Page 11

UnitCS-E1219KCU-E1219K
Capillary TubeLengthmm605
Flow Ratel/min—15.7
Inner Diametermm—1.7
Air FilterMaterial
StyleP.P.
Honeycomb—
Capacity ControlCapillary Tube
Compressor CapacitorµF, VAC—30 µF, 400VAC
Fan Motor CapacitorµF, VAC1.5 µF, 400VAC2.0 µF, 450VAC
Note:
 • 
Specifica tions are subject to change without notice for further improvement.
11
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 12

4 Dimensions
12
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 13

13
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 14

5 Refrigeration Cycle Diagram
14
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 15

6 Block Diagram
15
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 16

7 Wiring Diagram
16
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 17

Cooling in operation according to Remote Control setting.
Time DelaySafety Control (3 minutes)
7 minutes TimeSave Control
Starting Current Control
Anti-Freezing Control
 • If the temperature of the indoor heat exchan ger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
 • Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting...

Page 18

Automatic Fan Speed Mode
Cooling Operation Time Diagram
WhenAutomatic Fan Speed is selected at Remote Control during cooling operation.
 • Fan speed rotates in the range of Hi to Me.
18
CS-E719K CU-E7 19K / CS-E919K CU-E9 19K / CS-E1219K CU-E1219 K 

Page 19

Quiet Operation Control
(For Cooling Mode or cooling region of Soft Dry Mode)
 • Purpose of this operation is to provide quite cooling operation compare to normal operation.
 • W hen the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation.
 • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
 • Dew formation become severe at Quiet Lo cool,...

Page 20

Time DelaySafety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
 • The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
 • During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
 • The operation will be switched on and off for up to 10 minutes“ON”and 6 minutes“OFF”. Once Soft...