    Fieldbus Direct, CPVSC1-AE16-DN
    Technical data – Fieldbus node CPVSC1-AE16-DN
    CPVSC1 fieldbus node for communica-
    tion between a CPVSC1 valve terminal
    and a fieldbus master. The fieldbus
    node is used for activation of a
    CPVSC1 valve terminal with up to
    16 solenoid coils on max. 16 valve
    positions and for displaying the
    switching status via LED.
    TheCPVSC1…valvesareactivated
    using automatic current reduction,
    which results in less power consump-
    tion and heat emission. 16 digital
    inputs and 8 digital outputs or
    16 solenoid coils can be connected
    via a serial CP string extension.
    TheCPVSC1fieldbusnodesupports
    the DeviceNet protocol and conforms
    to the equipment profile of the
    pneumatic valve.
    Application
    Bus connection
    The DeviceNet connection is estab-
    lished via a 5-pin M12 plug with pins
    that corresponds to the specific mini
    connector. A DeviceNet installation
    with a higher degree of protection is
    typically configured using main and
    branch lines that are connected via
    T- pieces.Various manufacturers such as Turck,
    Lumberg and Rockwell offer finished
    cables and terminating resistors. The
    terminating resistors are attached to
    the two outermost T-pieces. This
    installation technique keeps the bus
    closed while a bus station is being
    removed.In order to prevent confusion when
    establishing a connection to the field-
    bus, a Micro Style M12, 5-pin plug
    connector with a straight socket
    (A-coded) is used. A Micro Style M12,
    5- pin plug connector with a straight
    socket (B- coded) is used for the power
    supply. 
    						
    							Info 201 – Subject to change – 2004/1122
    Fieldbus Direct, CPVSC1-AE16-DN
    Technical data – Fieldbus node CPVSC1-AE16-DN
    Condition monitoring
    Condition monitoring supports the
    preventative maintenance of the func-
    tionchaininautomationsystems.
    Each valve is assigned a switching
    cycle counter that automaticallyregisters movements of the system
    components.
    Once a maximum number of
    activations is reached, a message issent to the controller via DeviceNet
    and maintenance can be started. In
    the same way condition monitoring
    supports the determination of theservice intervals for the function
    chain.
    All movements immediately after
    installation are registered.
    General technical data
    Ty p eCPVSC1 -AE1 6 -DN
    Part No.538 654
    CP string extensionYes
    16 inputs and 8 outputs (or 16 valves)
    Baud rates[kbps]125, 250, 500
    Addressing range0…63
    Set using switch module
    Product familyPneumatic valve (27 dec.)
    Ident. number4736 dec.
    Type of communicationPolling, change of state, strobed I/O
    Configuration supportEDS file and graphics symbol
    Max. no. of solenoid coils2x16
    Max. no. of outputs8 (1x16 solenoid coils omitted)
    Max. no. of inputs16
    LED diagnostic displaysPSCommon message concerning supply voltagegpy
    PLPower supply for valves
    SFCP system error
    NETDeviceNet network status
    MODDeviceNet module status
    Device-specific diagnosis via DeviceNetShort circuit/overload of outputs
    Short circuit/overload of inputs
    Undervoltage of valve terminal
    Undervoltage of valve terminal (extension)
    Undervoltage of output module
    Undervoltage of sensor supply
    Missing module on CP string
    Condition monitoring
    Operating voltageNominal value[V]24 DC, reverse polarity protectedpgg
    Permissible range[V]20.4 … 26.4 DC
    Power failure buffering[ms]20
    Current consumption[mA]Max. 200 + sensor supply
    Residual ripple[Vss]4
    Protection class to EN 60 529IP40 (with fitted cover)
    Vibration resistanceTo EN 60 068-2-6: Wall mounting class 2
    H-rail mounting class 1
    Shock resistanceTo EN 60 068-2-27: Wall mounting class 2
    H-rail mounting class 1
    To EN 60 068-2-29: Wall mounting class 1
    H-rail mounting class 1
    ApprovalCE
    Temperature rangeOperating[°C]–5 … +50pg
    Storage[°C]–20 … +50
    MaterialsPolymer
    DimensionsInfo 226
    WeightInfo 226
    Technical data for valvesInfo 226 
    						
