14 COMPONENT SPECIFICATION
Compressor
ModelsHeat pump
model50HzCU-W50BBP8
Cooling only
model50HzCU-V50BBP8
60Hz-
Compressor ModelR68KCE-TFD
Compressor Type
No. of CylindersSCROLL
1
Revolutionr/min.2,900
Piston Displacementm3/h16.18
Motor Type
Direct on-line StartingStarting Method
Rated OutputkW4.1
Poles
Insulation Glass2
E
Oil TypeMMMAPOE
ChargeL1.8
Evaporator
ModelsCS-W50BD3P
Tube Material
Outer Diametermm9.52
Thicknessmm0.36
Row3
No. of Tubes/Row10
Fin Material
Thicknessmm0.115
Fin PitchNo./inch12
Fin...

Page 32

Condenser
ModelsHeat pump modelCU-W50BBP8
Cooling only modelCU-V50BBP8
Tube MaterialCopper tube
Outer Diametermm9.52
Thicknessmm0.3
Row2
No. of Tubes/Row46
Fin MaterialAluminum
Thicknessmm0.105
Fin PitchNo./inch14
Fin SurfaceX-Louvre-fin
Total Face Aream21.05
Fan
TypePropeller Fan
No.of /Unit2
Fan Motor
Starting MethodDirect on-line Starting
Rated OutputkW0.055 X 2
Poles6
PhaseSingle-Phase
Insulation ClassE
32 

Page 33

15 CAPACITY AND POWER CONSUMPTION
Q
QQ Q
PERFORMANCE DATA
COOLING PERFORMANCE
ModelCooling capacities are based conditions.
CS-W50BD3POIndoor temp. 27°C D.B. 19°C W.B.
OOutdoor temp. 35°C D.B.
OStandard air volume 40 m
3/min
OExternal Static Pressure (49Pa)Cooling capacity
12.5kW
EnteringTemperatu re Air Entering Condenser (°C D.B.)
Air25°C30°C35°C40°C45°C
Temperatu reTCSHCIPTTCSHCIPTTCSHCIPTTCSHCIPTTCSHCIPT
D.B.W.B.kWkWkWkWkWkWkWkWkWkWkWkWkWkWkW...

Page 34

16 DISCHARGE AND SUCTION PRESSURE
16.1. SATURATION TEMPERATURE OF DISCHARGE AND SUCTION
PRESSURE
O
OO O
Commonness TO ALL THE MODELS
O
OO O
SATURATIONTEMPERATURE OF DISCHARGE AND SUCTION PRESS URE
*For intake temperature, consult the pressure - Enthalpy Table (R407C) at the end.
34 

Page 35

17 SOUNDDATA
35 

Page 36

36 

Page 37

18.1.1. Operation
 
    • 
• •  • 
Simultaneous air conditioning of wide spaces and corners is
possible. Indoor units with different horsepower can even
be used in combination.
 
    • 
• •  • 
Master units and slave-units can be set automatically in twin
systems. No address setting is necessary.
 
    • 
• •  • 
Multiple indoor units can be operated simultaneousl y with a
single remote control unit. Note that individual operation is
not possible.
18 TWIN OPERATION
18.1. TWIN
(Twinoperation setting)...

Page 38

Function
Automatic address setting fortwinsystem
Procedure:Turn on the power supply for the indoor and outdoor units.
Operation:Automatic address setting will start 10 to 30 seconds after the power supply is turned on, and will be completed after about 1
minute.
If the power supplies for the indoor unit and outdoor unit cannot be turned on at the same time, turn on the power supply for the
outdoor unit, the indoor unit which is connected to the remote control, and then the other indoor units in that...

Page 39

Procedure:Press the ADDRESS RESET switch SW3 (push button switch) on the outdoor unit circuit board continuously until LEDs 2 to 8 on
the outdoor unit circuit board are all illuminated (takes approx. 3.5 seconds).
Operation:The outdoor unit will reset the addresses for the indoor units which it is connected to, and will send an instruction to carry out
automatic address setting again. If the indoor unit DIP switches have not been manually set for twin address setting, the indoor
units receive this...

Page 40

 
    • 
• •  • 
The branch pipe should be horizon tal to or perpendicular to the indoor unit.
O
OO O
Installing branch pipes
18.3. Refrigerant charging
 
    • 
• •  • 
For twin systems
The pipe length is the total of the branch pipe (L) and the junction pipes (Ia→
tIb→
t Ic in order from the thickest diameter). At
the point where the pipe length exceed s 30 m, determine the amoun t of refrigerant for the remaining liquid-side pipe diameters
and pipe lengths from the following table in order to charge...