Home > Panasonic > Air Conditioner > Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual

Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual

Here you can view all the pages of manual Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.

Page 1

 1 SERVICE INFORMATION 2
 2 FEATURES 
3
 3 SPECIFICATION (HEAT PUMP TYPE) 
9
 4 SPECIFICATION (COOLING ONLY TYPE) 
10
 5 TECHNICAL DRAWING 
11
 6 CIRCUITDIAGRAM 
13
 7 OPERATING INSTRUCTION 
22
 8 REFRIGERATION CYCLE 
24
 9 OPERATIO N RANGE 
25
 10  PIPE LENGTH 
26
 11  OPERATING CHARACTERISTIC 
28
 12  FAN PERFORMANCE 
29
 13  SAFETYDEVICE 
30
 14  COMPONENT SPECIFICATION 
31
© 2002 Matsushita Industrial Corporation. Sdn. Bhd.
(11969-T). All rights reserved. Unauthorized copying
and distribution is a...

Page 2

1 SERVICE INFORMATION
Caution:
OPb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
OPb free solder will tend to splash when heated too high (about 1100° F/600°C).
Notice of Address setting for NEW Cassette / NEW Outdoor Unit.
The new Hide-Away / New Outdoor models are possible to have...

Page 3

2.1. Variety of excellent features
2.1.1. Compact design
 
    • 
• •  • 
The height is only 36cm and can be installe d even where
the space is limited.
2.1.2. Automatic restart function
 
    • 
• •  • 
W hen the electric power comes back after a power failure,
the unit itself automatically restarts the operation in the pre-
failure mode.
2.1.3. Auto fanmode (indoor unit)
 
    • 
• •  • 
Auto fan mode is added beside s Hi, Me and Lo.
It automatically adjusts the fan speed according to the
indoor...

Page 4

[Product features]
2.2.1. Low-noise design improves in
surrounding areas
 1. The noise-suppressing winglet fan is a result of new
research into vane design theory. The unique curved shape
suppresses the generation of vortexes, thus reduces air
flow noise.
 2. The adoption of double -orifice rings reduces air passage
resistance.
 3. Strengthening of the noise insulation materials in the
compressor and the sealing-in of mechanical noise allows
vibration noise to be greatly enclosed and suppressed.
 4. The...

Page 5

2.3.1. Pipes that are one size larger can
also be connected for renewal
 
    • 
• •  • 
If renewing the system, existing refrigerant pipes can be
utilized so that only the indoor units need to be replaced.
 
    • 
• •  • 
For example, liquid and gas pipesfrom 10years ago can be
connected to current pipes with the same size for one size
larger. Effective utilization of materials reduces working
time and trouble. (Adaptor sockets are not supplie d.)
2.3.2. Additional refrigerant charging
unnecessary for...

Page 6

2.4.2. Separate indoor/outdoor unit
power supplies
The power supply can be connected to (1) just the outdoo r
units, or (2) to both indoor and outdoor units.
2.4.5. Twin operation
 
    • 
• •  • 
Simultaneous air conditioning of wide spaces and corners is
possible. Indoor units of different horsepowers and models
can even be used in combination.
 
    • 
• •  • 
Master unit and slave-units can be set automatically in twin
systems. No address setting is necessary.
 
    • 
• •  • 
Multiple indoor units...

Page 7

2.5.2.2. Installation
 1. Install the sleeve and the insert.
 2. Install the indoor unit.
 3. Install the refrigerant piping.
 
    • 
• •  • 
Pipe materials
 
    • 
• •  • 
Refrigerant pipes which were previously used to carry
R22 must not be re-used. If replacing the indoor and
outdoo r units, be sure to replace all refrigerant pipes
also.
 
    • 
• •  • 
Check the pipe thickness.
 
    • 
• •  • 
Clean the inside of the pipes.
 
    • 
• •  • 
W hen storing pipes, seal both ends of the pipes and...

Page 8

Q
Boiling point at normal atmospheric pressure
(reference)
RefrigerantHFC32HFC125HFC134a
Boiling point-52°C-49°C-26°C
 
    • 
• •  • 
Use a special gauge manifo ld and charging hose.
 
    • 
• •  • 
If refrigerant leaks occur, replace all of the refrigerant
(same as for R22).
 
    • 
• •  • 
Note that a R22 leak detector cannot be use to detect
leaks.
 
    • 
• •  • 
Refer to the Installation Instructions include d for the
correct charging amoun t.
 
    • 
• •  • 
Make a note of additio nal...

Page 9

3 SPECIFICATION (HEAT PUMP TYPE)
CS-W50BD2P / CU-W50BBP8
ITEM / MODELIndoor UnitOutdoor unit
Main BodyCS-W50BD2PCU-W50BBP8
Cooling CapacitykW14.00
(BTU/h)(47,700)
Heating CapacitykW16.00
(BTU/h)(54,600)
Refrigerant Charge-lessm30
Standard Air Volume for High Speedm3/minHi 38-
cfmHi 1342
External Static PressurePaHi 98 Me 81 Lo 70-
mmAqHi 10 Me 8.3 Lo 7.2
Air InletBackward SuctionBack sided Suction
Air OutletFront blow-outFront blow-out
Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 1100 x...

Page 10

4 SPECIFICATION (COOLING ONLY TYPE)
CS-W50B D2P / CU-V50BB P8
ITEM / MODELIndoor UnitOutdoor unit
Main BodyCS-W50BD2PCU-V50BBP8
Cooling CapacitykW14.00
(BTU/h)(47,700)
Refrigerant Charge-lessm30
Standard Air Volume for High Speedm3/minHi 38-
cfmHi 1342
External Static PressurePaHi 98 Me 81 Lo 70-
mmAqHi 10 Me 8.3 Lo 7.2
Air InletBackward SuctionBack sided Suction
Air OutletFront blow-outFront blow-out
Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 1100 x 320
Net Weightkg (lbs)59 (130)112...