Page 81
1-75 1. Specifications 5. SELECTING THE INSTALLATION SITE 5-1. Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near inverter lamps which may affect the performance of the unit. locations near heat sources which may affect the performance of the unit. locations where external air may enter the room directly. This may cause “sweating” on the air dis- charge ports, causing them to spray or drip....
Page 82
1-76 1. Specifications 6. HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette Type (U1 Type) 6-1. Suspending the Indoor Unit This unit uses a drain pump. Use a level gauge to check that the unit is level. 6-2. Preparation for Suspending (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs. 1-12 and 1-13), by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely and safely suspended. (2) Follow...
Page 83
1-77 1. Specifications 6-3. Placing the Unit Inside the Ceiling (1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 1-15) The size of the opening for the indoor unit can be confirmed by attaching the full-scale installation diagram beneath the unit. (Fig. 1-15) Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring...
Page 84
1-78 1. Specifications 6-4. Installing the Drain Piping (1) Prepare standard hard PVC pipe for the drain and use the supplied drain hose and hose band to pre- vent water leaks. The PVC pipe must be purchased separately. The transparent part allows you to check drainage. (Fig. 1-17) (2) After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe. (Fig. 1-18) NOTE Ensure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps....
Page 85
1-79 1. Specifications 6-5. Checking the Drainage After wiring and piping are completed, use the follow- ing procedure to check that the water will drain smooth- ly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water. (1) Take off the tube cover and through the opening, slowly pour about 0.3 gal of water into the drain pan to check drainage. (2) Do Test Run to check the drainage after complet- ing installation. When performing Test Run, refer to the installation...
Page 86
1-80 1. Specifications Ceiling Panel 6-6. Before Installing the Ceiling Panel (1) Remove the air-intake grille and air filter from the ceiling panel. (Figs. 1-24 and 1-25) (a) Remove the 2 screws on the latch of the air- intake grille. (Fig. 1-24) (b) Press on the 2 latches of the air-intake grille with your thumbs in the direction of the arrow to open the grille. (Fig. 1-24) (c) With the air-intake grille open about 45°, remove the safety cord (hook on the grille side). (Fig. 1-25) (d) Pull...
Page 87
1-81 1. Specifications 6-7. Installing the Ceiling Panel (1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit. NOTE The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size. Confirm that the catches are correctly matched between the ceiling panel and the indoor unit body. (2) Next, check to see that the ceiling panel is prop- erly aligned with the seamline of the ceiling. If it is not,...
Page 88
1-82 1. Specifications 6-9. Duct for Fresh Air There is a duct connection part on side of the indoor unit. (Fig. 1-27) (1) Accessories Check that the following parts are in the box when unpacking. (2) Installation Fit the duct connection box into the rectangular hole of air-intake plenum with the accessory screws. (M4 × L1/2, 4 pcs) (c) Installing the indoor unit Install the indoor unit to the ceiling. (Install the indoor unit according to instructions enclosed with the outdoor unit.)...
Page 89
1-83 1. Specifications (d) Installing the ceiling panel Attach the ceiling panel to the air-intake plenum. Drawing the panel downwards sets the panel in position temporarily with the panel catch (at 2 locations). Remove the socket cover of the air-intake plenum and pass the 8P sockets through it. (Fix the panel lead wire to air-intake plenum side clamper.) Connect the 3P socket (white) and 2P socket (green) to the other side of the 3P socket (white) and 2P socket (green) respectively. Reattach the...
Page 90
1-84 1. Specifications Wall Mounted Type (K1 Type) 6-10. Removing the Wall Fixture from the Unit Remove the set screws and take off the rear panel. (Fig. 1-30) NOTE Tubing can be extended in 3 directions as shown in Fig. 1-31. Select the direction that provides the shortest run to the outside unit. 6-11. Selecting and Making a Hole (1) Remove the rear panel from the indoor unit and place it on the wall at the location selected. Make sure the unit is horizontal using a level gauge or tape measure...