Page 165
4-1. Meaning of Alarm Messages ......................................................................................... 4-2 4-2. Symptoms and Parts to Inspect ................................................................................... 4-5 4-3. Details of Alarm Messages ........................................................................................... 4-8 4-4. Table of Thermistor Characteristics ............................................................................ 4-14 4....
Page 166
4-2 4. Service procedures Remote controller is detecting error signal from indoor unitE01 E02 E10 E11 E14 E03 E08 E09 E04 E05 E06 E07 E15 E12 E16 E20 E17 E18 E31 L01 L02 L03 L04 L07 L08 L09 L10 L11 L13 Indoor unit is detecting error signal from remote controller (and system controller)Error in receiving serial communication signal (Signal from main indoor unit in case of group control) Auto address is not completed Outdoor system address, indoor system address, or indoor unit individual/main/sub setting...
Page 167
4-3 4. Service procedures P09 P01 P10 P03 P04 P05 P15 P19 P20 P22 P26 P29 P31 H01 F01 F02 F10 F04 F06 F07 F08 F12 F29Ceiling panel connection failure Indoor protection Fan protective thermostat Float switch Discharge temperature trouble High pressure switch or compressor motor thermal protector is activated. Open phase detected, AC power trouble No gas 4-way valve locked High cooling load Outdoor fan trouble Inverter compressor trouble (HIC PCB) Inverter compressor trouble (MDC) Simultaneous-operation...
Page 168
4-4 4. Service procedures (2) LED Indicator Messages on Outdoor Control PCB Power ON sequence 1. No communication from indoor units in system 2. Communication received from 1 or more indoor units in system 3. Regular communication OK (Capacity and unit quantity match)If it is not possible to advance to 3, repeats 1 → 2. At 3, changes to normal control. P03 Normal operation Automatic address setting in progress Automatic address setting alarm (E15) Automatic address setting alarm (E20) Automatic...
Page 169
4-5 4. Service procedures 4-2. Symptoms and Parts to Inspect Judgment condition Clear condition P03 P05 P04 P15 P19 P20 P22 P26 Remote controller alarm displayAlarm contentsJudgment and correction Abnormal discharge temperature Discharge temp. detected at or above the specified value.Stops when temp. exceeds 232 F.Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart1. Check refrigerant cycle...
Page 170
4-6 4. Service procedures Judgment condition Clear condition P29 F04 F06Alarm contentsJudgment and correction Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Current detection circuit trouble AC current value is high even when compressor is stopped.Inverter stops after alarm is detected. Alarm is output when inverter stops (pre-trip) consecutively 4 times.1. Stops immediately when restarted. Layer short in the compressor 2. Check inverter...