Page 161
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–21 To assist in troubleshooting, the state of each switch can be verif ied using these messages. A separate message displays the status of each input identif ied by the corresponding name as shown in the wiring diagrams in chapter 2. For a dry contact closure across the corresponding switch terminals the message will read “Closed”. 6.3.3 Clock PATH: ACTUAL VALUES A2 STATUS CLOCK The current time and date is displayed in this...
Page 162
6–22PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.4 A3 Power Analysis 6.4.1 Power Quality PATH: ACTUAL VALUES A3 POWER ANALYSIS POWER QUALITY VALUES •Ia/Ib/Ic CREST FACTOR: The crest factor describes how much the load current can vary from a pure sine wave while maintaining the system’s full rating. A completely linear load (pure sine wave) has a crest factor of (1 /0.707), which is the ratio of the peak value of sine wave to its RMS value. Typically, the crest factor...
Page 163
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–23 •PHASE A/B/C/N CURRENT THD: These messages display the calculated total harmonic distortion for each current input . •VOLTAGE Van/Vbn/Vcn/Vab/Vbc THD: These messages display the calculated total harmonic distortion for each voltage input . Phase-to-neutral voltages will appear when the setpoint S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING is set as “Wye”. Line-to-line voltages will appear when VT WIRING is...
Page 164
6–24PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING •Van/Vbn/Vcn/Vab/Vbc MAX THD: These messages display the maximum total harmonic value for each voltage input and the time and date of its occurrence. The setpoint S1 PQMII SETUP CLEAR DATA \CLEAR MAX THD VALUES is used to clear this value. Phase to neutral voltages will appear when the setpoint S2 SYSTEM SETUP CURRENT/ VOLTAGE CONFIGURATION VT WIRING is set to “Wye”. Line to line voltages will appear when VT...
Page 165
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–25 Table 6–1: List of Possible Events (Sheet 1 of 4) Displayed Event Name Event Description 3Φ +kvar DMD ↑Positive Reactive Power Demand Alarm/Control Pickup 3Φ +kvar DMD ↓Positive Reactive Power Demand Alarm/Control Dropout 3Φ +kW DMD ↑Positive Real Power Demand Alarm/Control Pickup 3Φ +kW DMD ↓Positive Real Power Demand Alarm/Control Dropout 3Φ kVA DEMAND ↑Apparent Power Demand Alarm/Control Pickup 3Φ kVA DEMAND ↓Apparent Power...
Page 166
6–26PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING Ia DEMAND ↓Phase A Current Demand Alarm/Control Dropout Ib DEMAND ↑Phase B Current Demand Alarm/Control Pickup Ib DEMAND ↓Phase B Current Demand Alarm/Control Dropout Ic DEMAND ↑Phase C Current Demand Alarm/Control Pickup Ic DEMAND ↓Phase C Current Demand Alarm/Control Dropout In DEMAND ↑Neutral Current Demand Alarm/Control Pickup In DEMAND ↓Neutral Current Demand Alarm/Control Dropout NEG kvar ↑Negative Reactive Power...
Page 167
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–27 POS kvar ↑Positive Reactive Power Alarm/Control Pickup POS kvar ↓Positive Reactive Power Alarm/Control Dropout POS kW ↑Positive Real Power Alarm/Control Pickup POS kW ↓Positive Real Power Alarm/Control Dropout POWER OFF Power Off POWER ON Power On PROGRAM ENABLE Setpoint Access On PULSE IN 1 ↑Pulse Input 1 Alarm/Control Pickup PULSE IN 1 ↓Pulse Input 1 Alarm/Control Dropout PULSE IN 2 ↑Pulse Input 2 Alarm/Control Pickup PULSE IN 2...
Page 168
6–28PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.4.5 Voltage Disturbance Main Menu PATH: ACTUAL VALUES A3 POWER ANALYSIS VOLTAGE DIST. RECORDER The Voltage Disturbance Recorder runs continuously and records the source, level and duration of each voltage disturbance. Up to 500 disturbances are recorded in a circular buffer. When over 500 disturbances are recorded, data for older disturbances are lost as new disturbances are recorded. Additionally, since the events are...
Page 169
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–29 The duration and average level are recorded in sub-menus as shown below. Sub-Menus PATH: ACTUAL VALUES A3 POWER ANALYSIS VOLTAGE DIST... 1(500): The DURATION is the length of time of the disturbance. If the disturbance is either a sag or a swell the duration will be recorded in cycles with a maximum possible value of 1 minute (3600 cycles at 60Hz). The VOLTAGE LEVEL represents the average level in volts for the...
Page 170
6–30PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.5 A4 Product Info 6.5.1 Software Versions PATH: ACTUAL VALUES A4 PRODUCT INFO SOFTWARE VERSIONS Product software revision information is contained in these messages. •MAIN PROGRAM VERSION: When referring to documentation or requesting technical assistance from the factory, record the MAIN PROGRAM VERSION. This value identif ies the f irmware installed internally in the flash memory. The title page of this instruction...