61 Connection example with AC input device Contact output type Non-contact output type Cautions when using lead switch with LED Even when using input contact with embedded serial LED such as lead switch with LED, make sure to supply voltage higher than ON voltage to the PLC input terminal. Pay extra attention, in particular, when connecting multiple switches in serial. Input terminal COM terminal AC input unit Input terminal COM terminal AC input unit Lead switch with LED ON voltage error...
Page 62
62 Cautions when using 2 wired type Use a breeder resistor as below when the leakage current from 2 wired type photoelectric switch or proximity switch keeps flowing into the PLC. DC 12-24V type input unit (OFF voltage 2.5V, input impedance 3 KΩ) 2 wired sensor DC input unit Since the OFF voltage of input is 2.5V, determine the R value to set the voltage between COM terminal and input terminal to be 2.5V or less. Input impedance is 3 KΩ For the resistor, W can be calculated as follows: (Power...
Page 63
63 Cautions when using limit switch with LED Use a breeder resistor as below when the leakage current from limit switch with LED keeps flowing into the PLC or LED is accidentally turned on. Limit switch with LED DC 12-24V type input unit (OFF voltage 2.5V, input impedance 3 KΩ) r: Internal resistance of limit switch (KΩ) R: Breeder resistance (KΩ) Since the OFF voltage of the input is 2.5V, set R to get the following current, when the power supply voltage is 24V. Once calculating I, follow the...
Page 64
64 Output wiring Checkpoints for output unit wiring NThere can be limits on the number of points that can be simultaneously turned on or load current, based on the unit type. Refer to the specification of each unit. Pay extra attention, in particular, when ambient temperature is high. NConnect protection circuit to inductive load or capacity load, etc. as below. NThere can be current limitation per Common for output units, so make sure not to exceed the allowed range. Protection circuit for...
Page 65
65 Cautions when using capacity load Use protection circuit as below to minimize the effect of a load with high inrush current. Use an external fuse to protect against overload NUnits embedded with fuse can prevent damages in case of output shortage. NSince the unit with embedded fuse cannot protect all the components against overload, it is recommended that you use an external fuse for every point. NThe components of output unit may not be protected in case of shortage. Cautions for leakage...
Page 66
66 Terminal Block Type Module Wiring Compressed terminal, M3.0 The terminal base for the NX70 PLC I/O modules (Terminal Type) uses M3.0 terminal screw. Use the following compressed terminals for terminal wiring. Open terminal Circular terminal Removable terminal block NTerminal block of this type of I/O unit can be separated from the unit with wires connected, by unfastening the screws on both ends. NMake sure to refasten the screws after wiring. 7. 0 m m or less 7. 0 m m or less Screws Terminal...
Page 67
67 Connector Type Module Wiring Wiring Wiring method Both NX700 32-point I/O module (NX-X32D, NX-Y32RV, NX-Y32T) and 64-point I/O module (NX-X64D, NX-Y64T) use 40-pin MIL type connectors. To connect to external devices, 1. Insert each pin into socket 2. or, use harness with flat cables. (Available on the market) Connecting PIN type PIN type connection. Insert each PIN into a socket. Detail wirings are shown on the next page. Product name Catalog numberProduct specifications I/O connector ASSY...
Page 68
68 Connecting with harness (Using flat cable connector) 40-pin flat cable connector is used, and 20 crimped terminals are connected at the end. Its total length is 1.5m. Direct connection to the unit. Product nameCatalog numberProduct specifications Flat cable ASSYNX-CBLDCDC IN 32 points, 64 points Connectors harness cable 1.5m NX-CBLTRTR OUT 32 points, 64 points Connectors harness cable 1.5m NX-CBLRYRelay OUT 32 points Connectors harness cable 1.5m Applied products 32 pointsNX-X32D (DC IN 32...
Page 69
69 Pressure welding socket for PIN type connection Direct pressure welding with clothings on saves wiring time and efforts. Wiring 1. Bend the contact part at a carrier, and set it into the pressure welding device. 2. Insert both cables with case on until touching each other, and hold the pressure welder slightly. 3. Insert the cables into the housing once welding is done. Contact removal pin for wiring failure. In case of wiring failure or cable pressure welding failure, use the contact removal...
Page 70
70 Wiring flat cable connector Cautions when using flat cable connector When a flat cable connector is used for direct connection, the mapping between cable No. and I/O No. is as follows: Connecting 32-point unit (NX-X32D, NX-Y32T, NX-Y32RV) Mapping table between flat cable No. and I/O (32 points) NC: No Connection 2 391 40DC INNX-X32D Product nameCatalog numberSpecifications Flat cable (1.5m)NX-CBLDCDC IN 32 points (NX-X32D) NX-CBLTRTR OUT 32 points (NX-Y32T) NX-CBLRYRelay OUT 32 points...