NDA-24306 CHAPTER 3 Page 83 Revision 1.0 Figure 008-2 Connection of Power and Ground Cables to Power Receiving Terminal NAP-200-008 Sheet 3/12 Connection of Power and Ground Cables from the Power Equipment Note 1:For 1/2 PIM configuration, connect the cable only to the A terminal. Note 2:An example of End Jointing (using A Type-Clamp terminal) is explained in Section 3 of this NAP. +80V:Terminal -48V:B Terminal G:B Terminal -48V:A Terminal G:A Terminal FE Terminal POWER AND GROUND CABLES POWER...
Page 112
CHAPTER 3 NDA-24306 Pag e 8 4 Revision 1.0 2. CONNECTION OF DC-DC CONVERTER FOR TELEPHONE SETS EQUIPPED WITH MESSAGE WAITING LAMPS NAP-200-008 Sheet 4/12 Connection of Power and Ground Cables from the Power Equipment START Cable Running Referring to Figure 008-3, run the power and ground cables. Removal of shorting piece and cable connectionReferring to Figure 008-4, remove the shorting piece from the +80 V connector of PZ-M371 card, then connect the cable provided on the +80 V Power Receiving...
Page 113
NDA-24306 CHAPTER 3 Page 85 Revision 1.0 Figure 008-3 Example Connection Diagram-DC-DC Converter for Message Waiting Lamps NAP-200-008 Sheet 5/12 Connection of Power and Ground Cables from the Power Equipment Note:The current capacity of the DC-DC Converter is calculated by multiplying the (current capacity of the message waiting lamp) by the number of telephone sets. PBX IV(WHITE)+80V DC-DC CONVERTER OUTPUT INPUT G +80V G –48V IV(BL) IV(R) IV(G) TO RECTIFIERF G
Page 114
CHAPTER 3 NDA-24306 Pag e 8 6 Revision 1.0 Figure 008-4 Removal of Shorting Piece and Cable Connection NAP-200-008 Sheet 6/12 Connection of Power and Ground Cables from the Power Equipment BASEU Power Receiving Terminal Block Remove the shorting piece Connect the Cable to the +80V Connector of PZ-M371 cardPZ-M371 +80V +80V Powe r C a bl e
Page 115
NDA-24306 CHAPTER 3 Page 87 Revision 1.0 3. END JOINTING OF POWER AND GROUND CABLES NAP-200-008 Sheet 7/12 Connection of Power and Ground Cables from the Power Equipment START Stripping of Insulation Sheath Strip the wire to exceed the length of the terminal body by 1 - 2 mm (1/8 inch). Clamping Referring to Figure 008-5, place the terminal body on the die with the soldered part facing upward. Referring to Figure 008-6, insert the stripped wire into the terminal body up to the insulation-sheath edge,...
Page 116
CHAPTER 3 NDA-24306 Pag e 8 8 Revision 1.0 Figure 008-5 Placing the Clamp Terminal on the Die Figure 008-6 Clamping Method NAP-200-008 Sheet 8/12 Connection of Power and Ground Cables from the Power Equipment CONVEX DIE SOLDERED PART TERMINAL CONCAVE DIE 1/8 inch (1 - 2mm) CONVEX DIE A A INSULATION SHEATH TERMINAL CONCAVE DIE SOLDERED PART CLAMPED PORTION CLAMPED PORTION CONDUCTOR A-A
Page 117
NDA-24306 CHAPTER 3 Page 89 Revision 1.0 4. BRANCHING OF POWER CABLES NAP-200-008 Sheet 9/12 Connection of Power and Ground Cables from the Power Equipment START Stripping Main and Branch Cable Referring to Figure 008-7, strip insulation coating with an electrician’s knife. Avoid damage to the conductor during the stripping process. Inserting of Cables into Terminal Insert the stripped main wire and branch wire into the terminal as shown in Figure 008-8. Clamping for Branch Jointing Place T-Type...
Page 118
CHAPTER 3 NDA-24306 Pag e 9 0 Revision 1.0 Figure 008-7 Stripped Length of Main and Branch Cable NAP-200-008 Sheet 10/12 Connection of Power and Ground Cables from the Power Equipment Table 008-1 Stripped Length APPLICABLE TERMINALSTRIPPED MAIN-WIRE LENGTH I 1 [inch (mm)]STRIPPED MAIN-WIRE LENGTH I 2 [inch (mm)] T-20 Approx. 1.2 (28) Approx. 1.0 (24) T-26 1.3 (32) 1.2 (28) T-44 1.5 (37) 1.3 (33) T-60 1.6 (40) 1.5 (36) T-76 1.7 (42) 1.6 (39) T-98 1.8 (44) 1.7 (41) T-122 1.7–1.9 (43–46) 1.6–1.7 (40–43)...
Page 119
NDA-24306 CHAPTER 3 Page 91 Revision 1.0 Figure 008-8 Inserting of Cables into Terminal Figure 008-9 Clamping for Branch Jointing NAP-200-008 Sheet 11/12 Connection of Power and Ground Cables from the Power Equipment 1/8 inch (1 - 2 mm) BRANCH CABLEMAIN CABLE BEND PRIOR TO INSERTION T TYPE TERMINAL Note:• Prevent the wires from slipping out of the clamp termi- nal by holding them firmly. Check the indication of the pressure regulator. Operate the pressure release lever to release the wires from...
Page 120
CHAPTER 3 NDA-24306 Pag e 9 2 Revision 1.0 Figure 008-10 Taping Figure 008-11 Covering NAP-200-008 Sheet 12/12 Connection of Power and Ground Cables from the Power Equipment Note:Taping should be done in two rounds with the tape overlapping half the tape width. INSULATION TAPE 0.4- 1.2 in. ABOVE 0.4 in. (10 mm) (10 - 30 mm) INSULATION COVER