Page 191
CHAPTER 7: APPLICATIONS PQMII POWER QUALITY METER – INSTRUCTION MANUAL7–19 Total Space = (196224 / Record Size) – 1 As in the example, the total space calculated would be 196224 / 26 – 1 = 7546.07. This equates to 7546 records with 28 bytes of unused memory at the end of Block 1536. The total amount of space used in the structure can also be found in the Log Header in the Log Total Records f ield. Address 1270h in the PQMII Memory Map is the Holding Register for the f irst available parameter for...
Page 192
7–20PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 7: APPLICATIONS 7.6.5 Data Log Parameters Listed below are the parameters available for capturing data via the Data Logger. Note that these parameters will be placed within the Record structure of the Data Log in the order and size that they appear in this table. where: I = current; V = Voltage; P = Real Power; Q = Reactive Power; S = Apparent Power; PF = Power Factor; THD = Total Harmonic DistortionTable 7–1: Data Log Parameters DATA LOG...
Page 193
CHAPTER 7: APPLICATIONS PQMII POWER QUALITY METER – INSTRUCTION MANUAL7–21 7.7 Reading Long Integers from the Memory Map 7.7.1 Description The PQMII memory map contains data formatted as a long integer type, or 32 bits. Because the Modbus protocol maximum register size is 16 bits, the PQMII stores long integers in 2 consecutive register locations, 2 high order bytes, and 2 low order bytes. The data can be retrieved by the following logic: 7.7.2 Example Reading a positive 3 Phase Real Power actual...
Page 194
7–22PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 7: APPLICATIONS Following the method described above: DATA VALUE = (FF3A × 2 16) + EA7B hexadecimal = (65338 × 216) + 60027 converted to decimal = 4282051195 decimal The most signif icant bit of the High Order register is set , therefore the Data Value is: DATA VALUE = DATA VALUE – 2 32 = 4282051195 – 4294967296 = –12916101 Multiply the Data Value by 0.01 kW according to the Units and Scale parameter. The resultant 3 Phase Real Power value read...
Page 195
CHAPTER 7: APPLICATIONS PQMII POWER QUALITY METER – INSTRUCTION MANUAL7–23 7.8 Pulse Input Application 7.8.1 Description The PQMII has up to 4 Logical Switch Inputs that can be conf igured as Pulse Input Counters. Variables to consider when using the PQMII as a Pulse Input Counter are: •PQMII Switch Input A(D) Function: Def ines the functionality to be provided by the PQMII Switch Input . For use as a Pulse Input Counter, the PQMII Switch Input to be used must be assigned as either Pulse Input 1, 2,...
Page 196
7–24PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 7: APPLICATIONS 7.9 Pulse Totalizer Application 7.9.1 Description The PQMII has up to 4 Logical Switch Inputs that can be conf igured as Pulse Input Counters. One common application of these Pulse Inputs is their use as an energy totalizer for more than one circuit . One PQMII can totalize input from up to 4 different sources and sum these results into a single register. Variables to consider when using the PQMII as a Pulse Input Counter...
Page 197
CHAPTER 7: APPLICATIONS PQMII POWER QUALITY METER – INSTRUCTION MANUAL7–25 FIGURE 7–4: Multiple Metering Locations Various operating parameters must be taken into account . The PQMII Switch Inputs require a minimum 100 ms operation time to be detected. Therefore the Pulse Output Width should be equal to or greater than 100 ms. The duration of the contact operation can be indef inite. The internal Switch Input circuit of the PQMII is switched on and off at the times when the PQMII is reading the...
Page 199
PQMII POWER QUALITY METER – INSTRUCTION MANUAL8–1 PQMII Power Quality Meter Chapter 8: Warranty Digital Energy War ranty 8.1 GE Multilin Device Warranty 8.1.1 Warranty Statement General Electric Multilin (GE Multilin) warrants each device it manufactures to be free from defects in material and workmanship under normal use and service for a period of 24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the device...