling Fan is located in the backbone of CPR and the cable connector lies in its right side. Refer to Figure 4-24. Figure 4-24 Rear View of CPR STEP 8 Loosen the two screws fastening the box that contains the fan inside. Slightly lift the box and remove it from the CPR. Refer to Figure 4-24 and Figure...