GE Pqm 2 Manual
Here you can view all the pages of manual GE Pqm 2 Manual. The GE manuals for Power Products are available online for free. You can easily download all the documents as PDF.
Page 201
PQMII POWER QUALITY METER – INSTRUCTION MANUALA–1 PQMII Power Quality Meter Appendix A Digital Energy Appendix A A.1 Mod 506: Capacitor Bank Switching A.1.1 Description The standard PQM software has been altered to allow the four output relays to be used for 4 step capacitor bank switching. A.1.2 Setpoints The following messages have been added to the PQMII setpoint structure to accommodate this modif ication. The messages are located in setpoints page S4 ALARMSCONTROLMOD 506 SETPOINTS (after the...
Page 202
A–2PQMII POWER QUALITY METER – INSTRUCTION MANUAL APPENDIX A •STEP 1(4) RELAY: The state of the output relay assigned in this message will be controlled by the STEP it is assigned to. Once a relay has been assigned to a particular step, it will not activate upon any other PQMII conditions (i.e. pulse output , alarm, etc.). If a particular relay has not been assigned to any STEP, it will function as per standard PQMII implementation. •STEP 1(4) PICKUP: When the three-phase kvar value is positive...
Page 203
APPENDIX A PQMII POWER QUALITY METER – INSTRUCTION MANUALA–3 •STEP 1(4) DROPOUT: When the three-phase kvar value becomes less than or equal to the value set in this setpoint the output relay assigned to the STEP will de-energize. Since over compensation is possible, the dropout value can be set to negative vars. •STEP 1(4) PICKUP DELAY: The STEP will turn on after the delay set in this setpoint has elapsed assuming all other conditions have been met . NoteThis delay setting will start counting down...
Page 204
A–4PQMII POWER QUALITY METER – INSTRUCTION MANUAL APPENDIX A PATH: ACTUAL VALUES A2 STATUS MOD 506 ACTUAL VALUES •PICKUP TIMERS: These timers are loaded with the STEP 1(4) PICKUP DELAY setpoint settings when the required conditions are met . The timers are displayed beginning with STEP 1 on the left and ending with STEP 4 on the right . •DISABLE TIMERS: These timers are loaded with the STEP 1(4) DISABLE TIME setpoint settings when the required conditions are met . The timers are displayed...
Page 205
APPENDIX A PQMII POWER QUALITY METER – INSTRUCTION MANUALA–5 A.1.5 Additions to Modbus Memory Map The following two sections are added to the Modbus Memory Map for Mod 506.. The following memory map format has also been added: GROUPADDR (HEX)DESCRIPTIONRANGESTEP VALUEUNITS and SCALEFOR-MATFACTORY DEFAULT MOD 506 ACTUAL VALUES0E10 Step 1 Pickup T imer --- --- 0.1 x F1 --- 0E11 Step 2 Pickup T imer --- --- 0.1 x F1 --- 0E12 Step 3 Pickup T imer --- --- 0.1 x F1 --- 0E13 Step 4 Pickup T imer --- --- 0.1...
Page 206
A–6PQMII POWER QUALITY METER – INSTRUCTION MANUAL APPENDIX A 3 = “1, 3, 4, 2” --- 4 = “1, 4, 2, 3” --- 5 = “1, 4, 3, 2” --- 6 = “2, 1, 3, 4” --- 7 = “2, 1, 4, 3” --- 8 = “2, 3, 1, 4” --- 9 = “2, 3, 4, 1” --- 10 = “2, 4, 1, 3” --- 11 = “2, 4, 3, 1” --- 12 = “3, 1, 2, 4” --- 13 = “3, 1, 4, 2” --- 14 = “3, 2, 1, 4” --- 15 = “3, 2, 4, 1” --- 16 = “3, 4, 1, 2” --- 17 = “3, 4, 2, 1” --- 18 = “4, 1, 2, 3” --- 19 = “4, 1, 3, 2” --- 20 = “4, 2, 1, 3” --- 21 = “4, 2, 3, 1” --- 22 = “4, 3, 1, 2” --- 23 = “4, 3,...
Page 207
APPENDIX A PQMII POWER QUALITY METER – INSTRUCTION MANUALA–7 A.2 Revision History A.2.1 Release Dates A.2.2 Release Notes Table A–1: Release Dates MANUAL GE PART NO. PQMII REVISIONRELEASE DATE GEK-106435 1601-0118-A1 1.0x 17 September 2003 GEK-106435A 1601-0118-A2 1.0x 06 November 2003 GEK-106435B 1601-0118-A3 2.0x 01 December 2003 GEK-106435C 1601-0118-A4 2.0x 02 December 2003 GEK-106435D 1601-0118-A5 2.1x 18 June 2004 GEK-106435E 1601-0118-A6 2.2x Not released GEK-106435F 1601-0118-A7 2.2x 15 May...
Page 208
A–8PQMII POWER QUALITY METER – INSTRUCTION MANUAL APPENDIX A Table A–3: Major Updates for GEK-106435M (GEK-106475D) SECT (AC)SECT (AD)CHANGE DESCRIPTION T itle T itle Update Manual part number to 1601-0120-AD (1601-0130-A5) 1.5.2 1.5.2 Update MOD 506 update A.1.2 A.1.2 Added Note added Table A–4: Major Updates for GEK-106435L SECT (AB)SECT (AC)CHANGE DESCRIPTION T itle T itle Update Manual part number to 1601-0120-AC --- --- Update New Communications Guide (formerly Ch.7) 1.6.1 1.6.1 Update...
Page 209
APPENDIX A PQMII POWER QUALITY METER – INSTRUCTION MANUALA–9 Table A–7: Major Updates for GEK-106435G PA G E (A7)SECT (A8)CHANGE DESCRIPTION T itle T itle Update Manual part number to 1601-0120-A8 1.6.1 Update Voltage Input Specif ication change 5.2.6 Text Addn. Modbus time and date setting 2.2.8 Text Change Switch Input Table A–8: Major Updates for GEK-106435F PA G E (A5)PA G E (A7)CHANGE DESCRIPTION T itle T itle Update Manual part number to 1601-0120-A7 7-9 7-9 Update Updated Modbus Memory Map 7-58...