    							2004/11 – Subject to change – Info 20123
    Fieldbus Direct, CPVSC1-AE16-DN
    Technical data – Fieldbus node CPVSC1-AE16-DN
    Connection and display components
    654 73218
    1Connection for CP extension
    2Connection for power supply
    3Connection for fieldbus
    4DIL switch for CP extension
    5Rotary switch for baud rate
    6Rotary switch for station number
    7Earth terminal
    8Cover (for IP40 protection)
    Pin allocation for fieldbus interface
    PinSignal-specific
    core colourSignalDesignation
    1blankScreenConnection to housing
    2red24 V DC bus24 V supply CAN interface
    3black0Vbus0VCANinterface
    4whiteCAN_HReceived/transmitted data high
    5blueCAN_LReceived/transmitted data low 
    						
    							Info 201 – Subject to change – 2004/1124
    Fieldbus Direct, CPVSC1-AE16-DN
    Accessories – Fieldbus node CPVSC1-AE16-DN
    Ordering data
    DesignationTy p ePart No.
    Power supply Micro Style M12
    Power supply socket, for Micro Style connection, M12, 5-pin, straight socket (B-coded)NTSD-GD-9-M12-5POL-RK538 999
    Bus connection Micro Style M12
    Fieldbus socket for Micro Style connection, M12, 5- pin, straight socket (A- coded)FBSD-GD-9-5POL18 324
    Valve terminal connection
    Connecting cable with angled plug and angled socket0.5 mKVI-CP-1-WS-WD-0,5178 564ggpgg
    1mKVI-CP-1-WS-WD-1.0191 892
    2mKVI-CP-1-WS-WD-2163 139
    3mKVI-CP-1-WS-WD-3.0191 893
    5mKVI-CP-1-WS-WD-5163 138
    Connecting cable with straight plug and angled socket5mKVI-CP-1-GS-WD-5163 137
    8mKVI-CP-1-GS-WD-8163 136
    Connecting cable with straight plug and straight socket2 m, for chain link trunkingKVI-CP-2-GS-GD-2170 234ggpgg
    5 m, for chain link trunkingKVI-CP-2-GS-GD-5170 235
    8 m, for chain link trunkingKVI-CP-2-GS-GD-8165 616
    User documentation
    UserdocumentationforCPVDirect,CPVfieldbusnodeGermanP.BE-CPASC-CPVSC-DE539 008,
    DN2EnglishP.BE-CPASC-CPVSC-EN539 009
    ItalianP.BE-CPASC-CPVSC-IT539 010
    FrenchP.BE-CPASC-CPVSC-FR539 011
    SpanishP.BE-CPASC-CPVSC-ES539 012
    SwedishP.BE-CPASC-CPVSC-SV539 013
    Software
    CD-ROMValve terminal user
    documentation (PDF)P.CD-VALVE-T183 350
    UtilitiesP.CD-VI-UTILITIES-2533 500 
    						
