Home > Panasonic > Air Conditioner > Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

Here you can view all the pages of manual Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.

Page 51

 1. The main power is turned on while the transmission
wires between the indoor unit and the outdoor unit are
not connected (open circuit at section A).
Symptom:
Operation of indoor unit No. 1 and indoor unit No. 3 is
possible.
However, “CHECK” flashes in the remote control unit
display for 3-5 minutes after the main power is turned
on.
 
    − 
− −  − 
Remote control. . . “CHECK” flashes.
 
    − 
− −  − 
Indoor unit No. 2 . . . LED2 on the printed circuit
board flashes (both master and slave units)....

Page 52

 1. Automatic address setting (no need to have dip-switch set)
If the wiring connected properly as above example, the address is set automatically by the main powersupply. An indoor unit
with remote control will be set as the master. If the power source is installe d to indoor units and outdoor separately, turn on the
switch as the following procedure: outdoo r unit, indoor unit with control, and other indoor units.
When theslave units do not operate (when address cannot be set)
Important: The address...

Page 53

 1. Automatic address setting (no need to have dip-switch set)
If the wiring connected properly as above example, the AC numbe rs are set automatically by the main powersupply . An indoor
unit with remote control will be set as the master.
If the power source is installe d to indoor units and outdoo r separately, turn on the switch as the following procedure: outdoo r
unit, indoor unit with controller, and other indoor units. The AC numbe r will be set at random.
 2. Manua l address setting (by...

Page 54

Procedures of deleting memory attwincontrol system
Procedure of deleting memory at group control system  1. Set the “OFF” position for main power supply switch.
 2. Set the “ON” position for No. 8 pin of dip switch (DSW1) on indoor unit P.C. board.
 3. Take main power supply switch “ON” for one minute, and then main power supply switchoff.
 4. Set the “OFF” position for No. 8 pin of dip switch (DSW1).
 1. Set the “OFF” position for main power supply switch.
 2. Set the “ON” position for No. 1 pin to No....

Page 55

Emergencyoperation
 
    • 
• •  • 
Emergency operation of outdoor unit
Emergency operation can be carried out by setting the
DSW1 switch on the printed circuit board inside the
outdoo r unit to the EMERGENCY position. However,
emergency operation is only carried out when an
abnormality is detected by the indoor/outdoor
temperature thermistors.
The resistance values of each thermistor are measured
as shown in the table below to determine if there is an
abnormality.
Thermistor resistance table
Temperatu...

Page 56

25 CONTROL
25.1. Description of basic Functions
25.1.1. Cooling mode operation time chart
(*1)
Outdoor unit fan start control during cooling
At the start of cooling mode and drying mode operation, the outdoo r unit heat exchan ger outlet temperature is detected in order
to set the fan speed.
Operation is carried out at the fan speed detected for 30 seconds.
After 30 seconds, the heat exchan ger outlet temperature is detected and the outdoo r unit fan speed is changed automatically .
(*2)
Cooling low...

Page 57

25.2. Freezing prevention control
 1. Operation
During cooling mode operation, after 9 minutes have passed since the compressor turned on, the outdoor units stops operating
when the temperature detected by the indoor unit pipe temperature sensor is 2°C or lower.
The indoor unit continues operating at the fan speed set by the remote control unit. (The remote control unitdisplay does not
change.)
 2. Cancelling
This control is cancelled when the temperature detected by the indoor unit pipe temperature...

Page 58

(*2)
Outdoor unit fan control during heating mode operation
Under conditions when the compressor is on during heating mode operation (except during defrosting and when the liquid bypass
valve is on), the outdoor unit fan is controlled by means of input (CN2) indicating whether the contact of the heating pressure switch
on the outdoor unit circuit board is open or closed. (At the start of heating mode operation, the fan operates at HI speed.)
25.4. Hot starting
1. When heating mode operation starts
 1....

Page 59

2. When defrosting is complete
 1. Start
Hot start control commences when defrosting is complete.
 2. Operation
PREHEAT appears on the remote controldisplay . (Other display s remain unchanged.)
At the indoor unit, the indoor unit fan stops. In additio n, during hot starting, the louvre stays at the horizon tal position (angle
0°).
 3. Cancelling
Hot starting is cancelled when the temperature detected by the indoor unit pipe temperature sensor is 18°C or higher, or
after a maximum 1 minute has passed...

Page 60

25.6. Excess heat dissipation for indoor unit
The indoor unit fan continues operating for 30 seconds after heating mode operation turns off in order to dissipa te excess heat.
 1. Whenheating mode operation has stopped
(LOWoperation for 30 seconds)
 2. Whenoperation is set to a mode other than heating by means of the OPERATION MODE switch
 3. If operation starts again during the 30 seconds mentioned in (1) above
(The fan operates at LOW speed for the remainder of the 30 seconds in (1), and then hot start...
Start reading Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

Related Manuals for Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

All Panasonic manuals