NEC Neax 2400 Ipx Installation Manual
Here you can view all the pages of manual NEC Neax 2400 Ipx Installation Manual. The NEC manuals for Communications System are available online for free. You can easily download all the documents as PDF.
Page 61
NDA-24306 CHAPTER 2 Page 33 Revision 1.0 INSTALLATION DESIGN Because the Fusion link can be established either independently within the system (IPX-U) or jointly with other outside IPX and/or IMX series, the assignment of NCN can differ, depending on the network configuration. Figure 2-20 Example of NCN Assignment (1/3) Note 1:The network-level data (NDM data) can be assigned only at the NCN. However, other node-level data (LDM data) must also be assigned at each node (including ISW), depending on the...
Page 62
CHAPTER 2 NDA-24306 Pag e 3 4 Revision 1.0 INSTALLATION DESIGN Figure 2-20 Example of NCN Assignment (2/3) Note 1:The network-level data (NDM data) can be assigned only at the NCN. However, other node-level data (LDM data) must also be assigned at each node (including ISW), depending on the requirements. For more details, refer t o NAP-200-020 in Chapter 4 or the “Fusion Network System Manual.” Note 2:When the system is operated, the function to be performed by the ISW is only to provide the PCM time...
Page 63
NDA-24306 CHAPTER 2 Page 35 Revision 1.0 INSTALLATION DESIGN Figure 2-20 Example of NCN Assignment (3/3) Note 1:The network-level data (NDM data) can be assigned only at the NCN. However, other node-level data (LDM data) must also be assigned at each node (including ISW), depending on the requirements. For more details, refer to NAP- 200-020 in Chapter 4 or the “Fusion Network System Manual.” Note 2:When the system is operated, the function to be performed by the ISW is only to provide the PCM time...
Page 64
CHAPTER 2 NDA-24306 Pag e 3 6 Revision 1.0 INSTALLATION DESIGN 9.4 Preparation of Trunking Diagram Prepare the trunking diagram according to the customer’s specifications. Since there are different kinds of switching offices such as a single office, network offices, etc. are involved, the trunking diagram must be prepared as per the customer’s specifications. 9.5 Preparation of Module Group Face Layout and Port Accommodation Diagram When mounting of various circuit cards in the PBX have been finalized,...
Page 65
NDA-24306 CHAPTER 2 Page 37 Revision 1.0 INSTALLATION DESIGN 10.1 AC Input, DC Power, and Ground Cables 1. For AC input cable, VCT (Polyvinyl Chloride Cabtyre Cable) should be used. However, if shielding is necessary, as is the case when the AC input cable is to be installed in parallel with a low-voltage power cable, etc., be sure to use VCT-S (Shielded Polyvinyl Chloride Cabtyre Cable). 2. For the power receiving terminals of the PBX, -48 V and G terminals are provided in dual (A side and B side). For...
Page 66
CHAPTER 2 NDA-24306 Pag e 3 8 Revision 1.0 INSTALLATION DESIGN Figure 2-21 DC Main Power Cable and Main Ground Cable Note 1:Do not make a multiple connection across “A” terminal and “B” terminal of -48V. Likewise, do not make a multiple connection across “A” terminal and “B” terminal of GND. Note 2:It is recommended that each -48 V lead from the PBX be connected to a separate circuit breaker at the rectifier. MDFMAT GROUND TERMINAL Earth Bar BATTERY AC POWER DISTRIBUTION BOARD RECTIFIER -48V G -48V G...
Page 67
NDA-24306 CHAPTER 2 Page 39 Revision 1.0 INSTALLATION DESIGN Table 2-10 Clamp Terminal Shape and Purpose TYPE SHAPE PURPOSE REMARKS AEnd terminal TBranching or extension of power cable
Page 68
CHAPTER 2 NDA-24306 Pag e 4 0 Revision 1.0 INSTALLATION DESIGN Note:Selection of T-Type Clamp Terminal The asterisk (*) in Table 2-11 indicates that an auxiliary conductor is needed when using a main power wire and a branch power wire of a thinner diameter, and the clamp terminal of the type indicated in the selected columns.Table 2-11 Selection of T-Type Clamp Terminal BRANCH MAIN14 AWG/ 2 mm 2 12 AWG/ 3.5 mm 2 10 AWG/ 5.5 mm 2 8 AWG/ 8 mm 2 6 AWG/ 14 mm 2CURRENT REMARKS 10 AWG *T-20 *T-20 *T-20...
Page 69
NDA-24306 CHAPTER 2 Page 41 Revision 1.0 INSTALLATION DESIGN Figure 2-22 Calculation Method for Sectional Area BATTERY RECTIFIERPBX IV1M1 I2M2 S= 0.018x(I1M1+I2M2) V where, S I1 M1 I2 M2 V: Sectional area required (mm 2) : Maximum current passing between battery and rectifier : Two-way cable length between battery and rectifier : Maximum current passing between rectifier and PBX : Two-way cable length between rectifier and PBX : Voltage drop
Page 70
CHAPTER 2 NDA-24306 Pag e 4 2 Revision 1.0 INSTALLATION DESIGN 10.2 Cables between the PBX and MDF With respect to lines, trunks, and NCU (PFT), 25P shielded the PBX and the MDF are connected using cables with a CHAMP (Amphenol) connector at one end. Table 2-13 shows the procedure for calculating the required number of cables. Figure 2-23 also shows an outline of cable connections from the Module Group to the outside. Table 2-13 Calculating the Number of Cables CABLE NAME CALCULATION SUB TOTAL LT Cable...