Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual
Here you can view all the pages of manual Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 31
14 COMPONENT SPECIFICATION Compressor ModelsHeat pump model50HzCU-W50BBP8 Cooling only model50HzCU-V50BBP8 60Hz- Compressor Modelsingle-phase- 3-phaseR68KCE-TFD Compressor Type No. of CylindersSCROLL 1 Revolutionr/min.2,900 Piston Displacementm3/min.16.18 MotorType Starting MethodDirect On-Line Starting Rated OutputkW4.1 Poles Insulation Glass2 E RevolutionMEL56MMMAPOE RevolutionL1.8 Evaporator Models (Cooling Only Model)CS-W50BD2P Tube MaterialCopper Tube Outer Diametermm9.5 Thicknessmm0.28 Row3 No. of...
Page 32
Condenser ModelsHeat pump modelCU-W50BBP8 Cooling only modelCU-V50BBP8 Tube MaterialCopper tube Outer Diametermm9.52 Thicknessmm0.3 Row2 No. of Tubes/Row46 Fin MaterialAluminium Thicknessmm0.105 Fin PitchNo./inch14 Fin SurfaceX-Louvre-fin Total Face Aream21.05 Fan TypePropeller Fan No.of unit2 Fan Motor Starting MethodDirect on-line Starting Rated OutputkW0.055 X 2 Poles6 PhaseSingle-Phase Insulation ClassE 32
Page 33
15 CAPACITY AND POWER CONSUMPTION Q QQ Q PERFORMANCE DATA COOLING PERFORMANCE ModelCooling capacities are based conditions CS-W50BD2POIndoor temp. 27°C D.B. 19°C W.B. OOutdoor temp. 35°C D.B. OStandard air volume 36 m 3/min OExternal Static Pressure (147Pa)Cooling capacity 12.5kW EnteringTemperatu re Air Entering Condenser (°C D.B.) Air25°C30°C35°C40°C43°C Temperatu reTCSHCIPTTCSHCIPTTCSHCIPTTCSHCIPTTCSHCIPT D.B.W.B.kWkWkWkWkWkWkWkWkWkWkWkWkWkWkW...
Page 34
16 DISCHARGE AND SUCTION PRESSURE 16.1. SATURATION TEMPERATURE OF DISCHARGE AND SUCTION PRESSURE O OO O Commonness TO ALL THE MODELS O OO O SATURATIONTEMPERATURE OF DISCHARGE AND SUCTION PRESS URE *For intake temperature, consult the pressure - Enthalpy Table (R407C) at the end. 34
Page 36
18.1. TWIN • • • • Simultaneous air conditioning of wide spaces and corners is possible. • • • • Master units and slave-units can be set automatically in twin and triple systems. No address setting is necessary. • • • • Multiple indoor units can be operated simultaneousl y with a single remote control unit. Note that individual operation is not possible. 18 TWIN OPERATION 18.1.1. Operation (Twinoperation setting) • • • • The master units and slave units are set...
Page 37
Automatic address setting fortwinsystem Procedure:Turn on the power supply for the indoor and outdoor units. Operation:Automatic address setting will start 10 to 30 seconds after the power supply is turned on, and will be completed after about 1 minute. If the power supplies for the indoor unit and outdoor unit cannot be turned on at the same time, turn on the power supply for the outdoor unit, the indoor unit which is connected to the remote control, and then the other indoor units in that order. If the...
Page 38
Function Automatic address resetting fortwinsystem s • • • • This clears the current twin addresses which have been set automatically , and causes automatic twin address setting to be carried out once more. Procedure:Press the ADDRESS RESET switch SW3 (push button switch) on the outdoor unit circuit board continuously until LEDs 2 to 8 on the outdoor unit circuit board are all illuminated (takes approx. 3.5 seconds). Operation:The outdoor unit will reset the addresses for the indoor units which...
Page 39
• • • • The branch pipe should be horizon tal to or perpendicular to the indoor unit. • • • • Installin g branch pipes 18.3. Refrigerant charging • • • • For twin systems The pipe length is the total of the branch pipe (L) and the junction pipes (Ia→ tIb→ t Ic in order from the thickest diameter). At the point where the pipe length exceed s 30 m, determine the amoun t of refrigerant for the remaining liquid-side pipe diameters and pipe lengths from the following table in order...
Page 40
18.4. Wiring Whenboth indoor and outdoor unit draw power (Example: 3 Phase power supply model) When only theoutdoor unit draws power 40