Page 191
6-3 6. Test run U1, K1, T1, F1 Type 6-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used. This test run manual describes primarily the procedure when using the wired remote controller. 6-3. Test Run...
Page 192
6-4 6. Test run 6-4. Items to Check Before the Test Run (1) (2)Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. Fully open the closed valves on the liquid tube and gas tube sides. 6-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer. Then press the button. • “TEST” appears in the LCD display during the test run. Temperature control is not possible when test run mode is engaged. (This mode places a...
Page 193
6-5 6. Test run Wired remote controller display Cause Correction Nothing is displayedNothing is displayed E 0 1 dis played E 0 2 displayed E 0 9 displayed E 1 4 displayed E 0 4 displayed E 0 6 di splayed E 1 5 displayed E 1 6 displayed E 2 0 di splayed P 0 5 displayed L 0 2 displayed L 1 3 displayed P 0 9 displayed L 0 7 displayed Indoor unit receiver lampOperating lamp is blinking. Standby lamp is blinking.Both the Operation lamp and Stan dby lamp are blinking together. Operation lamp...
Page 194
6-6 6. Test run 6-8. Examples of Wiring Diagrams Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) 1 212 0 L2 U1 RCU2 L1 U2U1 G 1 2 System address rotary switch (Set to “0” at the time of shipment.) Outdoor unit Indoor unit Wired remote controller WHTBLK (Optional) Remote controller wiring (Field supply) Ground Power supply Single-phase 230 / 208 V Inter-unit power line 230 / 208 V, 60 Hz Fig. 6-5 6...
Page 195
6-7 6. Test run 1 212 L2 U1 RCU2 L1 U2U1 G 1 2 12 L2 U1 RCU2 L1 U2U1 G 1 2 System address rotary switch (Set to “0”at the time of shipment.) Outdoor unit Indoor unit Wired remote controller WHTBLK (Optional) Remote controller wiring (Field supply)System address rotary switch (Set to “0” at the time of shipment.) Outdoor unit Indoor unit Remote controller crossover wiring for group control Ground Power supply Single-phase 230 / 208 V Inter-unit power line 230 / 208 V, 60 Hz Ground Power supply...
Page 196
6-8 6. Test run Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) ON 1 2 0 System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address DIPswitch OFFON 10s 20s 3 – 5HPOutdoorunit control PCB Fig. 6-7 System address No.System address 10s digit (2P DIP switch)System address 1s place (Rotary switch) 0 Automatic address (Setting at shipment = “0”) 1 (If outdoor unit is No. 1)“0” setting0 0 1 1 1 2 Both...
Page 197
6-9 6. Test run Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed. (1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible location on...