Home > Panasonic > Air Conditioner > Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							25.8. Indoor thermostat characteristic
     1. Thermostat characteristic during cooling and heating modes
    61 
    						
    							63 
    						
    							25.9. Indoor unit fan control
     1. Fixing at LO, MED or HI
    When LO, MED or HI isset, the relay switches and operation is carried out at that setting.
     2. Automatic fan speed
    When set toAUTO, the indoor unit fan operation changes as shown in the table below.
    25.10. Forced operation during restart
    The compressor will not stop operating for 3 minutes after cooling mode or heating mode operation starts, even if the indoor unit
    thermostat turns off. (However, the compressor will stop operating during this time if the indoor unit air intake temperature exceeds
    33°C during heating mode operation or if the indoor unit air intake temperature drops below 16°C during cooling mode operation.)
    25.11. Outdoor unit fan excess heat dissipation control
     1. Start
    Carried out when the compressor switches from on to off (when the remote control unit is used to stop operation)
     2. Operation
    The outdoo r unit fan runs at SUPER HI speed for approximately 60 seconds and then stops.
    25.12. Discharge temperature control
     1. Operation
    When thedischarge temperature sensor detects a temperature of 100°C or higher during cooling mode operation, the liquid
    bypass valve is turned on.
     2. Cancelling
    When thedischarge temperature sensor detects a temperature of 70°C or lower, the liquid bypass valve is turned off.
    25.13. Emergency operation
    When the emergency operation switch(DSW1) on the outdoor unit printed circuit board is set to the emergency setting, then
    emergency operation is enable d. This allowsnormal operation to continue, with all abnormalities other than a discharge
    temperature abnormality, high pressure abnormality or overcurrent abnormality being ignored.
    64 
    						
    							25.14. DIP switch settings
     
        • 
    • •  • 
    Indoor unit printed circuit board (DSW1)
    65 
    						
    							26 INSTALLATION (INDOOR UNIT)
    66 
    						
    							67 
    						
    							69 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs W50bd3p Cu V50bbp8 Cu W50bbp8 Repair Manual