Page 81
73 Galaxy 2 Series Installation Manual52 - Zones Option 52 - Zones Zones are programmed in menu 52. Each zone has a set of attributes as shown in the following table: Selecting Zones On entering the option, the first zone on the system is displayed; the zone address, function and group as- signed are displayed on the top line, the descriptor is displayed on the bottom line. From the display of the first zone, any zone on the system can be displayed by pressing the A or B keys or by entering the address...
Page 82
74 Galaxy 2 Series Installation Manual52 - Zones (cont’d) 1 = Function This option allows the function of the zone to be selected. The zone can be assigned a different function for each set mode (full, part and night set) to allow maximum flexibility. For instance, the zone can be pro- grammed with the ‘Intruder’ function in Full and Part Set, but programmed as ‘Not Active’ in Night Set. On selecting this option, the main zone function is selectable using the cursor keys, or by direct entry of the code...
Page 83
75 Galaxy 2 Series Installation Manual52 - Zones (cont’d) 2 = Descriptor Each zone can be assigned with an alpha-numeric description of up to 16 characters (see Table 16, Zone Text Characters). The descriptor is assembled from the character set in this table. On selecting the Descriptor attribute, the currently assigned descriptor (blank by default) is displayed on the top line. Each of the keys on the keypad, when pressed, offers a choice of character on the bottom line. Press the key repeat- edly to...
Page 84
76 Galaxy 2 Series Installation Manual52 - Zones (cont’d) 6 = Groups This option selects the group that a zone belongs to. The zone will always default to group 1, but can be set to work under any group. Zone Functions and Descriptions 00 Not Active The zone is not active in alarms but tampers are monitored 01 Final Zones programmed as Final initiate the unsetting procedure and terminate the setting procedure. NOTE:The setting procedure can only terminate if the Exit Time (Parameter 51.04) is set to...
Page 85
77 Galaxy 2 Series Installation Manual52 - Zones (cont’d) 09 Keyswitch The Keyswitch function allows a zone to be used as an on/off switch for the system or assigned groups. Operating a Keyswitch zone when the system is unset starts the timed full setting routine, therefore the exit time is applicable. The system sets when the exit time expires or a Final or Push Set is activated. If the system is set, operating a Keyswitch immediately unsets the assigned groups; there is no entry time countdown. The...
Page 86
78 Galaxy 2 Series Installation Manual52 - Zones (cont’d) 20 Tamper The Tamper function is continuously operational. When a Tamper zone is activated (1kΩ to 2kΩ), a tamper alarm is generated; this requires to be reset by an authorised user code. If a tamper condition (open or short circuit) occurs, a tamper alarm is also generated. 23 Batt Fail This function is used to monitor the voltage of a back-up battery connected to a power supply. It causes an Aux. Power Supply fault condition. 25 AC Fail This...
Page 87
79 Galaxy 2 Series Installation Manual Option 53 - Outputs This option allows the operation of all the system outputs to be programmed. Outputs numbered 0001 to 0008 are the outputs from the trigger header. Outputs numbered 1001 to 1004 are the standard outputs on the main PCB. Outputs on expansion modules are shown if fitted. Each output has a sub menu containing attributes as shown: 1. Function Assigns the output function that activates the output. 2. Polarity This selects if the output is normally off...
Page 88
80 Galaxy 2 Series Installation Manual 04=Intruder (Latch) The Intruder output is activated on a full alarm event during the set state. 05=Tamper (Latch) The Tamper output is activated whenever a circuit tamper or lid tamper occurs. The output is not subject to rearm: it latches on and remains active until a valid code, with the appropriate System Reset level, is entered. 06=24 Hour The 24 Hour output is activated whenever a 24 Hour zone is activated. The output is not subject to rearm: it latches on and...
Page 89
81 Galaxy 2 Series Installation Manual 44=Abort (Pulse) The Abort output is activated when a valid code is entered to unset the system following an intruder alarm. The output stays on for one minute and then switches off. 45=Unset (Pulse) The Unset output is activated each time the system (or group) is unset. 51=Link (Reflex) Activates when link zone is activated see 52.1 66=RF Jam (Reflex) The RF Jam output is activated whenever any of the RF RIO’s configured onto the system detect a significant level...
Page 90
82 Galaxy 2 Series Installation Manual Option 56 - Comms The Communications option is used to control the Galaxy 2 Series system signalling and has five submenus broken down as follows: 1 = Telecoms; 5 = GSM; 6 = HW Priority; 7 = Parameters, 8 = 2-Way Voice Telecom/GSM These sub-sections set up the parameters for the built-in dialler modem and the GSM Module. Most of the programming options are shared between both sections and can be modified from either one, except where noted. Figure 32. Telecom/GSM...