Page 111
1-105 1. Specifications 7-11. Misoperation Alarm Indicators Alarm indicator lamps on the indoor unit indicate the error cause if the air conditioner fails to operate upon being switched on. The possible alarm indications are given in Table 1-9. Fig. 1-95 shows the location of the alarm lamps on the indoor unit. (See Table 1-9 and Fig. 1-95.) Table 1-9 Alarm (OPERATION(TIMER(STANDBYCause of Trouble lamp) lamp) lamp) S.C. errors* between the indoor unit’s controller (PCB) and the remote controller....
Page 112
1-106 1. Specifications CAUTION If the signal receiving unit is installed near a rapid-start or inverter type fluorescent lamp (neither one uses glow lamps), it may be impossible to receive signals from the wireless remote controller. To avoid signal interference from fluorescent lamps, install the receiving unit at least 6.6 ft. away from the lamps and install at a location where wireless remote controller signals can be received when the fluorescent lamps are on. 7-12. Separate Type Signal...
Page 113
1-107 1. Specifications When using the signal receiving unit on a wall with the front exposed, choose a wall surface that the signal receiving unit can be mounted on. (1) Insert a athead screwdriver into the slot on the lower side of the signal receiving unit and pry off the back case. (2) The wire routing at the signal receiving unit comes out of the upper case (thin portion at upper center) so use nippers or a similar tool to cut out a notch beforehand large enough for the remote control cable...
Page 114
1-108 1. Specifications 7-13. Electrical Wiring CAUTIONBe sure to do the wiring correctly (incorrect wiring will damage the equipment). Recommended wire diameter and allowable length for signal receiving unit wiring and its branch wiring: AWG #18, MAX 1,300 ft. 7-14. Test Run Switch (1) Remove the cover plate of the signal receiving unit. Set the “TEST RUN” switch of the dip switches to the ON position. (2) Press the ON/OFF operation button on the wireless remote controller. Wire joint (2 pcs. white,...
Page 115
1-109 1. Specifications 7-15. Misoperation Alarm Indicators A blinking lamp for other than the signal receiving unit lter shows that a problem has occurred in the unit, so make an inspection. (Refer to servicing information in the service manual, etc.) Also, if wired remote controller and dedicated service check lines (CV6380230938: service use) are available, then detailed error information can be obtained by connecting to the service connector as shown in the drawing. For information on how to...
Page 116
1-110 1. Specifications 7-16. Basic Wiring Diagram CAUTIONBe sure to do the wiring correctly (incorrect wiring will damage the equipment). Wiring procedure Carry out the wiring according to the above wiring diagram. Address setting is automatically executed after turning on the system. An indoor unit address is assigned to each indoor unit. Operation takes place successively at intervals of 1 second, by using combinations of the address setting of each unit. In case of using shielded wires for...
Page 117
1-111 1. Specifications 7-17. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a signal receiving unit (main unit). In this case, a signal receiving unit can be connected at any indoor unit. Group control using 2 signal receiving units It does not matter which of the 2 signal receiving units you set as the main controller.Wiring procedure Wire according to the diagram at left: Address setting is executed automatically when the outdoor unit...
Page 118
1-112 1. Specifications 7-18. Wiring System Diagram for Multiple Remote Controllers To operate 1 indoor unit with 2 signal receiving units set at different locations. CAUTIONCarry out the wiring correctly (incorrect wiring will damage the equipment). When installing multiple remote controllers This multiple system is used for operating the unit(s) at different positions. (A maximum of 2 signal receiving units can be installed.) Setting method To execute this control, make the setting according to the...
Page 119
1-113 1. Specifications 7-19. Test Run Procedure Wall mounted Type (K1 Type) 7-20. Check Items Before the Test Run (1) Turn ON the remote power switch at least 12 hours before the test run in order to charge the crankcase heater. (2) Fully open the service valves on the gas-tube and liquid-tube sides. (3) Set the sliding switches on the inside of the wireless remote controller cover to the correct settings for that model. After changing the settings, press the RESET hole. Check the “Check Items...
Page 120
1-114 1. Specifications 7-21. Preparing for the Test Run 7-21-1. Changing the room temperature sensor Room temperature sensors are installed inside the indoor unit and the wireless remote controller. Either room temperature sensor can be used. When “Unit Sensor” is indicated on the wireless remote controller’s LCD, the indoor unit sensor is operating as the room temperature sensor. To change to the remote control sensor, open the remote control cover and press the SENSOR button once. The “Unit...