Samsung Ht As700 User Manual
Here you can view all the pages of manual Samsung Ht As700 User Manual. The Samsung manuals for Home Theater System are available online for free. You can easily download all the documents as PDF.
Page 101
101 Specialty Module Dimensions NX-IOLINK Module Dimensions 115 .5 35.0 RS232C COM1 RS485 RS232C COM2 RS485RESET 104 .0 AU I T 12V 35.035.0 LINK NO00 0 FG - + + - F.G NX-MWLINKMW LINKNX-SC USCUNX-ETHER N ETEtherN et unit (mm) + - FG LINE 4 3 2 1 OFF ON MODE SW 24V D C INPUT+ -105.0 70.5 unit (mm)
Page 103
103 ASCII Code Table b4b3b2b101234567 00000NULDEL0@P`p 00011SO HDC1!1AQaq 00102ST XDC2“2BRbr 00113ETXDC3#3CScs 01004EO TDC4$4DTdt 01015ENQNAK%5EUeu 01106ACKSYN&6FVfv 01117BELETB'7GWgw 10008BSCA N(8HXhx 10019HTEM)9IYiy 1010ALFSUB*:JZjz 1011BVTESC+;K〔k{ 1100CFFFS‘N∧n~ 1111FSIUS/?O_oDEL b8b7b6b5 b8 b700001111 b600110011 b501010101 C R SPA CE
Page 105
105 Appendix Communication Protocols The communication protocol of NX-CPU700p PLC provides a complete method of communications between the graphic consol programmers (WinGPC) and the PLC by controlling programs, CPU status, and I/O at user’s convenience. The user can easily expand the capabilities of the overall PLC system by communicating to the PLC using a variety of peripheral communications equipment in accordance with the following communication protocols and procedures. Additionally, the...
Page 106
106 Communication Protocols Q (Query) is a signal sent from the peripheral devices to the PLC after setting the network ID number and the function code for the PLC to communicate with. QA (Query Acknowledge) is a signal sent from the PLC to the peripheral devices, indicating that the Q signal from the peripheral device was received. RR (Response Request) is a signal sent from the peripheral device to the PLC, indicating that the QA signal from the PLC was received. This signal is sent...
Page 107
107 When several CPU modules are connected to one communication network, they must use individual ID numbers. The PLC’s network ID number is configured using the WinGPC. Communication steps The NX CPU can support 2-step or 4-step communication methods. The communication methods are easily distinguished each other by selecting and sending the function code of the Q frame. Even for the 4- step method, the 2-step method can be used for the repeated function. This function sends and receives the only RR...
Page 108
108 2-step communication method 4-step communication method No communication error Peripheral device PLC Peripheral device PLC Peripheral device PLC When R is not received Response to repeated function code 3 seconds No communication error Peripheral device PLC Peripheral device PLC Peripheral device PLC When QA is not received Peripheral device PLC When R is not received Response to repeated function code3 secondsFor the internal processing of the PLC CPU send RR at least 5 msec after receiving QA. 3...
Page 109
109 Function codes included in the query Each function code is 1 byte. When the PLC receives a query (Q), the function code of the final response (R) is formed by adding $80 (hex) to the function code sent by the query. The value added to the function code sent by the query differs for 2-step and 4-step by $20 (hex). The function code of the R message can be used by the peripheral device to verify that the correct Q message has been received by the PLC. Communication function codes $ notes...
Page 110
110 Cyclic Redundancy Checking (CRC) The CRC is a 2-byte checksum code attached to the end of the message by the sender to check if the communication frame is transmitted without error. The sender calculates the CRC when it sends one-byte message, and the receiver should also calculate the CRC from the data of the message. Since this CRC calculation takes a long time when writing a communication program, you should find any ways to increase the speed of this part to avoid errors and improve the...