Here you can view all the pages of manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Maintenance For Survivable Remote EPN Manual. The Lucent Technologies manuals for Communications System are available online for free. You can easily download all the documents as PDF.
Page 91
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-35 Fault isolation procedures 2 8. Connec t the transmit and rec eive c ab les tog ether using the fib er op tic c oup ler (Comc od e 407643014, p rovided in Maintenanc e Kit #30) to c reate a loop as shown in Fig ure 2-19 . Figure 2-19. Manual loopback with fiber optic coupling 9. Go to the front of the c ab inet and inspec t the...
Page 92
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-36 Fault isolation procedures 2 10. Rep lac e faulty c omp onent(s) and rec onnec t the orig inal fib er. Be sure to rec onnec t the fib ers p rop erly as noted in Step 7 in this ‘‘ Manual loop bac k p roc ed ure’’ section. 11. Release the Exp ansion Interfac e c irc uit p ac k or Switc h Nod e Interfac e c irc uit p ac k (release board...
Page 93
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-37 Fault isolation procedures 2 Table 2-11. DS1 Interface Cable Connectors Lead Desig.50-Pin Connector Pin #15-Pin Connector Color Pin Color Plug 04 Fac ility D Line In LID 38 W-BL 11 W-BL Fac ility D Line In LID* 13 BL-W 03 BL-W Fac ility D Line Out LOD 39 W-O 09 W-O Fac ility D Line Out LOD* 14 O-W 01 O-W Plug 03 Fac ility C Line In LIC...
Page 94
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-38 110 block cross-connect pins 2 110 block cross-connect pins Table 2-12. 110 block cross-connect pins SRP AuxEPN Aux Amphenol Pin Number ColorCross- Connect Pin NumberLead Designation 1 1. When the loop b etween Cust A (alarm) and Cust Rtn (return) c loses, the SRSwitc h c onfigures the SRP into Restore mod e, overriding the fac ep...
Page 95
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-39 Replacing the TN2301 circuit pack 2 Fi g u re 2 - 2 0 shows the p inout and c ross-c onnec tions for the SREPN. Figure 2-20. SREPN pinout and connections Replacing the TN2301 circuit pack !CAUTION: EPN service is interrupted until a replacement TN2301 is installed, powered up , and the EI links restored . Unseat the circuit pack 1. Power...
Page 96
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-40 Replacing the TN2301 circuit pack 2 3. Push the latc h p in up ward to unloc k the loc king lever. 4. Pull d own on the loc king lever until the c irc uit p ac k d isc onnec ts from its soc ket. 5. Pull the c irc uit pac k just enoug h to b reak c ontac t with the bac kp lane c onnec tor, b ut d o not remove it from the c ab inet....
Page 97
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-41 Replacing the TN2301 circuit pack 2 Figure 2-21. Transceivers attached to the TN2301 circuit pack 2. Remove the b rac ket and then the transc eivers from the old c irc uit p ac k and rep lac e them in the id entic al positions on the new TN2301 c irc uit pack. 3. Rep lac e the b rac ket over the transc eivers to sec ure them to the b...
Page 98
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-42 Restore from remote location 2 5. Insert the new c irc uit p ac k, feed ing the fiber p atc h c ord s to the b ottom p an of the c ab inet. Reseat the circuit pack 1. Reseat the c irc uit pac k into the b ac kp lane c onnec tor. !WARNING: Ensure that the fib er c ab les are not b ent or p inc hed b etween the b ac k of the c irc uit p ac...
Page 99
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-43 Restore from remote location 2 Th e Tab le 2-13 d esc rib es the c ond itions in whic h the restore from a remote loc ation is p ossib le. Table 2-13.TN2301 switch configuration based on input Inputs to Control Logic Modes Remote restoreSurvive mode requested 1 1. The EPN Maintenance (TN775C) c irc uit p ac k req uests switc hing to...
Page 100
DEFINITY® Enterprise Communications Server Release 7 Installation and Maintenance for Survivable Remote EPN 555-233-102 Issue 2 June 1999 SREPN Maintenance 2-44 System links 2 System links The state of a system link is d ep end ent on the state of the various hard ware c omp onents that it travels over. The switc h maintains a list of hard ware c omp onents over whic h the link travels, c alled the hard ware p ath. For eac h system link there is a c urrent and a faulted hard ware p ath as...