Home > Mitel > Communications System > Mitel SX-200 DIGITAL Pabx Information Manual

Mitel SX-200 DIGITAL Pabx Information Manual

Here you can view all the pages of manual Mitel SX-200 DIGITAL Pabx Information Manual. The Mitel manuals for Communications System are available online for free. You can easily download all the documents as PDF.

Page 21

Shipping, Receiving, And installation information 
DECRYPTION 
MODULE 
I r 
7736ROEO 
Figure 2-7 Main Control Card and Decryption Module 
Page 2-12  

Page 22

Shipping, Receiving, And Installation Information 
can be used for night bells, alarms, etc. Module power rating is 
2. 
a Music/Paging Module - Provides one 600 ohm balanced audio 
(music) input and a 200 ohm output, to a paging amplifier. 
There is also one relay contact, which can be used for control- 
ling an amplifier. Module power rating is 1. 
0 Console Module - Provides interface to certain Digital Line 
Interface Circuit-based peripheral devices. Each Attendant Con- 
sole requires a CONSOLE...

Page 23

Shipping, Receiving, And Installation Information 
7685ROEO 
Figure 2-8 Digital Interface Card 
Page 2-14  

Page 24

Shipping, Receiving, And installation Information 
Digital Peripheral Shelf 
2.23 Bay Control Card. 
The Bay Control Card (BCC) is installed in 
the lower rightmost slot of digital Bays 3 and 4. This card 
monitors lines, trunks and other circuits within the bay. 
Maintenance Panels 
2.24 Control Cabinet. 
The maintenance panel is located at the top 
front of the control cabinet, behind the door, and contains the 
following controls and connections for the PABX: 
Top Shelf Power - controls bay 3 power...

Page 25

Shipping, Receiving, And Installation Information 
PFT Switches - control source of power fail transfer 
initiation. 
Default Hardware Assignments 
2.27 The following hardware equipment assignments are pro- 
grammed into the default database; it is recommended that 
these default assignments be followed when first configuring or in- 
stalling a system. 
test line (terminal and jack) 
Bay 2, Slot 1, Circuit 1 
(requires ONS Line card at Bay 2, Slot 1) 
maintenance panel console jack 
bay 2, slot 3,...

Page 26

Shipping, Receiving, And Installation Information 
hook, and dial the required number. With a loop start trunk, go 
off-hook and dial the required number. Since the telephones 
are connected directly to the CO, usual PABX access codes are 
not dialed. 
Relays 
2.30 
Two relays are provided on the receiver module, which can be 
operated under control of the program, to control various sys- 
tem functions, such as night bells or alarms. 
relay contact ratings 90 Vrms at 0.1 A 
48 Vdc at 0.5 A 
Note: This...

Page 27

Shipping, Receiving, And Installation Information 
Output Waveform Sinewave or Quasi square wave (not 
square wave) 
Output Receptacle 
NEMA 15 A 3-pin grounded 
Holdup/Recharge Times Per customer requirements. 
Several recommended manufacturers of Uninterruptible Power Sup- 
plies has provided samples of their equipment which have proved to 
be compatible with an SX-200a 
DIGITAL PABX in laboratory tests. 
Please note that compliance to electrical installation and building 
codes is the responsibility...

Page 28

Shipping, Receiving, And installation Information 
E&M Trunk Module 
2.37 The E&M Trunk Module plugs into the Universal Card. It pro- 
vides interface to Types 1 or 5 E&M trunks. The module has a 
power consumption category of 3. Because of this, only three of these 
modules can be used per Universal Card. 
2.38 The E&M Trunk Module is set for the type of trunk in use by 
setting its eight DIL switches. 
2.39 
0 Facilities provided by the E&M Trunk Module include: 
selectable Type 1 or Type 5 signaling...

Page 29

Shipping, Receiving, And installation information 
3. INSTALLATION REQUIREMENTS 
Environmental Requirements 
3.01 
The SX-ZOO@ DIGITAL PABX equipment maybe installed in any 
location which fulfills the space requirements as detailed in 
paragraph 3.02, and is within the following temperature and humidity 
ranges: 
l Temperature +I0 to +4O”C (+50 to +104”F) 
0 Relative Humidity 20-80% (non-condensing) 
0 Maximum Altitude 4000 meters. 
Floor Space 
3.02 The minimum floor space for installation and...

Page 30

Shipping, Receiving, And Installation Information 
0 Near a reproducing or copying machine. A minimum clearance 
of 3 m (10 It) must be provided if the reproducing machine is 
not equipped with a filtering system, and the room should be 
ventilated by an exhaust fan. 
Power Supply Requirements 
3.04 The customer must provide one single-phase power receptacle 
for each cabinet, as follows: 
0 Each cabinet should have its own 120 V, 60 Hz, 15 A branch 
circuit. 
0 The power receptacle must be a 3-wire...
Start reading Mitel SX-200 DIGITAL Pabx Information Manual

Related Manuals for Mitel SX-200 DIGITAL Pabx Information Manual

All Mitel manuals