Page 41
1-35 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-26PE1U6, U-26PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F : 9.7 23°F:18.8 , 68 °F : 6.5 32°F:15.0 , 86 °F : 4.4 41°F : 12.1 , 104 °F : 3.1 113°F : 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1 158°F : 9.7 , 212 °F : 3.8 167°F : 8.2 , 230 °F : 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F: 1.7 Solenoid coil or 4 way valve...
Page 42
1-36 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-36PE1U6, U-36PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F: 9.7 23°F:18.8 , 68 °F: 6.5 32°F:15.0 , 86 °F: 4.4 41°F : 12.1 , 104 °F: 3.1 113°F: 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F: 5.1 158°F : 9.7 , 212 °F: 3.8 167°F : 8.2 , 230 °F: 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F: 1.7 Solenoid coil or 4 way valve G 2 U 2 0 -...
Page 43
1-37 1. Specifications U-42PE1U6, U-42PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F: 9.7 23°F : 18.8 , 68 °F : 6.5 32°F : 15.0 , 86 °F: 4.4 41°F : 12.1 , 104 °F : 3.1 113°F: 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1 158°F : 9.7 , 212 °F: 3.8 167°F : 8.2 , 230 °F : 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F : 1.7 Solenoid coil or 4 way valve G 1 U 4 0 - F T S e v l a v y a w 4 ) y l n o...
Page 44
1-38 1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 26 Type 33-27/323-15/16 30-9/16 19-11/16 19-11/16 12-1/8 1-3/16 4-7/8 15/32 15/32 1-7/833-27/32 32-9/32 (Ceiling opening) Grille center 29-13/16 (Suspention bolt pitch) 14-1/2 1 Air intake grille Air outlet Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Drain connection Power supply entry (conduit size : 1/2) For discharge duct Suspention bolt mounting For fresh air intake X-view X...
Page 45
1-39 1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 36, 42Type 45-9/32 41-31/32 31-3/32 19-11/1613-5/16 1-3/16 4-7/8 15/32 15/32 1-7/833-27/32 32-9/32 (Ceiling opening) Grille center 29-13/16 (Suspention bolt pitch) 20-3/16 1 Air intake grille Air outlet Refrigerant liquid line (3/8 ) Flare connectionRefrigerant gas line (5/8) Flare connectionDrain connection Power supply entry (conduit size : 1/2) For discharge duct Suspention bolt mounting For fresh air intake X-view X...
Page 46
1-40 1. Specifications 1-4 Dimensional data Dimension : inchRefrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Drain hose OD 45/64 Drain and wiring port (3-5/32) Indoor unit : Wall Mounted Type 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
Page 47
1-41 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling Type 26 Type Drain connection Drain connection for left side Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (ø3-15/16 hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2)...
Page 48
1-42 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling Type 36, 42 Type Drain connection Drain connection for left side Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing ( ø3-15/16 hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size...
Page 49
1-43 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct Type 26 Type Refrigerant liquid line (3/8) Flare connectionRefrigerant gas line (5/8) Flare connectionUpper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2) Fresh air intake port ( ø5-29/32) Flange for the flexible air outlet duct (ø7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)91011 1914_U_I (Suspension bolt pitch)...
Page 50
1-44 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct Type 36 Type Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Upper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2) Fresh air intake port ( ø5-29/32) Flange for the flexible air outlet duct (ø7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)91011 1915_U_I (Suspension bolt...