1. Automatic address setting (no need to have dip-switch set) If the wiring connected properly as above example, the address is set automatically by the main powersupply. An indoor unit with remote control will be set as the master. If the power source is installe d to indoor units and outdoor separately, turn on the switch as the following procedure: outdoo r unit, indoor unit with control, and other indoor units. When theslave units do not operate (when address cannot be set) Important: The address...
Page 52
1. Automatic address setting (no need to have dip-switch set) If the wiring connected properly as above example, the AC numbe rs are set automatically by the main powersupply . An indoor unit with remote control will be set as the master. If the power source is installe d to indoor units and outdoo r separately, turn on the switch as the following procedure: outdoo r unit, indoor unit with controller, and other indoor units. The AC numbe r will be set at random. 2. Manua l address setting (by...
Page 53
Procedures of deleting memory attwincontrol system 1. Set the “OFF” position for main power supply switch. 2. Set the “ON” position for No. 8 pin of dip switch (DSW1) on indoor unit P.C. board. 3. Take main power supply switch “ON” for one minute, and then main power supply switchoff. 4. Set the “OFF” position for No. 8 pin of dip switch (DSW1). Procedure of deleting memory at group control system 1. Set the “OFF” position for main power supply switch. 2. Set the “ON” position for No. 1 pin to No....
Page 54
Emergencyoperation • • • • Emergency operation of outdoor unit Emergency operation can be carried out by setting the DSW1 switch on the printed circuit board inside the outdoo r unit to the EMERGENCY position. However, emergency operation is only carried out when an abnormality is detected by the indoor/outdoor temperature thermistors. The resistance values of each thermistor are measured as shown in the table below to determine if there is an abnormality. Thermistor resistance table Temperatu...
Page 55
25 CONTROL 25.1. Description of basic Functions 25.1.1. Cooling mode operation time chart (*1) Outdoor unit fan start control during cooling At the start of cooling mode and drying mode operation, the outdoo r unit heat exchan ger outlet temperature is detected in order to set the fan speed. Operation is carried out at the fan speed detected for 30 seconds. After 30 seconds, the heat exchan ger outlet temperature is detected and the outdoo r unit fan speed is changed automatically . (*2) Cooling low...
Page 56
25.2. Freezing prevention control 1. Operation During cooling mode operation, after 9 minutes have passed since the compressor turned on, the outdoor units stops operating when the temperature detected by the indoor unit pipe temperature sensor is 2°C or lower. The indoor unit continues operating at the fan speed set by the remote control unit. (The remote control unitdisplay does not change.) 2. Cancelling This control is cancelled when the temperature detected by the indoor unit pipe temperature...
Page 57
25.3. Heating mode operation time chart (Heat pump type only) (*2) Outdoor unit fan control during heating mode operation Under conditions when the compressor is on during heating mode operation (except during defrosting and when the liquid bypass valve is on), the outdoo r unit fan is controlled by means of input (CN2) indicating whether the contact of the heating pressure switch on the outdoor unit circuit board is open or closed (At the start of heating mode operation, the fan operates at HI speed.) 57
Page 58
25.4. Hot starting 1. When heating mode operation starts 1. Start Hot start control commences heating mode operation starts. 2. Operation “PREHEAT” appears on the remote controldisplay . (Other display s remain unchanged.) At the indoor unit, the indoor unit fan stops. In additio n, during hot starting, the louvre stays at the horizon tal position (angle 0°). 3. Cancelling After 1 minute has passed since heating mode operation started, or if the compressor has turned on, hot starting is cancelled when...
Page 59
3. Cancelling Hot starting is cancelled when the temperature detected by the indoor unit pipe temperature sensor is 18°C or higher, or after a maximum 1 minute has passed since defrosting was completed. After cancellation, the “PREHEAT” display on theremote control disapp ears and the louvre operation returns to the previous setting. (However, the indoor unit fan operates at LOW speed for 2 minutes after cancellation, and then returns to the previous setting.) < When hot startoperation is cancelled by...
Page 60
25.6. Excess heat dissipation for indoor unit The indoor unit fan continues operating for 30 seconds after heating mode operation turns off in order to dissipa te excess heat. 1. Whenheating mode operation has stopped (LOWoperation for 30 seconds) 2. Whenoperation is set to a mode other than heating by means of the OPERATION MODE switch 3. If operation starts again during the 30 seconds mentioned in (1) above (The fan operates at LOW speed for the remainder of the 30 seconds in (1), and then hot start...