    							2004/11 – Subject to change – Info 20125
    Fieldbus Direct, CDVI-DN
    Technical data – Fieldbus node CDVI-DN
    CDVI fieldbus node for communication
    between a CDVI valve terminal and a
    fieldbusmaster.Thefieldbusnodeis
    used for activation of a CDVI valve
    terminal with up to 24 solenoid coils
    on max. 12 valve positions and for
    displaying the switching status via
    LED.
    The CDVI… valves are activated using
    automatic current reduction, which
    resultsinlesspowerconsumption
    and heat emission. 16 digital inputs
    and 8 digital outputs or 16 solenoid
    coils can be connected via a serial CP
    string extension.
    The CDVI fieldbus node supports the
    DeviceNet protocol and conforms to
    the equipment profile of the
    pneumatic valve.
    Application
    Bus connection
    The DeviceNet connection is estab-
    lished via a 5-pin M12 plug with pins
    that corresponds to the specific mini
    connector. A DeviceNet installation
    with a higher degree of protection is
    typically configured using main and
    branch lines that are connected via
    T- pieces.Various manufacturers such as Turck,
    Lumberg and Rockwell offer finished
    cables and terminating resistors. The
    terminating resistors are attached to
    the two outermost T-pieces. This
    installation technique keeps the bus
    closed while a bus station is being
    removed.In order to prevent confusion when
    establishing a connection to the field-
    bus, a Micro Style M12, 5-pin plug
    connector with a straight socket
    (A-coded) is used. A Micro Style M12,
    5- pin plug connector with a straight
    socket (B- coded) is used for the power
    supply. 
    						
    							Info 201 – Subject to change – 2004/1126
    Fieldbus Direct, CDVI-DN
    Technical data – Fieldbus node CDVI-DN
    Condition monitoring
    Condition monitoring supports the
    preventative maintenance of the func-
    tionchaininautomationsystems.
    Each valve is assigned a switching
    cycle counter that automaticallyregisters movements of the system
    components.
    Once a maximum number of
    activations is reached, a message issent to the controller via DeviceNet
    and maintenance can be started. In
    the same way condition monitoring
    supports the determination of theservice intervals for the function
    chain.
    All movements immediately after
    installation are registered.
    General technical data
    Ty p eCDVI-DN
    Part No.197 648
    CP string extensionYes
    16 inputs and 8 outputs (or 16 valves)
    Baud rates[kbps]125, 250, 500
    Addressing range0…63
    Set using switch module
    Product familyCommunication adapter (12 dec.)
    Ident. number5141 dec.
    Type of communicationPolling, change of state
    Configuration supportEDS file and graphics symbol
    Max. no. of solenoid coils24+16
    Max. no. of outputs8 (1x16 solenoid coils omitted)
    Max. no. of inputs16
    LED diagnostic displaysPSCommon message concerning supply voltagegpy
    PLPower supply for valves
    MNSDeviceNet module/network status
    CPCP extension modules
    Device-specific diagnosis via DeviceNetShort circuit/overload of outputs
    Short circuit/overload of inputs
    Undervoltage of valve terminal
    Undervoltage of valve terminal (extension)
    Undervoltage of output module
    Undervoltage of sensor supply
    Missing module on CP string
    Condition monitoring
    Operating voltageNominal value[V]24 DC, reverse polarity protectedpgg
    Permissible range[V]20.4 … 26.4 DC
    Power failure buffering[ms]20
    Current consumption[mA]Max. 100 + sensor supply
    Residual ripple[Vss]4
    Protection class to EN 60 529IP66, IP67, IP69k1)
    Vibration resistanceTo EN 60 068-2-6: Wall mounting class 2
    H-rail mounting class 1
    Shock resistanceTo EN 60 068-2-27: Wall mounting class 2
    H-rail mounting class 1
    To EN 60 068-2-29: Wall mounting class 1
    H-rail mounting class 1
    ApprovalCE
    Temperature rangeOperating[°C]–5 … +50pg
    Storage[°C]–20 … +40
    MaterialsInfo 204
    Dimensions (LxWxD)[mm]Info 204
    Weight[g]Info 204
    1) To DIN 40 050 Part 9 (only up to 50 bar at 80°C; with sealed CP connection)
    Type 4 to NEMA 250 (hose-down test, test no. 5.7) 
    						
