Galaxy 3 Series Programming Manual 165 3 = Setting The Setting attribute determines the function (if any) that the custom zone has in setting and unsetting the system. 1. Begin Setif enabled, the custom zone starts the setting procedure, 2. Begin Entryif enabled, the custom zone starts the unsetting procedure, 3. Sets Systemif enabled, the custom terminates the setting procedure. The default for each of the Setting attributes is disabled. To enable the options, select the required Setting attribute...
Page 172
Galaxy 3 Series Programming Manual 166 Assemble Zone Example: Assemble a zone that: • activates Bells outputs when the system is set, • activates Link-A outputs when the system is unset, • generates an alarm condition when the system is part and full set, • does not generate an alarm condition during the setting and unsetting procedure, • acts as a terminator when the system is setting, • logs all activation (in both set and unset states). Programming: (Assuming factory default settings) 1.Select option...
Page 173
Galaxy 3 Series Programming Manual 167 Option 65 – Timers The Timer Control menu are as follows: 65 - Timers Figure 13. Timer Control Timers 1 = Timer A 1 = Timer Status0 = Off 1 = On 2 = Timers (1-20) Use A or B key to select timer - 20 times can be programmed, then press ent. [>], [), B(>) key to program day # to toggle ON/OFF status 0-9 keys to enter time to delete programming 2 = Timer B1 = Timer Status0 = Off 1 = On 2 = Timers (1-20) Use A or B key to select timer - 20 times can be programmed,...
Page 174
Galaxy 3 Series Programming Manual 168 Timer A and B The Galaxy 3 Series control panels provide 2 timers that allow up to 20 times to be assigned over a 7 day period; these can be combined in any order of On and Off times as required. Programming Timers 1.Enter the Timers option; 1=TIMER A is displayed. To modify or assign times go to Step 5. 2.Press the ent key to select Timer A or the A then ent keys to select Timer B; 1=TIMER STATUS is displayed. 3.Press the ent key; the status of the selected...
Page 175
Galaxy 3 Series Programming Manual 169 Autoset Each group can be programmed with 20 Autoset times over a 7 day period. These can be combined in any order of On and Off times as required - for example 20 On times may be allocated to a group, or six Off times and 14 On times. When the system has been set by the Autoset function, outputs programmed as Autoset (refer to option 53 = PROGRAM OUTPUTS) are activated; the Set outputs are also activated. Programming Autoset If groups are enabled (refer to option...
Page 176
Galaxy 3 Series Programming Manual 170 There are five stages to programming the Autoset function: 1. Autoset Status 0 = Off (default) 1 = On 2 = Monitor - if selected, the setting and unsetting of the group is monitored: • if not set manually before the On time, then the Set Late output is activated • if unset before the Off time, then the Unset Early output is activated. 2. Prewarning 1 = Period 0 – 50 minutes (default 30 minutes): 2 = Audible (this can be turned ON or OFF) This option determines the...
Page 177
Galaxy 3 Series Programming Manual 171 5. Autoset Events This option programs the times when the selected group is automatically switched On (Autoset) and Off (Autounset). On selecting the option, the first 2 times assigned to the timer are displayed (the first time is on the top line, the second is on the bottom). If no autoset times have been assigned, the keypad displays stars (7) on the top line. Press the A key to step through each of the times until the required time is shown on the top line of...
Page 178
Galaxy 3 Series Programming Manual 172 During the Lockout period, the group can not be unset unless an alarm has been activated in the group. In the event of an alarm occurring during the Lockout period, any valid type 2.3 (or above) code assigned to the group in alarm may be used to unset and/or reset the group. If multiple locked-out groups are in an alarm condition entry of a single valid code (type 2.3 or above with access to the relevant groups) cancels the alarms and unsets the activated groups....
Page 179
Galaxy 3 Series Programming Manual 173 66 - Pre-Check The Entry/Exit Horns beep once when each zone is tested. As each zone is successfully tested, the keypad indicates the number that remain to be tested. When the last zone is successfully tested the Entry/Exit Horn sounds twice and the keypad displays 0 CHECK ZONES; press the ent key to resume the system routine. 1 = Mode The Mode determines the pre-check level that the selected zones are subjected to before the system can set. The Mode is selected...
Page 180
Galaxy 3 Series Programming Manual 174 Option 67 – Remote Reset The Remote Reset option allows a user to perform an engineer reset authorized by the Alarm Receiving Centre (ARC). In the event of an alarm that requires an engineer reset, the keypad displays a number, which, when quoted to the ARC is decoded and exchanged for a new number. When this new number is entered it resets the Galaxy panel. Entering the engineer code also resets the Galaxy panel. NOTE:The alarm conditions that require to be reset...