8 REFRIGERATION CYCLE 8.1. Heating Model CS-W50BD2P / CU-W50BBP8 8.2. Cooling Only Model CS-W50BD2P / CU-V50BB P8 24
Page 25
9 OPERATION RANGE The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage. Power Supply Model CU-Unit Main PowerApplicable Voltage Phase, VoltsHzMaximumMinimum W50BBP8 V50BBP83N~38050418342 3N~40050440360 3N~41550457374 Indoor and Outdoor Temperature Q QQ Q Coolingonly type Model 50Hz ... V50BB...
Page 26
Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 7.5 metres connecting pipe and horizontal installation. (Cooling) Equivalent Length = actual pipe length + number of elbow x ELE ELE: equiva lent length ofelbow. 10.2. REFRIGERANT ADDITIONAL CHARGE • • • • The piping length exceeds 30 metres. APPLICABLE FOR ALLMODELS Before shipment, this air conditioner is filled with the rated amoun t of...
Page 27
10.3. Piping installation by existing piping Q Coolingonly type(50Hz) Model NameStandard piping specification Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume (g/m) CU-V50BBP89.5219.053050 Q Heat pumptype(50Hz) Model NameStandard piping specification Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume (g/m) CU-W50BBP89.5219.053050 Attention • • • • Please never decrease the gas piping size. (It causes the breakdown of...
Page 28
11 OPERATING CHARACTERISTIC HEAT PUMPMODEL ModelMain PowerCompressor MotorIndoor UnitOutdoor UnitElectrical Data (50Hz) SourceFan MotorFan MotorR.CIPT VoltageFrequencyS.C.R.C.(A)IPT(kW)R.C.IPTR.C.IPT(A)(kW) (V)(Hz)(A)COOL / HEATCOOL / HEAT(A)(kW)(A)(kW)COOL / HEATCOOL / HEAT CS-W50BD2P38050698.57 / 8.574.94 / 5.040.910.190.990.229.20 / 9.205.35 / 5.45 CU-W50BBP840050698.55 / 8.554.91 / 5.010.930.211.020.239.20 / 9.205.35 / 5.45 41550698.53 / 8.534.88 / 4.980.960.221.040.259.20 / 9.205.35 / 5.45 COOLING...
Page 29
12 FAN PERFORMANCE O OO O CS-W50BD2P ModelCS-W50BD2P External Static PressureFan SpeedCurrent (A)Power Consumption (kW)Power Factor (%)RPM (r/min)Air Volume (m3/min) 98pA (10mmAq)Hi2.440.4998.9140645 90Pa (9.2mmAq)Me1.740.3898.8135043 79Pa (8.1mmAq)Lo1.370.3198.3126540.5 O OO O CS-W50BD2P Fan Performance Curve 29
Page 30
13 SAFETY DEVICE • • • • INDOOR UNIT Indoor unitModelCS- W50BD2P For fan motor protection InternalOFF°C135 Protector (49F)ON°C87 For control protection FuseCUTA5 • • • • OUTDOOR UNIT Outdoor unitHeat pump model50HzCU- W50BBP8 Cooling only model50HzCU- V50BBP8 For refrigerant cycle High pressureOFFMPa3.1 switch (63H1)ONMPa2.3 For compressor Over current protection Heat pump modelOFFA15 Cooling only modelOFFA 50Hz15 RESET-Automatic Discharge temp. protection Discharge temperature...