7 OPERATING INSTRUCTION 7.1. Wired Remote Control Name and function of each part 22
8 REFRIGERATION CYCLE 8.1. Heating Model CS-W50BD3P / CU-W50BBP8 8.2. Cooling Only Model CS-W50BD3P / CU-V50BB P8 24
9 OPERATION RANGE The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage. Power Supply Model CU-Unit Main PowerApplicable Voltage Phase, VoltsHzMaximumMinimum W50BBP8 V50BBP83N~38050418342 3N~40050440360 3N~41550457374 Indoor and Outdoor Temperature Q QQ Q Coolingonly type Model 50Hz ... V50BB P8 OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C) MaximumMinimumMaximumMinimum Cooling5032/2321/1543/--5/- Q QQ Q Heat pumptype Model 50Hz ...W50BBP8 OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C) MaximumMinimumMaximumMinimum Cooling5032/2321/1543/--5/- Heating5027/-16/-24/18-10/- 25
Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 7.5 metres connecting pipe and horizontal installation. (Cooling) Equivalent Length = actual pipe length + number of elbow x ELE ELE : equivalent length ofelbow. 10.2. REFRIGERANT ADDITIONAL CHARGE • • • • The piping length exceeds 30 metres. APPLICABLE FOR ALLMODELS Before shipment, this air conditioner is filled with the rated amoun t of refrigerant subject to 30m piping length. (The rated amoun t of refrigerant is indicated on the name plate.) But when the piping length exceed s 30m, additio nal charge is required according to the following table.For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity. (Heating) Outer diameter of gas side pipe mm (inch) 9.52 (3/8)0.18 12.7 (1/2)0.20 15.88 (5/8)0.25 19.05 (3/4)0.35 ModelRef. Charge 2.0~2.5HP20g per 1m 3~6HP50g per 1m Example : CS-W50BD3P In case of 50m long pipe (one-way), the amoun t of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g 10 PIPE LENGTH 10.1. CORRECTION OF COOLING AND HEATING CAPACITIES 26
10.3. Piping installation by existing piping Q Coolingonly type(50Hz) Model NameStandard piping specification Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume (g/m) CU-V50BBP89.5219.053050 Q Heat pumptype(50Hz) Model NameStandard piping specification Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume (g/m) CU-W50BBP89.5219.053050 Attention • • • • Please never decrease the gas piping size. (It causes the breakdown of the compressor) • • • • The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping specification. 27
11 OPERATING CHARACTERISTIC HEAT PUMPMODEL ModelMain PowerCompressor MotorIndoor UnitOutdoor UnitElectrical Data (50Hz) SourceFan MotorFan MotorR.CIPT VoltageFrequencyS.C.R.C.(A)IPT(kW)R.C.IPTR.C.IPT(A)(kW) (V)(Hz)(A)COOL / HEATCOOL / HEAT(A)(kW)(A)(kW)COOL / HEATCOOL / HEAT CS-W50BD3P38050698.57 / 8.574.94 / 5.040.910.190.990.229.20 / 9.205.35 / 5.45 CU-W50BBP840050698.55 / 8.554.91 / 5.010.930.211.020.239.20 / 9.205.35 / 5.45 41550698.53 / 8.534.88 / 4.980.960.221.040.259.20 / 9.205.35 / 5.45 COOLING ONLY MODEL CS-W50BD3P38050698.574.940.910.190.990.229.205.35 CU-V50BBP840050698.554.910.930.211.020.239.205.35 41550698.534.880.960.221.040.259.205.35 Legend: S.C.: Starting Current R.C.: Runnin g Current IPT: Power Consumption 28
12 FAN PERFORMANCE Fan Performance ModelCS-W50BD3P External Static PressureFan speedCurrent (A)Power Consumption (kW)Power Factor (%)RPM (r / min)Air Volume (m3 / min) 69Pa (7mmAq)Hi1.210.2797.0136040 H59Pa (6mmAq)Me1.030.2397.1123035 49Pa (5mmAq)Lo0.920.2094.5111030 49Pa (5mmAq)Hi1.150.2698.3127040 L39Pa (4mmAq)Me1.020.2398.0114035 29Pa (3mmAq)Lo0.900.2096.6100030 O OO O CS-W50BD3P Fan Performance Curve 29
13 SAFETY DEVICE • • • • INDOOR UNIT Indoor unitModelCS- W50BD3P For fan motor protection InternalOFF°C135 Protector (49F)ON°C87 For control protection FuseCUTA3.15 • • • • OUTDOOR UNIT Outdoor unitHeat pump model50HzCU- W50BBP8 Cooling only model50HzCU- V50BBP8 For refrigerant cycle High pressureOFFMPa3.1 switch (63H1)ONMPa2.3 For compressor Over current protection Heat pump modelOFFA15 Cooling only modelOFFA 50Hz15 RESET-Automatic Discharge temp. protection Discharge temperature thermistor (Th1)Com- pressor OFF°C120 Liquid compress protection Crankcase heaterInput powerW34~41 Compressor protection Internal protectorOFF°C 50Hz145 ON°C 50Hz61 Trip time°C3-10sec/ 48A For fan motor protectionOFF°C 50Hz135 Internal protector (49F)ON°C 50Hz85 Heating control (Heat pump only) Pressure switchOFFMPa2.50 (Fan speed)(63H2)ONMPa2.05 Cooling control Heat exchanger outlet temperature thermistor (Th2)Control methodTh30°C---High speed Th