Page 91

83
Galaxy 2 Series Installation Manual
01  Format
The communicator provides three signalling formats:
• DTMF
• SIA
• Contact ID
Once the format has been selected, the alarm and event triggers that the panel will transmit to the ARCs, may
be programmed.
1 = DTMF (Dual tone Multiple Frequency)
DTMF is the fast format. When DTMF format is selected, the operation of the dialler is similar to that of a
hardwired 8-channel communicator.
Programming Channels
On selecting DTMF, the keypad displays 1 = Channels 1...

Page 92

84
Galaxy 2 Series Installation Manual
4 = Groups
NOTE:The Groups attribute is only available if groups have been enabled on the system (refer to
Option 63 = OPTIONS) and is also dependent upon the programmed output function for
the channel.
The Group attribute allows the channel to be assigned to the groups on the system; a channel can be
assigned to more than one group. The channel will only trigger when an event occurs on one of the
groups assigned to the channel. All channels default to all groups on...

Page 93

85
Galaxy 2 Series Installation Manual
2 = SIA (Security Industry Association)
The SIA format provides a highly detailed protocol that transmits detailed information including zone descrip-
tions to a PC loaded with suitable software or to a SIA compatible receiver.  The SIA format is capable of
transmitting over 70 different Galaxy 2 Series events (refer to Appendix A for further details).
On selecting the SIA format, the keypad prompts for the required SIA level to be entered, there are 4 SIA
levels...

Page 94

86
Galaxy 2 Series Installation Manual
02  Telephone No.1
Telephone number 1 must be entered. This is the main telephone number that the alarms are signalled to. Up
to 20 digits may be entered, including control modifiers.
Note on dial Attempts
After a dialling sequence the panel waits 25 seconds from the last digit dialled, for a kiss-on tone. If nothing is
received in that time, the call will be considered a fault call and that attempt terminated. Between redial at-
tempts, the panel will go back on...

Page 95

87
Galaxy 2 Series Installation Manual
Table 26. Panel Operation
s g n i r f o o Nno i t a r e p O l e n a P
0 0sl l a c g n i m o c n i s r e w s n a r e v e n l e n a P
4 1 - 1 0sr e w s n a l e n a p e h t e r o f e b s g n i r f o r e b m u n e h t s l a u q e y
r t n E
5 1ed o m t a e f e d e n i h c a m r e w s n A
09 No. of Rings
This option determines the number of rings before the dialler modem answers an incoming call; the program-
mable range is 00 – 15. The following table shows the panel...

Page 96

88
Galaxy 2 Series Installation Manual
10 = Line Fail
This option has two settings:
0 = No
When set to No there is no internal alarm or indication in the event of a telephone line fail condition.
1 = Yes
If this option is set to Ye s, a line fail condition will cause a fault condition. An alert indication is given in the
unset state. A Line Fail condition does not exist until 30 seconds after loss of line voltage. A line fault indication
will then be given within 10 seconds if the debounce time is set to...

Page 97

89
Galaxy 2 Series Installation Manual
2 = Access Mode
This option determines what authorisation is required for remote service connection. There are two options:
1 = Direct Access
This permits access anytime. The remote centre can dial directly to the panel and gain access. If a call-back
number is programmed in option 3, then connection must be made by the call back procedure.
2 = Manager Authorise
This requires the user to authorise the remote servicing call via menu 47. The panel will not answer an...

Page 98

90
Galaxy 2 Series Installation Manual
1 = Mobile Nos
1 = Mobile 1
This selects the first mobile user.
1 = Mobile Number
This is a 20 digit telephone number and is the mobile phone number of the recipient of the message.
2 = Event Type
Refer to Table 27. Event types.
3 = Group Map
This option selects the system group or area from which messages will be sent.
2 = Mobile 2
As per mobile 1.
3 = Mobile 3
As per mobile 1.
2 = Centre No
This is a 20 digit telephone number and is the phone number of the SMS...

Page 99

91
Galaxy 2 Series Installation Manual
5 = UCP Operation
This option specifies the coding of UCP SMS operation both from the panel and the replies from the SMS
message centre.
1 = Call Input
This option sets part of the SMS operation message from the panel to the SMS message centre to be 01
(default value).
2 = Call Input sup
This option sets part of the SMS operation message from the panel to the SMS message centre to be 03.
3 = SMS Message
This option sets part of the SMS operation message from the...

Page 100

92
Galaxy 2 Series Installation Manual
03 = Fire Delay
This parameter determines the delay between the activation of a fire alarm and the signalling to an ARC. The
Fire Delay is programmable within the range 00-60 seconds. The default is 00 seconds.
04 = Power Delay
This parameter determines the delay between the activation of AC Fail outputs following a mains failure to
allow the power to return before signalling the fault. The Power Delay is programmable within the range
00-60 minutes. The default is...