Home > Panasonic > Air Conditioner > Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual

Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							21 
    						
    							7 OPERATING INSTRUCTION
    7.1. Wired Remote Control
    Name and function of each part
    22 
    						
    							23 
    						
    							8 REFRIGERATION CYCLE
    8.1. Heating Model
    CS-W50BD2P / CU-W50BBP8
    8.2. Cooling Only Model
    CS-W50BD2P / CU-V50BB P8
    24 
    						
    							9 OPERATION RANGE
    The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases
    must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher
    than 85% of the rated voltage.
    Power Supply
    Model
    CU-Unit Main PowerApplicable Voltage
    Phase, VoltsHzMaximumMinimum
    W50BBP8 V50BBP83N~38050418342
    3N~40050440360
    3N~41550457374
    Indoor and Outdoor Temperature
    Q
    QQ Q
    Coolingonly type
    Model 50Hz ... V50BB P8
    OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C)
    MaximumMinimumMaximumMinimum
    Cooling5032/2321/1543/--5/-
    Q
    QQ Q
    Heat pumptype
    Model 50Hz ...W50BBP8
    OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C)
    MaximumMinimumMaximumMinimum
    Cooling5032/2321/1543/--5/-
    Heating5027/-16/-24/18-10/-
    25 
    						
    							Correction of cooling and heating capacities according to
    the connecting pipe length.
    The data of cooling capacities (marked on the name plate)
    are based on 7.5 metres connecting pipe and horizontal
    installation.
    (Cooling)
    Equivalent Length = actual pipe length +
    number of elbow x ELE
    ELE: equiva lent length ofelbow.
    10.2. REFRIGERANT ADDITIONAL
    CHARGE
     
        • 
    • •  • 
    The piping length exceeds 30 metres.
    APPLICABLE FOR ALLMODELS
    Before shipment, this air conditioner is filled with the rated
    amoun t of refrigerant subject to 30m piping length. (The
    rated amoun t of refrigerant is indicated on the name plate.)
    But when the piping length exceed s 30m, additio nal charge
    is required according to the following table.For other pipe length of other installation multiply
    by the following correction factor to determine the
    revised cooling capacity.
    (Heating)
    Outer diameter of gas
    side pipe mm (inch)
    9.52 (3/8)0.18
    12.7 (1/2)0.20
    15.88 (5/8)0.25
    19.05 (3/4)0.35
    ModelRef. Charge
    2.5HP20g per 1m
    3~6HP50g per 1m
    Example:
    CS-W50BD2P
    In case of 50m long pipe (one-way), the
    amoun t of refrigerant to be replenished is:
    (50 - 30) x 50 = 1,000g
    10 PIPE LENGTH
    10.1. CORRECTION OF COOLING AND HEATING CAPACITIES
    26 
    						
    							10.3. Piping installation by existing piping
    Q
    Coolingonly type(50Hz)
    Model NameStandard piping specification
    Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length
    (m)Additional gas volume (g/m)
    CU-V50BBP89.5219.053050
    Q
    Heat pumptype(50Hz)
    Model NameStandard piping specification
    Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume
    (g/m)
    CU-W50BBP89.5219.053050
    Attention
     
        • 
    • •  • 
    Please never decrease the gas piping size. (It causes the breakdown of the compressor)
     
        • 
    • •  • 
    The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping
    specification.
    27 
    						
    							11 OPERATING CHARACTERISTIC
    HEAT PUMPMODEL
    ModelMain PowerCompressor MotorIndoor UnitOutdoor UnitElectrical Data (50Hz)
    SourceFan MotorFan MotorR.CIPT
    VoltageFrequencyS.C.R.C.(A)IPT(kW)R.C.IPTR.C.IPT(A)(kW)
    (V)(Hz)(A)COOL / HEATCOOL / HEAT(A)(kW)(A)(kW)COOL / HEATCOOL / HEAT
    CS-W50BD2P38050698.57 / 8.574.94 / 5.040.910.190.990.229.20 / 9.205.35 / 5.45
    CU-W50BBP840050698.55 / 8.554.91 / 5.010.930.211.020.239.20 / 9.205.35 / 5.45
    41550698.53 / 8.534.88 / 4.980.960.221.040.259.20 / 9.205.35 / 5.45
    COOLING ONLY MODEL
    CS-W50BD2P38050698.574.940.910.190.990.229.205.35
    CU-V50BBP840050698.554.910.930.211.020.239.205.35
    41550698.534.880.960.221.040.259.205.35
    Legend:
    S.C.: Starting Current
    R.C.: Runnin g Current
    IPT: Power Consumption
    28 
    						
    							12 FAN PERFORMANCE
    O
    OO O
    CS-W50BD2P
    ModelCS-W50BD2P
    External Static
    PressureFan
    SpeedCurrent
    (A)Power Consumption
    (kW)Power Factor
    (%)RPM
    (r/min)Air Volume
    (m3/min)
    98pA (10mmAq)Hi2.440.4998.9140645
    90Pa (9.2mmAq)Me1.740.3898.8135043
    79Pa (8.1mmAq)Lo1.370.3198.3126540.5
    O
    OO O
    CS-W50BD2P
    Fan Performance Curve
    29 
    						
    							13 SAFETY DEVICE
     
        • 
    • •  • 
    INDOOR UNIT
    Indoor unitModelCS-
    W50BD2P
    For fan motor protection
    InternalOFF°C135
    Protector (49F)ON°C87
    For control protection
    FuseCUTA5
     
        • 
    • •  • 
    OUTDOOR UNIT
    Outdoor unitHeat
    pump
    model50HzCU-
    W50BBP8
    Cooling
    only
    model50HzCU-
    V50BBP8
    For refrigerant cycle
    High pressureOFFMPa3.1
    switch (63H1)ONMPa2.3
    For compressor
    Over current protection
    Heat pump
    modelOFFA15
    Cooling
    only modelOFFA
    50Hz15
    RESET-Automatic
    Discharge temp.
    protection
    Discharge temperature
    thermistor (Th1)Compressor
    OFF°C120
    Liquid compress
    protection
    Crankcase heaterInput
    powerW34~41
    Compressor protection
    Internal protectorOFF°C
    50Hz145
    ON°C
    50Hz61
    Trip
    time°C3-10sec/
    48A
    For fan motor
    protectionOFF°C
    50Hz135
    Internal protector
    (49F)ON°C
    50Hz85
    Heating control
    (Heat pump only)
    Pressure switchOFFMPa2.50
    (Fan speed)(63H2)ONMPa2.05
    Cooling control
    Heat exchanger outlet
    temperature thermistor
    (Th2)Control
    methodTh30°C---High speed
    Th
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs W50bd2p Cu V50bbp8 Cu W50bbp8 Repair Manual