18.4. Wiring
Whenboth indoor and outdoor unit draw power
(Example: 3 Phase power supply model)
When only theoutdoor unit draws power
41 

Page 42

19 WIRING MISTAKE PREVENTION
Improved quality of installation work through adoption of an “Connection error prevention” circuitwhichpreven ts wiring
mistakes
Conne ction errors with the control wires and the power supply wires will not only contribute to burning-out of the control circuit
board, but can also cause large-scale working losses and affect reliability. If a circuit board with a “Connection error prevention”
circuit is used, the relay will not operate if the wires have been connected...

Page 43

20.1. Test operation
 
    • 
• •  • 
Always be sure to use a properly-insu lated tool to operate
the switch on the circuit board. (Do not use your finger or a
metallic object).
 
    • 
• •  • 
Never turn on the power supply until all installa tion work has
been completed.
 
    • 
• •  • 
Turn on the circuit breaker before test operation extends
past 6 hours.
(The crankcase heater will become energized, which will
warm the compressor and prevent liquid compression.)
 
    • 
• •  • 
For three-phase...

Page 44

20.3. Test operation using the wired remote control
44 

Page 45

45 

Page 46

O
OO O
Self-diagnosis error code table
46 

Page 47

21 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH
21.1. Energy save setting
Open the cover remote control unit and confirm the presence of the [ RP1] marking.
Energy save setting method should be different for with [ RP1] marking and without [RP1] marking.
47 

Page 48

22 GROUP CONTROL
1 Setting group for 1 remote control unit
 
    • 
• •  • 
W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group.
 
    • 
• •  • 
During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling only
units.)
 
    • 
• •  • 
Do not mix manua l settings and automatic settings. (Manual settings take priority.)
 
    • 
• •  • 
The master unit and slave units can all be centrally...

Page 49

If test operation does not proceed correctly
Carry out test operation after approximately 6 hours have passed
since the power was turned on (crankcase heater is energized). If
operation is started by using the remote control within 1 minute of
turning on the power, the outdoor unit settings will not be made
correctly and correct operation will not be possible.
If the following symptoms occur after turning on the power,
check the wiring connections once more.
 
    • 
• •  • 
For standard installation...

Page 50

 1. The main power is turned on while the transmission
wires between the indoor unit(s) are not connected
(open circuit at section A)
Symptom:
Nothing abnormal appears on the remote control
display . If operation is then started in this condition, the
combination of the 43BB outdoo r unit and the 40U
indoor unit (master unit) will cause abnormal operation
to occur.
↓
If operation continues, an abnormality will occur on the
refrigeration cycle and operation will stop.
 
    − 
− −  − 
Remote control. . ....