Page 71
1-65 1. Specifications 3. SELECTING THE INSTALLATION SITE 3-1. Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 1-3) damp, humid or uneven locations DO: choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly. allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 1-4) use lug bolts or equal to bolt down unit, reducing vibration and noise. if cooling operation is...
Page 72
1-66 1. Specifications 3-2. Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: it is difficult to keep a space of min. 20 between the air discharge outlet and an obstacle. the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by. Refer to Fig. 1-7. 3-3. Installing the Unit in Heavy Snow Areas In locations with strong wind, snow-proof ducting should be fitted and direct exposure to the wind should be avoided as much...
Page 73
1-67 1. Specifications 3-5. Dimensions of Wind Ducting Reference diagram for air-discharge chamber ( eld supply) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ƒAir discharge chamber „Air discharge chamber (base) For U-42PE(S)1U6 unit ƒUnit front, air discharge chamber „Unit left side, air discharge chamber …Unit right side, air discharge chamber †Reinforcement brackets, 4 locations Note: In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the...
Page 74
1-68 1. Specifications Dimensions of Outdoor Unit with air-discharge chamber ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 13-3/8 2-17/32 21-13/161/2 6-11/16 25-31/324-5/16 2 / 1 2 / 1 14-31/32 15-15/16 19/322 3 / 5 2 2 3 / 5 2 13/32 Wind direction Wind direction Wind direction Wind direction Wind direction 37 30-23/32 23/32 9-7/8 21-5/8 4-1/16 5-3/16 Wind direction Unit: inch 4-5/16 25-31/32 6-11/16 1/2 1/2 13-3/8 15-15/16 14-31/32 13/32 19/3225/32 25/32 1/2 2-11/36 21-13/32 11 - 1 3...
Page 75
1-69 1. Specifications Reference diagram for air-discharge chamber ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation (2) Multiple-unit installation Installation in lateral rows Installation in front-rear rows...
Page 76
1-70 1. Specifications 3-6. Dimensions of Snow Ducting Reference diagram for snow-proof vents ( eld supply) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ƒUnit top, snow-proof vent „Unit left side …Unit right side †Unit reverse side ‡Unit reverse side ˆUnit sides, reinforcement brackets for snow-proof vent For U-42PE(S)1U6 unit ƒUnit top, snow-proof vent „Unit left side …Unit right side †Unit reverse side ‡Unit reverse side ˆUnit sides, reinforcement brackets for snow-proof vent 25-13/32 17-15/32...
Page 77
1-71 1. Specifications Dimensions of outdoor unit with snow-proof vents ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 11-57/64 16-47/6415-15/16 14-61/64 25/64 19/3225/32 30-5/64 25-25/64 7-3/64 3/4 30-45/64 37-1/64 Wind direction Wind direction Wind direction Wind direction Wind direction Wind direction Unit: inch 11-57/64 28-13/16 Wind direction Wind direction Wind direction Wind direction Wind direction Wind direction 48-27/64 47-19/32 37-1/64 24-7/8 15-15/1614-61/64 25/64 19/3225/32...
Page 78
1-72 1. Specifications Reference diagram for snow-proof vents – 1 Space requirements for setting – (1) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 ] t i n u f o t n o r f e h t o t e l c a t s b O [ ] t i n u f o r a e r e h t o t e l c a t s b O [ : n e p o s i p o T : n e p o s i p o T Top is blocked by an obstacle: Top is blocked by an obstacle: Unit: inch Min. C Min. E Min. FMin. E Min. EMin. B Min. A Min. D Min. G (1) Single-unit installation (3) Multiple-unit...
Page 79
1-73 1. Specifications Reference diagram for snow-proof vents – 2 Space requirements for setting – (2) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. [Installation in front-rear rows] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no...
Page 80
1-74 1. Specifications 4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Installing the Outdoor Unit Use concrete or a similar material to create the base, and ensure good drainage. Ordinarily, ensure a base height of 2. or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 6. or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.) Refer to the...