Home > ATT > Communications System > ATT DEFINITY Communications System Generic 3 For Single-Carrier Cabinets Instructions Manual

ATT DEFINITY Communications System Generic 3 For Single-Carrier Cabinets Instructions Manual

    Download as PDF Print this page Share this page

    Have a look at the manual ATT DEFINITY Communications System Generic 3 For Single-Carrier Cabinets Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Install and Connect the Cabinets
    4-34Issue 1  September 1995 
    Install Cable Clamps
    At the back of the cabinets, on each ground plate, install two cable clamp s 
    using the screws provided (see Figure 4-23). These clamp s hold the 25-pair 
    input/output or cross-connect field cables in place.
    Figure 4-23. Location of Cable Clamps
    452 1
    3
    Figure Notes:
    1. Cable Clamp
    2. Cable Slack Manager
    3. Switch Cabinet4. Cabinet Trough for Port  Cables
    5. Spare Center Troughs 
    						
    							Install Front Plates
    Issue 1  September 1995 
    4-35
    Install Front Plates
    The front plates provide electromagnetic radiation and radio frequency (RF) 
    shielding and earthquake protection. 
    If you do not have a requirement for electromagnetic radiation shielding, radio 
    frequency shielding, or earthquake protection, use the cabinet clips as 
    described in this section.
    Install Front Plates on Systems with
    Earthquake Protection
    Refer to Ap pendix B to install the front plates to help provide earthquake 
    protection and radiation shielding.
    Front plates are used in place of cabinet clips (as described in Appendix B), for 
    earthquake protection.
    Install Cabinet Clip On Systems without
    Earthquake Protection
    A cabinet clip is required between each cabinet to stabilize the c a binets. 
    Figure 4-24. Cabinet Clip
    At the front of the c a binets, install a cabinet clip (Figure 4-24) between each 
    cabinet by hooking the clip into the slot of the upper cabinet and sna p ping the 
    straight leg of the clip into the slot on the lower c a binet (see Figure 4-25).
    1 
    						
    							Install and Connect the Cabinets
    4-36Issue 1  September 1995 
    Figure 4-25. Location of Cabinet Clips
    1
    2
    3
    4
    5
    1. Port Cabinet D
    2. Port Cabinet C
    3. Cabinet clips4. Port Cabinet B
    5. Basic Control Cabinet A
    Figure Notes: 
    						
    							Issue 1  September 19955-1 
    5
    Install Telecommunications Cabling
    This chapter describes how to install telecommunications cables and cross-
    connect equipment. 
    The specific equipment being installed varies on what was ordered for your site. 
    Use the material presented in this chapter as an example.
    Install the Cross-Connect Field
    This section describes how to connect to the cross-connect field. 
    Typical Cross-Connect Field Using
    110-Type Hardware
    The cross-c onnect field is normally located directly behind the switch cabinet. 
    Figure 5-1 shows a typical cross-connect field installation using 110A-type 
    terminal blocks. Allow at least 3 feet (1 meter) between the back of cabinet and 
    the 110-type hardware. 
    						
    							Install Telecommunications Cabling
    5-2Issue 1  September 1995 
    Figure 5-1. Typical Cross-Connect Field Installation: 
    110A-Type Terminal Blocks 
    3
    2
    87
    4
    5
    5
    5
    5
    1
    6
    1. D Ri n g
    2. Trunk auxiliary field
    3. Port distribution field
    4. Station distribution field5 . Sta ti on  c a b l es
    6 . Swi tch  c a b ine t
    7. Z113A cable slack manager
    8. 25-pair cable to switch cabinet
    Figure Notes: 
    						
    							Issue 1  September 19955-3
    In Figure 5-1, a pproximately 576 4-Pair or 768 3-Pair Station Capacity is 
    illustrated. 
    Hardware Installation
    These hardware installation instructions are written so one system technician 
    can install the following equipment:
    nCross-c onnec t field
    nCable slac k managers
    nSneak c urrent p rotec tor (507B) 
    The preferred cross-connect field location is directly b ehind the switch cabinet. 
    Install Cable Slack Managers
    To install the cable slack managers (Figure 5-2), proceed as follows: 
    1. Place the Z113A cable slack manager against the wall under the cross-
    connect field, aligning the left side of the cable slack manager with the 
    first terminal block of the trunk/auxiliary field.
    2. Place the next cable slack manager beside the previous cable slack 
    manager. Align the tabs and interlocks and snap the cable slack 
    managers together.
    3. Repeat Step 2 until all c a ble slack managers are installed.
    NOTE:
    Nine holes (1/4-inch or 0.6 cm) are provided in a cable slack manager 
    base for earthquake mounting. Also, if a cable slack manager base is 
    mounted on an uneven floor, shims may be required to level it and insure 
    proper fit of the covers. Holes are p rovided in the sides of the base for 
    bolting cable slack managers together. Bolts and shims are not provided.
    Route Cables from Cabinet to Cross-
    Connect Field
    Use the following guidelines when routing cables from the cabinet to the cross-
    connect field. 
    nWhen c a ble routing is to the top/bottom of the cross-connect field, each 
    port cable is connected at the cabinet and routed along the front trough 
    of the cable slack manager to the c onnecting/terminal block. The cable is 
    then terminated.
    nEnough slack must be left at the cabinet end of the cable to allow for 
    proper dressing of the cables (Figure 5-3). 
    						
