7 OPERATING INSTRUCTION
7.1. Wired Remote Control
Name and function of each part
22 

Page 23

23 

Page 24

8 REFRIGERATION CYCLE
8.1. Heating Model
CS-W50BD3P / CU-W50BBP8
8.2. Cooling Only Model
CS-W50BD3P / CU-V50BB P8
24 

Page 25

9 OPERATION RANGE
The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases
must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher
than 85% of the rated voltage.
Power Supply
Model
CU-Unit Main PowerApplicable Voltage
Phase, VoltsHzMaximumMinimum
W50BBP8 V50BBP83N~38050418342
3N~40050440360
3N~41550457374
Indoor and Outdoor Temperature
Q
QQ Q
Coolingonly type
Model 50Hz ... V50BB...

Page 26

Correction of cooling and heating capacities according to
the connecting pipe length.
The data of cooling capacities (marked on the name plate)
are based on 7.5 metres connecting pipe and horizontal
installation.
(Cooling)
Equivalent Length = actual pipe length +
number of elbow x ELE
ELE : equivalent length ofelbow.
10.2. REFRIGERANT ADDITIONAL
CHARGE
 
    • 
• •  • 
The piping length exceeds 30 metres.
APPLICABLE FOR ALLMODELS
Before shipment, this air conditioner is filled with the rated
amoun t of...

Page 27

10.3. Piping installation by existing piping
Q
Coolingonly type(50Hz)
Model NameStandard piping specification
Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length
(m)Additional gas volume (g/m)
CU-V50BBP89.5219.053050
Q
Heat pumptype(50Hz)
Model NameStandard piping specification
Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume
(g/m)
CU-W50BBP89.5219.053050
Attention
 
    • 
• •  • 
Please never decrease the gas piping size. (It causes the breakdown of...

Page 28

11 OPERATING CHARACTERISTIC
HEAT PUMPMODEL
ModelMain PowerCompressor MotorIndoor UnitOutdoor UnitElectrical Data (50Hz)
SourceFan MotorFan MotorR.CIPT
VoltageFrequencyS.C.R.C.(A)IPT(kW)R.C.IPTR.C.IPT(A)(kW)
(V)(Hz)(A)COOL / HEATCOOL / HEAT(A)(kW)(A)(kW)COOL / HEATCOOL / HEAT
CS-W50BD3P38050698.57 / 8.574.94 / 5.040.910.190.990.229.20 / 9.205.35 / 5.45
CU-W50BBP840050698.55 / 8.554.91 / 5.010.930.211.020.239.20 / 9.205.35 / 5.45
41550698.53 / 8.534.88 / 4.980.960.221.040.259.20 / 9.205.35 / 5.45
COOLING...

Page 29

12 FAN PERFORMANCE
Fan Performance
ModelCS-W50BD3P
External Static PressureFan speedCurrent (A)Power Consumption
(kW)Power Factor (%)RPM (r / min)Air Volume (m3 / min)
69Pa (7mmAq)Hi1.210.2797.0136040
H59Pa (6mmAq)Me1.030.2397.1123035
49Pa (5mmAq)Lo0.920.2094.5111030
49Pa (5mmAq)Hi1.150.2698.3127040
L39Pa (4mmAq)Me1.020.2398.0114035
29Pa (3mmAq)Lo0.900.2096.6100030
O
OO O
CS-W50BD3P
Fan Performance Curve
29 

Page 30

13 SAFETY DEVICE
 
    • 
• •  • 
INDOOR UNIT
Indoor unitModelCS-
W50BD3P
For fan motor protection
InternalOFF°C135
Protector (49F)ON°C87
For control protection
FuseCUTA3.15
 
    • 
• •  • 
OUTDOOR UNIT
Outdoor unitHeat
pump
model50HzCU-
W50BBP8
Cooling
only
model50HzCU-
V50BBP8
For refrigerant cycle
High pressureOFFMPa3.1
switch (63H1)ONMPa2.3
For compressor
Over current protection
Heat pump
modelOFFA15
Cooling
only modelOFFA 50Hz15
RESET-Automatic
Discharge temp.
protection
Discharge temperature...