APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-25 Digital Counter 6 nameDigCnt 6 Name NA Digital counter 6 PresetDigCnt 6 Preset0 1 [-2147483648 : 2147483647] Digital counter 6 CompareDigCnt 6 Compare0 1[-2147483648 : 2147483647] Function permissionDigCnt 7 FunctionDISABLED NA Digital Counter 7 nameDigCnt 7 Name NA Digital counter 7 PresetDigCnt 7 Preset0 1 [-2147483648 : 2147483647] Digital counter 7 CompareDigCnt 7 Compare0 1 [-2147483648 :...
Page 282
D-26F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Output typeOutput Type_X_0 Z NORMAL N/A[NORMAL, PULSE, LATCH] Output pulse length Pulse Output Ti me_ X_0 Z 10000 1 ms[0 : 60000] Analog Inputs Range Range_X_0 Z NONE N/A[NONE, -1 to 0mA, 0 to 1 mA, -1 to 1 mA, 0 to 5 mA, 0 to 10 mA] Minimum Value Min_Value_X_0 Z 0.00 0.01[ -9999.99 : 9999.99] Maximum Value Max_Value_X_0 Z 0.00 0.01[ -9999.99 : 9999.99] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED –...
Page 283
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-27 Default Value SelectionDefault Value XOFFN/A[OFF – ON – LATEST OFF – LA TEST ON] Note: X is the Remote Device index, up to 32 LIST OF TIME OVERCURRENT CURVES AVAILABLE IN F650 IEEE extremely/very/moderately inverse IEC Curve A/B/C/Long-T ime Inverse/ Short-T ime Inverse IAC extremely/very/normally/moderately inverse ANSI extremely/very/normally/moderately inverse I2t Def inite time Rectif ier curve User Curve -...
Page 284
D-28F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: D.2 Factory default conf iguration NOTE: SOURCE COLUMN: This columns allow selecting the simple or complex (OR signal or Virtual output) operand that actives the selected elements on relay configuration If more than one operands are selected, the relay performs an OR gate with them to activate the selected element. SIGNAL LOGIC COLUMN: Refers to each individual signal selected on its left. NOT...
Page 285
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-29 SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC LED RESET INPUTOPERATION BIT 3 CHANGE LOCAL-REMOTENot Conf igured CHANGE OP BLOCKED Not Conf igured HMI BACKLIGHT ON Not Conf igured HMI BACKLIGHT OFF Not Conf igured PH IOC1 HIGH A BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 A OP NOT LATCHED VIRT IP 1 PH IOC1 HIGH B BLK GROUP 1 BLOCKED CONT...
Page 286
D-30F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: PH IOC1 LOW B BLKGROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 B OP NOT LATCHED VIRT IP 2 PH IOC1 LOW C BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 C OP NOT LATCHED VIRT IP 2 PH IOC2 LOW A BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 A OP NOT LATCHED VIRT IP 2 PH IOC2 LOW B BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 B OP NOT LATCHED VIRT IP 2 PH...
Page 287
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-31 GROUND IOC3 BLOCKGROUP 3 BLOCKED CONT IP_F_CC5 (50G BLOCK)(CC5) GROUND DIR3 OP NOT LATCHED VIRT IP 3 SENS GND IOC1 BLK GROUP 1 BLOCKED SENS GND DIR1 OP NOT LATCHED VIRT IP 4 SENS GND IOC2 BLK GROUP 2 BLOCKED SENS GND DIR2 OP NOT LATCHED VIRT IP 4 SENS GND IOC3 BLK GROUP 3 BLOCKED SENS GND DIR3 OP NOT LATCHED VIRT IP 4 PH TOC1 HIGH A BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 A OP NOT LATCHED...
Page 288
D-32F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: PH TOC3 HIGH C BLKGROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 C OP NOT LATCHED VIRT IP 5 NEUTRAL TOC1 BLOCK GROUP 1 BLOCKED NEUTRAL DIR1 OP NOT NEUTRAL TOC2 BLOCK GROUP 2 BLOCKED NEUTRAL DIR2 OP NOT NEUTRAL TOC3 BLOCK GROUP 3 BLOCKED NEUTRAL DIR3 OP NOT GROUND TOC1 BLOCK GROUP 1 BLOCKED CONT IP_F_CC6 (51G BLOCK)(CC6) GROUND DIR1 OP NOT LATCHED VIRT IP 7 GROUND TOC2 BLOCK GROUP 2 BLOCKED CONT...
Page 289
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-33 PHASE DIR3 BLK INPGROUP 3 BLOCKED CONT IP_F_CC4 (67P BLOCK)(CC4) LATCHED VIRT IP 9 NEUTRAL DIR1 BLK INP GROUP 1 BLOCKED NEUTRAL DIR2 BLK INP GROUP 2 BLOCKED NEUTRAL DIR3 BLK INP GROUP 3 BLOCKED GROUND DIR1 BLK INP GROUP 1 BLOCKED LATCHED VIRT IP 10 GROUND DIR2 BLK INP GROUP 2 BLOCKED LATCHED VIRT IP 10 GROUND DIR3 BLK INP GROUP 3 BLOCKED LATCHED VIRT IP 10 NEUTRAL OV1 HIGH BLK GROUP 1 BLOCKED LATCHED VIRT IP 12...
Page 290
D-34F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: ISOLATED GND2 BLKGROUP 2 BLOCKED SENS GND DIR2 OP NOT ISOLATED GND3 BLK GROUP 3 BLOCKED SENS GND DIR3 OP NOT SENS GND DIR1 BLK IP GROUP 1 BLOCKED SENS GND DIR2 BLK IP GROUP 2 BLOCKED SENS GND DIR3 BLK IP GROUP 3 BLOCKED FWD PWR1 BLOCK GROUP 1 BLOCKED FWD PWR2 BLOCK GROUP 2 BLOCKED FWD PWR3 BLOCK GROUP 3 BLOCKED PH TOC1 LOW A BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 A OP NOT LATCHED VIRT IP...