    							Install Telecommunications Cabling
    5-4Issue 1  September 1995 
    nRoute the cable from the cabinet to the wall. Place the c a ble beside one 
    of the rows of columns in the cable slack manager (see following note).
    NOTE:
    Retainers mounted on the columns keep the cable from protruding 
    above the top of the base of the cable slack manager.
    nDetermine the length of the cable required to reach from the cable slack 
    manager to the assigned connecting/terminal block.
    nThe c a ble must be supp orte d on the wall.
    nCable slack is stored by coiling the cable around the columns in the 
    cable slack manager. The first run should always g o across the full length 
    of the five columns in the cable slack manager.
    nConnect the cable to the assigned connecting/terminal block. 
    						
    							Issue 1  September 19955-5
    Figure 5-2. Cable Routing Through Cable Slack Manager for 
    Single Cabinet Installation 
    452 1
    3
    1. Cable Clamp
    2. Trunk Auxiliary Field3 . Swi tch  Ca b i ne t
    4. Cabinet Trough for Port Cables
    5. Spare Center Troughs
    Figure Notes: 
    						
    							Install Telecommunications Cabling
    5-6Issue 1  September 1995 
    Figure 5-3. Typical Port Cable Installation at Switch Cabinet
    Connect Control Carrier Outputs 
    Cable
    Plug the connector c able in the AUX connector on the rear of the control carrier. 
    Route the connector cable through the c a ble slack manager to the assigned 
    connecting block in the yellow field of the trunk/auxiliary field.
    Refer to Table 9-9 for pinout information.
    The output wiring connections for the Initialization Ad ministration System 
    (INADS) trunk interface are described in Install Initialization and Ad ministration 
    System (INADS) Interface on pa ge 9-21
    .
    3
    4
    4
    4
    4
    4
    4
    55
    1
    2
    1. B25A cables
    2. Loop and Drape Excess Fibre-Optic 
    Cable. Do Not Route Fibre-Optic Cable 
    and B25A Cables Together.3. Fibre-Optic Cable Sheath
    4. Port Cabinet
    5. Control cabinet
    Figure Notes: 
    						
    							Issue 1  September 19955-7
    Label Cables
    Label the cables as d esc rib e d in this section. 
    The port label shown in the next figure is installed on both ends of the
    25-pair cables  connecting to the trunk/auxiliary field and/or the distribution field. 
    See Table 5-1 for the c a ble label and colour code. The building and floor labels 
    connect from the equipment room to a site/satellite location on another floor or in 
    another building. The auxiliary circuits connect to the trunk/auxiliary field.
    Figure 5-4. Equipment Room Cabling Labels 
    Install Trunk Cables Among Network 
    Interface, Sneak Current Protector, 
    and 
    Switch Cabinet
    The 1-pair external trunks are installed by the local telephone company in the 
    trunk auxiliary field. Tie trunks also a ppear in the trunk auxiliary field. Refer to 
    callout 2 on Figure 5-1 on p a ge 5-2. 
    Table 5-1. Cable Labels
     Number Label Name Range Colour
    1 Port Label 1A1-1A10, 1B1-1B20, 1C1-1C20, 
    1D1-1D20, 1E1-1E20Pu rp l e
    2 Building Field Identified Blue/Yellow
    3 Floor Field Identified Blue/Yellow
    4 Auxiliary Cable Field Identified Yellow
    5 Site or Satellite A-F and/or Field Id entified Blue/Yellow
    1AA 2
    34512 
    						
    All ATT manuals Comments (0)

    Related Manuals for ATT DEFINITY Communications System Generic 3 For Single-Carrier Cabinets Instructions Manual