PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–1 PQMII Power Quality Meter Chapter 6: Monitoring Digital Energy Monit oring 6.1 Actual Values Viewing 6.1.1 Description Any measured value can be displayed on demand using the MENU and MESSAGE keys. Press the MENU key to select the actual values, then the MESSAGE RIGHT key to select the beginning of a new page of monitored values. These are grouped as follows: A1 Metering, A2 Status, A3 Power Analysis, and A4 Product Info. Use the MESSAGE keys to...
Page 142
6–2PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.1.2 Actual Values Menu ACTUAL VALUES [] A1 METERING CURRENT []See page 6–4. MESSAGE VOLTAGE []See page 6–6. MESSAGE PHASORS []See page 6–8. MESSAGE POWER []See page 6–8. MESSAGE ENERGY []See page 6–12. MESSAGE DEMAND []See page 6–14. MESSAGE FREQUENCY []See page 6–15. MESSAGE PULSE INPUT [] COUNTERSSee page 6–16. MESSAGE ANALOG INPUT []See page 6–17. MESSAGE END OF PAGE A1 [] MESSAGE ACTUAL...
Page 143
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–3 MESSAGE EVENT RECORDER []See page 6–24. MESSAGE VOLTAGE DIST. [] RECORDERSee page 6–28. MESSAGE END OF PAGE A3 [] MESSAGE ACTUAL VALUES [] A4 PRODUCT INFO SOFTWARE [] VERSIONSSee page 6–30. MODEL [] INFORMATIONSee page 6–30. MESSAGE END OF PAGE A4 []
Page 144
6–4PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2 A1 Metering 6.2.1 Current Metering PATH: ACTUAL VALUES A1 METERING CURRENT •A, B, C CURRENT: Displays the current in each phase corresponding to the A, B, and C phase inputs. Current will be measured correctly only if the CT PRIMARY is entered to match the installed CT primary and the CT secondary is wired to match the 1 or 5 A input . If the displayed current does not match the actual current , check this setpoint and...
Page 145
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–5 •NEUTRAL CURRENT: Neutral current can be determined by two methods. One method measures the current via the neutral CT input . The second calculates the neutral current based on the three phase currents; using the instantaneous samples, Ia + Ib + Ic = In. If the sum of the phase currents does not equal 0, the result is the neutral current . When using the CT input , the neutral current reading will be correct only if the CT is...
Page 146
6–6PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2.2 Voltage Metering PATH: ACTUAL VALUES A1 METERING VOLTAGE VOLTAGE [] Van = 120 Vbn = 120 Vcn = 120 V MESSAGEIavg = 100 AMPS Vavg = 120 V L-N MESSAGEVab= 0 Vbc= 0 Vca= 0 V MESSAGEAVERAGE LINE VOLTAGE = 208 V MESSAGEVOLTAGE UNBALANCE = 0.0% MESSAGEVan MIN = 100 V 12:00:00am 01/01/95 MESSAGEVbn MIN = 100 V 12:00:00am 01/01/95 MESSAGEVcn MIN = 100 V 12:00:00am 01/01/95 MESSAGEVab MIN = 173 V 12:00:00am 01/01/95...
Page 147
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–7 •Van, Vbn, Vcn: Displays phase voltages corresponding to the A, B, and C voltage inputs. This voltage will be measured correctly only if the VT RATIO, VT NOMINAL SECONDARY , and VOLTAGE WIRING setpoints match the installed VTs. If the displayed voltage does not match the actual voltage, check the setpoints and wiring. This message appears only if the VT WIRING is conf igured for a wye input . •Iavg/Vavg: Displays the average...
Page 148
6–8PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING 6.2.3 Phasors PATH: ACTUAL VALUES A1 METERING PHASORS •Va PHASOR: Displays a phasor representation for the magnitude and angle of Va. Va is used as a reference for all other phasor angles. If there is no voltage present at the PQMII voltage inputs, then Ia will be used as the reference for all other angles. Va is also used as the reference when in Simulation Mode. •Vb/Vc PHASOR: Displays a phasor representation for the...
Page 149
CHAPTER 6: MONITORING PQMII POWER QUALITY METER – INSTRUCTION MANUAL6–9 MESSAGE PHASE A REAL POWER = 1000 kW MESSAGEPHASE A REACTIVE POWER = 120 kvar MESSAGEPHASE A APPARENT POWER = 1007 kVA MESSAGEPHASE A POWER FACTOR = 0.99 Lag MESSAGEPHASE B REAL POWER = 1000 kW MESSAGEPHASE B REACTIVE POWER = 120 kvar MESSAGEPHASE B APPARENT POWER = 1007 kVA MESSAGEPHASE B POWER FACTOR = 0.99 Lag MESSAGEPHASE C REAL POWER = 1000 kW MESSAGEPHASE C REACTIVE POWER = 120 kvar MESSAGEPHASE C APPARENT POWER =...
Page 150
6–10PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 6: MONITORING MESSAGE3Φ kVA MAX = 1007 12:00:00am 01/01/95 MESSAGE3Φ PF MAX = 0.99 Lag 12:00:00am 01/01/95 MESSAGEAΦ kW MIN = 1000 12:00:00am 01/01/95 MESSAGEAΦ kvar MIN = 120 12:00:00am 01/01/95 MESSAGEAΦ kVA MIN = 1007 12:00:00am 01/01/95 MESSAGEAΦ PF MIN = 0.99 Lag 12:00:00am 01/01/95 MESSAGEAΦ kW MAX = 1000 12:00:00am 01/01/95 MESSAGEAΦ kvar MAX = 120 12:00:00am 01/01/95 MESSAGEAΦ kVA MAX = 1007 12:00:00am 01/01/95 MESSAGEAΦ PF MAX =...