Page 41

1-35
1. Specifications
1-3 Other Component Specifications
Outdoor Unit
U-26PE1U6, U-26PS1U6 . o N   L E D O M
Thermistor (Coil sensor) : TH2 to 5
Coil resistance kΩ14°F:23.7 , 50 °F : 9.7
23°F:18.8 , 68 °F : 6.5
32°F:15.0 , 86 °F : 4.4
41°F : 12.1 , 104 °F : 3.1
113°F : 2.6
Thermistor (Comp. discharge gas sensor) : TH6
Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1
158°F : 9.7 , 212 °F : 3.8
167°F : 8.2 , 230 °F : 2.8
176°F : 7.0 , 248 °F : 2.2
185°F : 5.9 , 266 °F: 1.7
Solenoid coil or 4 way valve...

Page 42

1-36
1. Specifications
1-3 Other Component Specifications
Outdoor Unit
U-36PE1U6, U-36PS1U6 . o N   L E D O M
Thermistor (Coil sensor) : TH2 to 5
Coil resistance kΩ14°F:23.7 , 50 °F: 9.7
23°F:18.8 , 68 °F: 6.5
32°F:15.0 , 86 °F: 4.4
41°F : 12.1 , 104 °F: 3.1
113°F: 2.6
Thermistor (Comp. discharge gas sensor) : TH6
Coil resistance kΩ140°F : 13.8 , 194 °F: 5.1
158°F : 9.7 , 212 °F: 3.8
167°F : 8.2 , 230 °F: 2.8
176°F : 7.0 , 248 °F : 2.2
185°F : 5.9 , 266 °F: 1.7
Solenoid coil or 4 way valve
G 2 U 2 0   -...

Page 43

1-37
1. Specifications
U-42PE1U6, U-42PS1U6 . o N   L E D O M
Thermistor (Coil sensor) : TH2 to 5
Coil resistance kΩ14°F:23.7 , 50 °F: 9.7
23°F : 18.8 , 68 °F : 6.5
32°F : 15.0 , 86 °F: 4.4
41°F : 12.1 , 104 °F : 3.1
113°F: 2.6
Thermistor (Comp. discharge gas sensor) : TH6
Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1
158°F : 9.7 , 212 °F: 3.8
167°F : 8.2 , 230 °F : 2.8
176°F : 7.0 , 248 °F : 2.2
185°F : 5.9 , 266 °F : 1.7
Solenoid coil or 4 way valve
G 1 U 4 0   -   F T S e v l a v   y a w   4
) y l n o...

Page 44

1-38
1. Specifications
1-4 Dimensional data
Indoor unit : 4-Way Cassette Type
26 Type
33-27/323-15/16 30-9/16
19-11/16
19-11/16
12-1/8 1-3/16
4-7/8
15/32
15/32
1-7/833-27/32
32-9/32 (Ceiling opening)
Grille center
29-13/16 (Suspention bolt pitch)
14-1/2 1
Air intake grille
Air outlet
Refrigerant liquid line
(3/8) Flare connection
Refrigerant gas line
(5/8) Flare connection
Drain connection
Power supply entry (conduit size : 1/2)
For discharge duct
Suspention bolt mounting
For fresh air intake
X-view X...

Page 45

1-39
1. Specifications
1-4 Dimensional data
Indoor unit : 4-Way Cassette Type
36, 42Type
45-9/32 41-31/32
31-3/32
19-11/1613-5/16 1-3/16
4-7/8
15/32
15/32
1-7/833-27/32
32-9/32 (Ceiling opening)
Grille center
29-13/16 (Suspention bolt pitch)
20-3/16 1
Air intake grille
Air outlet
Refrigerant liquid line (3/8
) Flare connectionRefrigerant gas line (5/8) Flare connectionDrain connection
Power supply entry (conduit size : 1/2)
For discharge duct
Suspention bolt mounting
For fresh air intake
X-view X...

Page 46

1-40
1. Specifications
1-4 Dimensional data
Dimension : inchRefrigerant liquid line (3/8) Flare connection
Refrigerant gas line (5/8) Flare connection
Drain hose OD 45/64
Drain and wiring port (3-5/32) 
Indoor unit : Wall Mounted Type
1
4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 

Page 47

1-41
1. Specifications
1-4 Dimensional data
Indoor unit : Ceiling Type
26 Type
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8) Flare connection
Refrigerant gas line (5/8) Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16 hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2)...

Page 48

1-42
1. Specifications
1-4 Dimensional data
Indoor unit : Ceiling Type
36, 42 Type
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8) Flare connection
Refrigerant gas line (5/8) Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (
ø3-15/16 hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size...

Page 49

1-43
1. Specifications
1-4 Dimensional data
Indoor unit : Low Silhouette Duct Type
26 Type
Refrigerant liquid line (3/8) Flare connectionRefrigerant gas line (5/8) Flare connectionUpper drain port (O.D. 1-1/4)
Bottom drain port (O.D. 1-1/32)
Suspension lug
Power supply inlet (conduit size 1/2)
Fresh air intake port (
ø5-29/32)
Flange for the flexible air outlet duct (ø7-7/8)
Tube cover 
Electrical component box
Flange for the air intake duct
(option or field supply)91011
1914_U_I
(Suspension bolt pitch)...

Page 50

1-44
1. Specifications
1-4 Dimensional data
Indoor unit : Low Silhouette Duct Type
36 Type
Refrigerant liquid line (3/8) Flare connection
Refrigerant gas line (5/8) Flare connection
Upper drain port (O.D. 1-1/4)
Bottom drain port (O.D. 1-1/32)
Suspension lug
Power supply inlet (conduit size 1/2)
Fresh air intake port (
ø5-29/32)
Flange for the flexible air outlet duct (ø7-7/8)
Tube cover 
Electrical component box
Flange for the air intake duct
(option or field supply)91011
1915_U_I
(Suspension bolt...