Page 171
4-7 4. Service procedures Judgment condition Clear condition F31 L02 L04 L07 L10 L13 E07 E06 E14 E15 E16 E20 E31 H01 Remote controller alarm displayAlarm contentsJudgment and correction Automatic recovery EEPROM trouble Reading/writing failure Recovery at power reset1. Check EEPROM (IC007). 2. Check outdoor unit control PCB. Mismatch of indoor and outdoor unit types (Espacio, Multi )Indoor unit judges that type does not match outdoor unit type.Recovery at power reset1. Check indoor unit EEPROM....
Page 172
4-8 4. Service procedures No No No No NoNo No No No Ye s Ye s Ye sYe s Ye s Ye s Ye s Ye s Ye s [Alarm “P29”] (MDC trouble) (1) Input power detection circuit trouble Compressor does not run. Breakdown Motor current detection circuit trouble Is power OK? Correct power line. Is current detection circuit wiring OK?Check and correct wiring. Are wiring and connector connections OK?Check and correct wiring. Is compressor OK? Ground fault?Replace compressor. Coil resistor short circuit? Coil open...
Page 173
4-9 4. Service procedures No No No NoNo No No Ye s Ye s Ye s Ye s Ye s Ye s Ye s Replace outdoor unit control PCB. (2) [Alarm “P26”] HIC PCB trouble)IGBT short-circuit protection on inverter control (IPDU) PCB Is power OK? Correct power line. Are circuit wiring, connector connections, and reactor connections OK? Correct. Has filter PCB RY001 or RY002 relay activated? Has filter PCB AC fuse blown? Replace filter PCB. Disconnect U.V.W. output terminal on HIC PCB and start operation. Does...
Page 174
4-10 4. Service procedures HIC +Between terminals Resistance HIC + HIC + HIC + HIC – HIC – HIC –HIC – U V W U V W Resistance 200 kΩ or more 300 kΩ or more 300 kΩ or more 300 kΩ or more 200 kΩ or more 200 kΩ or more 200 kΩ or more No Ye s Replace outdoor unit control PCB. (3) [Alarm “E31”] (communications trouble within unit)IGBT short-circuit protection Is “E31” displayed even after the power voltage is reset?Normal HIC-CH4872R (42 Type)HIC-CH2672R (26, 36 Type) 4...
Page 175
4-11 4. Service procedures No No No No Ye s Ye s Ye s Ye s (4) [Alarm P22]Outdoor unit fan motor drive circuit trouble Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB? Correct the connector connections. Disconnect connectors CN003 and CN004 from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily? Outdoor unit fan motor coil resistance is OK if it is as shown below. (1) Red – white: 30 – 40 Ω (2) White – black: 30 – 40 Ω (3) Black – red:...
Page 176
4-12 4. Service procedures No No Ye s Ye s Check the outdoor unit control PCB. Replace if PCB has failed. Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Are connectors CN020, 021, 022, 023, and 024 (TD, TO, C1, C2, and TS sensors) connected correctly to the outdoor unit control PCB? Correct the connector connections. Are the TD, TO, C1, C2, and TS sensor resistance* characteristics OK? Replace the TD, TO, C1, C2, or TS sensor. * Refer to “4-4. Table of Thermistor...
Page 177
4-13 4. Service procedures Sensor installation Sensor Sensor typeSensor Sensor type s s e r d d a s s e r d d a n o i t a c o l 00 Room temp. 05 – (temp. used for control)* 01 Remote controller temp. 06 Discharge temp. Indoor unit 02 Indoor intake temp. 07 – 03 Indoor heat exchanger temp. (E1 ) 08 – 04 Indoor heat exchanger temp. (E2 ) 09 – 0A Discharge temp. (TD ) 12 – – 3 1 – b 0 t n e r r u C 4 1 – C 0 (AC current) Outdoor unit 0d Intake temp. (TS ) 15 Outdoor electronic control valve position 0E...
Page 178
4-14 4. Service procedures Check Pin Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below. 1. Thermistor checks The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2. Discharge temp. (TD) Outdoor air temp. ( TO) Heat exchanger temp. (C1) Heat exchanger temp. (C2) Intake temp. (TS) ThermistorCheck results Normal Abnormal LED 1 and 2 OFF...
Page 179
5-1. Overview......................................................................................................................... 5-2 5-2. Functions ....................................................................................................................... 5-2 5-3. Normal Display Operations and Functions ................................................................. 5-3 5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures...
Page 180
5-2 5. Outdoor unit maintenance remote control 5-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings. This remote controller can be used for checking the outdoor...