21 Operating condition setting switches Switch for termination resistance setting (DIP switch 1) Switch for communication and program booting method setting (DIP switch 2) Pin No.Pin settingDescriptionDIP Switch 1 43 ON ONFor RS-485 communication, set both pins 3 and 4 to On if the system is a termination station. (Enables termination for COM1 terminal) OFF OFFFor RS-485 communication, set both pins 3 and 4 to Off if the system is not a termination station. (Disables termination for COM1...
Page 22
22 Power Supply Module Hardware features 1. Power status LED Turns on when power is on. 2. Power fuse holder 3. Terminal block Terminal block for power wiring. Crimped terminal for M3.5 can be used. Detachable. 4. Power input terminal 110-240V AC Free Voltage power input terminal (NX-PWR220 is only for 220V ac). 5. Frame ground (FG) terminal As a grounding terminal, it is connected to the metal part of the backplane. Use triple grounding to prevent electric shock. 6. Service power terminal (24V...
Page 23
23 Specifications Input typeAC input power DC input power Catalog number NX-POWERNX-PWR220NX-PWRDC Input rated voltage110 to 220V AC Free Voltage220V AC 24V DC Allowed voltage range 85 to 264V AC 176 to 264V AC 24V DC ± 10 % Input power frequency 47 to 63Hz Inrush current 20A or less Rated output current 5V 4.0A, 24V 0.5A 5V 6.0A 5V 3.0A Fuse 250V 1.5A Weight 350g 300g 320g ATTENTIONNX-POWER module does not guarantee protection against momentary power failure at 110V ac. ATTENTIONMake sure that...
Page 24
24 I/O Modules Hardware features 1. I/O Status LED Shows I/O ON/OFF status. 2. Terminal block fixing screw Fixes detachable terminal block on the unit. 3. Terminal block (20P, detachable terminal block) Terminal block for I/O and power wiring. Crimped terminal for M3.5 can be used. See Terminal Block Type Module Wiring in Chapter 4. 4. Connector 32 points (40P x 1), Connector 64 points (40P x 2) Connector for I/O contact and power wiring. Use harness for PIN type or flat cable. See Connector Type...
Page 25
25 Input unit specifications Internal circuit and wiring diagram Product nameDC input module Catalog numberNX-X16D Number of input points 16 points Insulation method Photocoupler Rated input voltage 12 to 24V Operating voltage range 10.2 to 26.4V Max. input current 10mA or less (for 24V) ON voltage/current Min. 9.6V OFF voltage/current Max. 2.5V Input impedance: Approx. 3 K Ω Response timeOFF → ON 10ms or less ON → OFF 10ms or less Internal current consumption (5V) 65mA or less Common method 8...
Page 26
26 Wiring diagram Internal circuit Product nameDC input module Catalog numberNX-X32D Number of input points 32 points Insulation method Photocoupler Rated input voltage 12 to 24V Use voltage range 10.2 to 26.4V Max. input current 10mA or less (for 24V) ON voltage/current Min. 9.6V OFF voltage/current Max. 2.5V Input impedance Approx. 3 K Ω Response timeOFF → ON 10ms or less ON → OFF 10ms or less Internal current consumption (5V) 130mA or less Common method 32 points/1COM (Common for polarity +, -)...
Page 27
27 Wiring diagram Internal circuit Same as NX-X32D. NThe connectors [I] and [II] have opposite orientation each other, so be careful with wiring. NThe COM terminal of the connector has a short inside of the unit. NFor wiring method, See Terminal Block Type Module Wiring in Chapter 4. NUse separate commercial cable harness (NX-CBLDC) and Pin Type Assy (CPL8890) for external connection. NNC: No Connection Product nameDC input module Catalog numberNX-X64D Number of input points 64 points Insulation...
Page 28
28 Wiring diagram Internal circuit Product nameAC input module Catalog numberNX-X16A110 NX-X16A220 Number of input points 16 points Insulation method Photocoupler Rated input voltage AC 100 to 120V AC 200 to 240V Operating voltage range AC 85 to 132V AC 170 to 264V Max. input current 20mA or less ON voltage/current Min. 80V/6mA Min. 160V/6mA OFF voltage/current Max. 30V/3mA Max. 50V/3mA Input impedance Approx. 15K ΩApprox. 20KΩ Response timeOFF → ON 15ms or less ON → OFF 20ms or less Internal...
Page 29
29 Output module specifications Internal circuit and wiring diagram NX-Y16R: No varistor NX-Y16RV: Varistor Product nameRELAY output module Catalog numberNX-Y16R NX-Y16RV Number of output points 16 points Insulation method Photocoupler Rated load voltage 2A 250V AC, 2A 30V DC Response timeOFF → ON 10ms or less ON → OFF 10ms or less Life timeMechanical 30 million times Electric 200 thousand times External power supply 24V 150mA or less Surge protection N/A Varistor Internal current consumption (5V)...
Page 30
30 Wiring diagram Internal circuit Same as NX-Y16RV. NThe COM terminal of the connector has a short inside of the unit. NFor wiring method, See Terminal Block Type Module Wiring in Chapter 4. NUse separate commercial cable harness (NX-CBLRY) and Pin Type Assy (CPL8890) for external connection. Product nameRELAY output module Catalog numberNX-Y32RV Number of output points 32 points Insulation method Photocoupler Rated load voltage 1A 250V AC, 1A 30V DC Response timeOFF → ON 10ms or less ON → OFF 10ms...