    							2004/11 – Subject to change – Info 20127
    Fieldbus Direct, CDVI-DN
    Technical data – Fieldbus node CDVI-DN
    Connection and display components
    4321
    6 51Power supply
    (plug, M12)
    2CP extension (M9)
    3Fieldbus input
    (plug, M12)
    4Fieldbus output
    (socket, M12)
    5PS Power system
    Operating voltage of
    electronics
    PL Power load
    Load voltage of valves
    MNS Module/network status
    CP Compact Performance
    CP extension modules
    6Status display of the solenoid
    coils
    Pin allocation for fieldbus interface (M12 socket)
    PinSignal-specific
    core colourSignalDesignation
    1blankScreenConnection to housing
    2red24 V DC bus24 V supply CAN interface
    3black0Vbus0VCANinterface
    4whiteCAN_HReceived/transmitted data high
    5blueCAN_LReceived/transmitted data low
    Pin allocation for fieldbus interface (M12 plug)
    PinSignal-specific
    core colourSignalDesignation
    1blankScreenConnection to housing
    2red24 V DC bus24 V supply CAN interface
    3black0Vbus0VCANinterface
    4whiteCAN_HReceived/transmitted data high
    5blueCAN_LReceived/transmitted data low 
    						
    							Info 201 – Subject to change – 2004/1128
    Fieldbus Direct, CDVI-DN
    Accessories – Fieldbus node CDVI-DN
    Ordering data
    DesignationTy p ePart No.
    Power supply Micro Style M12
    Power supply socket, for Micro Style connection, M12, 5-pin, straight socket (A-coded)FBSD-GD-9-5POL18 324
    Bus connection Micro Style M12
    Micro Style connection, M12, 5- pin, straight socket (A- coded)FBSD-GD-9-5POL18 324
    Micro Style connection, M12, 5-pin, straight plug (A-coded)FBS-M12-5GS-PG917 538
    Valve terminal connection
    Connecting cable with angled plug and angled socket0.5 mKVI-CP-1-WS-WD-0,5178 564ggpgg
    1mKVI-CP-1-WS-WD-1.0191 892
    2mKVI-CP-1-WS-WD-2163 139
    3mKVI-CP-1-WS-WD-3.0191 893
    5mKVI-CP-1-WS-WD-5163 138
    Connecting cable with straight plug and angled socket5mKVI-CP-1-GS-WD-5163 137
    8mKVI-CP-1-GS-WD-8163 136
    Connecting cable with straight plug and straight socket2 m, for chain link trunkingKVI-CP-2-GS-GD-2170 234ggpgg
    5 m, for chain link trunkingKVI-CP-2-GS-GD-5170 235
    8 m, for chain link trunkingKVI-CP-2-GS-GD-8165 616
    User documentation
    User documentation for CDVI-DNGermanP.BE-CDVI-DN-DE539 044
    EnglishP.BE-CDVI-DN-EN539 045
    ItalianP.BE-CDVI-DN-IT539 048
    FrenchP.BE-CDVI-DN-FR539 047
    SpanishP.BE-CDVI-DN-ES539 046
    SwedishP.BE-CDVI-DN-SV539 049
    Software
    CD-ROMValve terminal user
    documentation (PDF)P.CD-VALVE-T183 350
    UtilitiesP.CD-VI-UTILITIES-2533 500 
    						
