Page 131
2-1 Room Temperature Control .......................................................................................... 2-2 2-2 Cold Draft Prevention (Heating Cycle) ........................................................................ 2-4 2-3 Automatic Fan Speed (Indoor Unit) ............................................................................. 2-5 2-4 Control Functions ......................................................................................................... 2-6 2-5 Outdoor...
Page 132
2-2 2. Processes and functions Fig. 1 (THERMO. OFF) (THERMO. ON)ROOM TEMP. THERMO. ON 5 MINUTES MORE THAN 5 MINUTES 3 MINUTES SET TEMP COMPRESSOR OUTDOOR FAN (H OR M) INDOOR FANF F O F F O F F O F F O 1 1. Refer to 2-4 Outdoor Fan Speed ControlMORE THAN 3 MINUTES MORE THAN 5 MINUTES N O N O N O N O N O N O SET SPEED T+2°F T–2°F . T °F BODY SENSOR 1133_THS_I THERMO. OFF Chart Summary and Explanations Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it...
Page 133
2-3 2. Processes and functions Fig. 2 THERMO. ON THERMO. ON +2°F F F O F F O 2 1. Refer to 2-4 Outdoor Fan Speed Control OFF SET SPEED N O N O N O ON (REVERSING CYCLE) ON TEMP. OPERATION REMOTE CONTROL SENSOR (Only for wireless remote controller) BODY SENSOR OFFOFF SET SPEED SET SPEED 3 SECONDSON OFF ONMORE THAN 3 MINUTES OFF ON OFFON OFF ON OFF OFF ON3 MINUTESMORE THAN 5 MINUTES 5 MINUTESTHERMO. ON THERMO. ON THERMO. ON THERMO. ON 2. Refer to 2-2 Cold Draft Prevention (Heating)...
Page 134
2-4 2. Processes and functions Fig. 3 92 88 81 77 50 SET FA N SPEEDAUTO OR H M L LL LL/OFF LL L L LLL LL/OFF LL L M M LL LL/OFF LL L M HMAX. 6 MINUTES “STANDBY” INDICATOR INDOOR UNIT COIL TEMP. E2 (°F) LL= Very low speed L= Low speedM= Medium speed H= High speed “STANDBY” APPEARS 1135_THS_I Chart Summary and Explanations The main idea of this chart is to show that the indoor fan speed increases and gets closer to the set fan speed as the coil temperature E2 rises. The indoor unit fs coil temperature...
Page 135
2-5 2. Processes and functions Fig. 4 INDOOR FAN SPEED L H MMH 1923_M_S ROOM TEMP. (deg) SET TEMP.+3 +2 +1 H M: High : MiddleL: Low Chart Explanations and notes When the fan speed changes, it keeps the speed step for at least 3 minutes, even if the temperature changes to another speed step during the time. Fig. 5 INDOOR FAN SPEED H L MMH 1924_M_S ROOM TEMP. (deg) SET TEMP. –2 –4 H M: High : MiddleL : Low Chart Explanations and notes When the fan speed changes, it keeps the speed step for at least 1...
Page 136
2-6 2. Processes and functions 124 142 2-4 Control Functions Electronic control valve control Opening of the electronic control valve is controlled so that the appropriate operating conditions are maintained, based on the signal from each sensor (discharge temperature [TD], intake temperature [TS], outdoor heat exchanger temperature [C1], and indoor heat exchanger temperature [E1, E2]). Discharge temperature release control (1) This control lowers the operating frequency of the compressor when electronic...
Page 137
2-7 2. Processes and functions 36 (36, 48 types) Overcurrent protection control (1) If the overcurrent protection circuit detects abnormal current, the compressor is stopped. (Error count = 1.) The compressor then restarts after 3 minutes. (2) If compressor start/stop is repeated 4 times (error count = 4), alarm P26, P29 or H01 (count = 2 in this case only) occurs. Operation stops and does not restart. Current release value shift control (1) This control is intended to improve compressor reliability by...
Page 138
2-8 2. Processes and functions 1 2 3Defrost control Defrost sequence Heating operation (25-minute mask) Frost detection Defrost start (reverse cycle defrost) Defrost in progress Defrost cancel Start-up operationOperating frequency: 61.8 Hz Outdoor unit fan: OFF Electronic control valve: step 300 4-way valve: OFF Indoor unit fan: OFF Defrost control (1) Frost detection 1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start) 2. Outdoor air temperature is 7°F or...
Page 139
2-9 2. Processes and functions Fan motor plug (CN004)EEPROM IC MDC Heat exchanger temperature (C2) sensorHeat exchanger temperature (C1) sensorSuction temperature (TS) sensor Outdoor air temperature (TO) sensor Compressor discharge temperature (TD) sensor Refrigerant recovery switch (S005) Quiet mode plug (CN028) EXCT plug (CN026) Automatic address setting switch (S001) Snowfall sensor Cooling test Test pin (CN036) Operation circuit fuse (F002) LED 1, 2 Serial 1 plug Terminal plug (CN015) Serial 2...
Page 140
2-10 2. Processes and functions Push-button switch (black): Automatic address setting switch If the system address switch (S002: set to 0 at time of shipment) setting is other than 0 (central control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit. During automatic address setting, the 2 LEDs (red) on the outdoor unit control PCB blink alternately. (Pressing this switch again stops automatic address...