    							2004/11 – Subject to change – Info 20129
    Fieldbus Direct, CPV-CO2
    Technical data – Fieldbus node CPV-CO2
    CPV fieldbus node for communication
    between a CPV valve terminal and a
    fieldbusmaster.Thefieldbusnodeis
    used for activation of a CPV valve
    terminal with 8 valve slices and
    16 solenoid coils and for displaying
    the switching status via LED.
    TheCPV-…valvesareactivatedusing
    automatic current reduction, which
    resultsinlesspowerconsumption
    and heat emission. 16 digital inputs
    and 8 digital outputs or 16 solenoid
    coils can be connected via a serial CP
    string extension.
    TheCPVvalveterminalsupportsthe
    CANopen protocol as per the
    specifications:
    DS 301, V4.02
    DS 401, V2.1
    TheCPVfieldbusnodeisavailablein
    three sizes, with identical
    performance characteristics:
    CPV10
    CPV14
    CPV18
    Application
    Bus connection
    Plug connector
    2xM12 Screw terminals
    Sub-D
    fieldbus plugThebranchlinelengthdoesnotapply
    no matter what type of connection is
    used.
    Screw terminals
    5-pin screw terminal strip
    For installations in protected
    environments (IP20)
    The bus connection is established via
    a5-pinrow.
    If the valve terminal is ordered with
    this bus connection, the 5-pin screw
    terminal strip will also be supplied. It
    is designed with double screw
    terminals for the incoming and the
    outgoing bus cable. This connection
    technology provides the function of a
    T-distributor.
    Plug connector 2xM12
    Plug connector 2xM12
    Installation with IP65 protectionThe bus connection is established via
    an M12 plug and socket.
    The bus connection fulfils the require-
    ment of a T-distributor, this means
    that the CPV valve terminal can be
    disconnected from the bus without
    interrupting the bus.
    Sub-D fieldbus plug
    9- pin Sub- D plug
    Installation with IP65 protection
    The bus connection is established via
    a 9-pin Sub-D plug as per the CAN in
    Automation (CiA) specification DS102
    with additional 24 V CAN transceiver
    supply (option as per DS102). The bus
    connector plug facilitates the connec-
    tion of an incoming and an outgoing
    bus cable. There are spring-loaded
    terminals for the four wires (CAN_L,
    CAN_H,24V,0V)oftheincomingand
    outgoing bus cable. 
    						
    							Info 201 – Subject to change – 2004/1130
    Fieldbus Direct, CPV-CO2
    Technical data – Fieldbus node CPV-CO2
    Condition monitoring
    Condition monitoring supports the
    preventative maintenance of the func-
    tionchaininautomationsystems.
    Each valve is assigned a switching
    cycle counter that automaticallyregisters movements of the system
    components.
    Once a maximum number of
    activations is reached, a message issent to the controller via CANopen
    and maintenance can be started. In
    the same way condition monitoring
    supports the determination of theservice intervals for the function
    chain.
    All movements immediately after
    installation are registered.
    General technical data
    Ty p eCPV10-GE-CO2-8CPV14-GE-CO2-8CPV18-GE-CO2-8
    Part No.525 876525 882525 884
    CP string extensionYes
    16 inputs and 8 outputs (or 16 valves)
    Fieldbus interfaceSub-D, 9-pin, socket (to DS102)
    Bus interface electrically isolated via optocoupler, 24 V DC supply
    CAN interface via bus
    Baud rates[kbps]125, 250, 500 and 1000
    Set using DIL switch
    Addressing rangeNode ID 1 … 127
    Set using DIL switch
    Product familyDigital I/O
    Communication profileDS 301, V4.02
    Device profileDS 401, V2.1
    Number of PDOs1Tx/Rx
    Number of SDOs1serverSDO
    Configuration supportEDS file and bitmaps
    Max. address volume, inputs[Byte]8
    Max. address volume, outputs[Byte]8
    Max. no. of solenoid coils2x16
    Max. no. of outputs8 (1x16 solenoid coils omitted)
    Max. no. of inputs16 digital
    LED diagnostic displaysPSOperating voltage for electronics and load supplygpy
    MNSBus status (module/network status)
    Device-specific diagnosisVia emergency message and object 1001, 1002 and 1003
    ParameterisationVia SDO
    Additional functionsCondition counter
    Operating voltageNominal value[V DC]24, reverse polarity protectedpgg
    Permissible range[V]20.4 … 26.4
    Power failure buffering[ms]10
    Current consumption[mA]Max. 200 + sensor supply
    Protection class to EN 60 529IP65
    ApprovalCE, CiA certification
    Temperature rangeOperating[°C]–5 … +50pg
    Storage[°C]–20 … +70
    MaterialsHousingDie-cast aluminium
    Plug capPolyamide, glass fibre (Ultramide)
    SealNitrile rubber, Neoprene
    DimensionsInfo 213 Valve terminal CPV
    WeightInfo 213
    Technical data for valvesInfo 213 
    						